The Schneider GV3P50 motor circuit breaker is an ideal choice for protecting 22kW three-phase motors. Featuring thermal-magnetic tripping, an adjustable current range of 37–50A, a breaking capacity of 100kA and IP20 ingress protection rating, it is widely deployed in industrial automation, fluid conveyance, building facilities and other sectors. Key points: match breaker rating to motor power and operating conditions; avoid non-recommended applications including DC circuits, high-frequency starting and high-altitude environments. Combined with contactors and auxiliary contacts, it forms a complete motor protection and control system.
| Segmento di codice | Definizione | Descrizione dettagliata |
| GV3 | Serie di prodotti | TeSys GV3 range motor circuit breakers for three-phase motor protection |
| P | Tipo di prodotto | Standard thermal-magnetic trip unit with rotary knob operation |
| 50 | Corrente nominale | Max adjustable trip current 50A; thermal trip setting range: 37–50A |
| Modello completo | GV3P50 | 3-pole thermal-magnetic motor breaker, 37–50A, EverLink BTR screw terminals, IP20 |
| Codice ordine | FD6887 | Schneider official standard part number |
- Core Technical Specification Table
| Categoria dei parametri | Dati tecnici | Osservazioni |
| Parametri di base | ||
| Configurazione del palo | 3P (3-palo) | For three-phase AC circuits |
| Tipo di viaggio | Thermal-Magnetic | Combines thermal overload protection & magnetic short-circuit protection |
| Modalità operativa | Rotary Knob Control | Manual switching with ON/OFF marking |
| Terminazione | EverLink BTR screw-clamp terminals | Fast wiring to reduce loose connection risks |
| Parametri Elettrici | ||
| Thermal Trip Adjustment | 37–50A | Compatible with motors of different rated powers |
| Tensione operativa nominale (Ui) | 690V e | 50/60Hz |
| Tensione di isolamento nominale (Ue) | 690V e | Conforme alla norma CEI 60947-2 |
| Corrente operativa nominale (Cioè) | 50UN | Maximum continuous operating current |
| Corrente di intervento magnetico | 700UN | Short-circuit instantaneous tripping value |
| Capacità di interruzione massima (terapia intensiva) | 100IL | A 400 V |
| Matched Motor Rating | 22kW@400V | For three-phase asynchronous motors |
| Meccanico & Parametri Ambientali | ||
| Protezione dall'ingresso | IP20 | Finger-touch safe against live components |
| Montaggio | Montaggio su guida DIN | Standard 35mm top-hat rail |
| Peso | ca. 0.45kg | Installazione semplice & trasporto |
| Temperatura operativa | -25°C~+60°C | Suitable for most industrial environments |
| Temperatura di conservazione | -40°C~+85°C | Wide storage temperature range |
| Certificazioni | ||
| Main Approvals | CE, UL, CSA, CCC, EAC | Globally certified per international standards |
| Eco Certifications | RoHS, PORTATA | EU-compliant environmentally friendly design |
III. Full GV3P Series Model List
| Modello | Thermal Trip Range | Matched Motor Power @400V | Corrente di intervento magnetico | Codice ordine |
| GV3P40 | 25–40A | 18.5kW | 600UN | FD6886 |
| GV3P50 | 37–50A | 22kW | 700UN | FD6887 |
| GV3P65 | 48-65A | 30kW | 800UN | FD6888 |
| GV3ME50 | 37–50A | 22kW | 700UN | FD6890 |
| GV3ME65 | 48-65A | 30kW | 800UN | FD6891 |
| GV3ME80 | 56–80A | 37kW | 1000UN | FD6892 |
| GV3ME100 | 70–100A | 45kW | 1200UN | FD6893 |
- Alternative Cross Reference (Modelli sostitutivi)
- In-house Schneider Replacement
| Modello originale | Sostituzione | Descrizione |
| GV3P50 | GV3ME50 | Identical performance; ME is enhanced version with better accessory compatibility |
| GV3P50 | New production GV3P50 | No functional change, only production batch update |
- Equivalenti cross-brand
| Marca | Modello equivalente | Matching Grade | Vantaggi |
| ABB | MS132-50 | ★★★★★ | Stessa valutazione attuale, interchangeable mounting dimension |
| Siemens | 3RV2031-4KA10 | ★★★★☆ | Thermal-magnetic trip, fits 22kW motors |
| Eaton | PKZM0-50 | ★★★★☆ | 3-progettazione del palo, 100potere di interruzione kA |
| Cinto | NDM2-63M/3300 | ★★★☆☆ | Cost-effective for bulk replacement |
| Delizioso | CDM1-63M/3300 | ★★★☆☆ | Well-known domestic brand with high cost-performance |
- Ambienti applicativi & Field Cases
- Applicazioni consigliate
Automazione industriale: Sovraccarico & short-circuit protection for 3-phase asynchronous pumps, fans and compressors
Manufacturing: Production line motor control & machine tool protection
Building Electrical: Central air-conditioning & fire-fighting pump control
Energy Sector: Front-end protection for small generator sets and inverters
Infrastrutture: Wastewater treatment equipment & bulk material conveying systems
- Non-Recommended Applications
DC Circuits: Designed exclusively for AC; abnormal tripping characteristics under DC supply
Ultra-Frequent Cycling: Not applicable for >30 starts per hour (accelerates trip unit aging)
High Altitude: Derating mandatory above 2000m elevation
Corrosive Atmosphere: No anti-corrosion coating; unsuitable for strong acid/alkali surroundings
- Casi applicativi tipici
Caso 1: Fan System Protection for Food Processing Plant
Attrezzatura: 3×22kW centrifugal fans, 380V/50 Hz
Soluzione: GV3P50 + LC1D65 contactor combination
Risultato: Tripla protezione contro il sovraccarico, cortocircuito & perdita di fase; equipment failure rate reduced by 40%
Caso 2: Submersible Sewage Pump Control at Wastewater Plant
Attrezzatura: 4×22kW submersible sewage pumps, 380V/50 Hz
Soluzione: GV3P50 + contatti ausiliari + PLC interlock control
Risultato: Full motor protection plus remote monitoring, lower maintenance expense
- Air Shipment Compliance & Certificazione CE
- Conformità del trasporto aereo
UN38.3: Non richiesto; no built-in lithium battery or supercapacitor inside
Shipping Class: General commodity without special transport restriction
Imballaggio: Standard industrial carton to avoid transit damage
Shipping Document: Copy of CE certificate + RoHS compliance declaration available
- Dettagli sulla certificazione CE
Standard applicabili: CEI 60947-2 (LV switchgear) & CEI 60947-4-1 (motor control equipment)
Valid Region: European Economic Area (EEA) & global territories accepting CE marking
Validità: Permanently valid complying with current normative requirements
Inchiesta: Check Schneider official website product page or certification database
VII. Risoluzione dei problemi comuni
| Sintomo di guasto | Probable Causes | Remedial Actions |
| Frequent thermal tripping | 1. Sovraccarico del motore | 1. Inspect motor load |
| 2. Underset trip current | 2. Adjust rotary knob to correct setting | |
| 3. Excess ambient temperature | 3. Improve ventilation or derate operating current | |
| Unable to close | 1. Tripping latch not reset | 1. Toggle knob OFF then ON to reset |
| 2. Short circuit in wiring | 2. Troubleshoot short-circuit faults | |
| 3. Inceppamento meccanico | 3. Clean or replace breaker | |
| No protection upon phase loss | 1. Cablaggio errato | 1. Recheck three-phase cabling |
| 2. Damaged trip unit | 2. Replace trip component | |
| 3. Severe 3-phase unbalance | 3. Balance connected loads | |
| Terminali surriscaldati | 1. Terminali allentati | 1. Retighten terminal screws |
| 2. Undersized cable | 2. Upgrade to proper wire gauge | |
| 3. Terminal oxidation | 3. Clean terminals or replace unit |
VIII. Sizing Guidelines & Regole di selezione rapida
Quick Selection Formula Summary
> GV3P series 3-pole thermal-magnetic breakers;
> Suffix number denotes upper current limit;
> 40 = 25–40A, 50 =37–50A, 65 max at 65A;
> Power matching rule: 40 for 18.5kW, 50 for 22kW, 65 for 30kW.
Regole veloci
- Corrispondenza attuale: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
- Power Reference: A 400 V, GV3P50 matches 22kW motor (~44A nominal)
- Accessory Option: Contatto ausiliario: GV3AE11 (1NA+1NC) / GV3AE20 (2NO)
- Spaziatura di montaggio: DIN rail install; ≥10mm clearance for heat dissipation, away from heat-generating devices
- Installazione & Istruzioni di cablaggio
- Passaggi di installazione
Confirm standard 35mm DIN rail
Snap breaker firmly onto rail
Incoming power: top-feed or bottom-feed acceptable
Motor cable connection: terminal tightening torque 2.5Nm recommended
- Specifiche di cablaggio
Wire cross-section range: 1.5mm² min ~35mm² max
terminale: EverLink BTR screw terminal compatible with copper/aluminum conductors
Phase marking: R/S/T corresponds to L1/L2/L3; no neutral connection (3P without N pole)
- EMC Protection
Maintain ≥50mm clearance between breaker and contactors
Separate control wiring from power cables to avoid cross-interference
Install EMC filter if needed for EMI suppression
Full Application Overview for Schneider GV3P50 Motor Circuit Breaker
- Core Application Summary
Schneider GV3P50 is a 3-pole thermal-magnetic motor circuit breaker with adjustable trip 37–50A, rated for 22kW three-phase asynchronous motors @400V. Its core functions: motor overload, cortocircuito & phase-loss protection plus manual switching, widely used in below industries:
- Detailed Application Classification
- Automazione industriale & Manufacturing
| Applicazione | Attrezzatura | Requisito di protezione | Application Benefit |
| Production Line Control | Trasportatori, sorters, macchine confezionatrici | Continuous running protection against overload shutdown | Improve line stability & reduce breakdown loss |
| Macchine utensili | Milling, lathe & grinder spindle motors | Protection for frequent start-stop & instant short-circuit breaking | Protect costly equipment and extend service life |
| Bulk Handling | Bucket elevators, trasportatori a coclea | Stall & phase-loss protection | Prevent burnout & cut maintenance cost |
| General Machinery | Stampa, tessile & plastic processing machines | Protezione da sovraccarico + emergency manual cut-off | Simplify control circuit & enhance operational safety |
- Fluid Conveyance Systems
| Applicazione | Attrezzatura | Protection Feature | Typical Parameter |
| Pump Set | Industrial pump, fire pump, sewage pump | Dual overload + phase-loss protection, resistente all'umidità | 22kW/380 V,50Hz, setting 37–50A |
| Fan Unit | Centrifugal/axial/induced draft fans | Light-load startup protection against impeller jamming | Adapt to current fluctuation from variable duct resistance |
| Compressore | Aria & compressori frigoriferi | Heavy-start & overheat protection | Tolerate frequent loading/unloading cycles |
| Vacuum Pump | Industriale & water-ring vacuum pumps | Low-current idle-running damage prevention | Adjustable setting for light-load operation |
- Edificio & Municipal Infrastructure
| Sector | Sistema | Key Demand | Metodo di montaggio |
| HVAC | Central air-con, air handler, cooling tower | Stable continuous-duty protection | DIN rail mounted with contactor interlock |
| Automazione degli edifici | Fire control, security & elevator room equipment | Emergency cut-off safety | Remote monitoring via PLC |
| Wastewater | Aerator & sludge processing units | Polvere & moisture resistance | Cabinet installation with IP20 protection |
| New Energy | Small gen-set & PV inverter | Sovracorrente & grid-fault isolation | Rated up to 690V high-voltage system |
- Other Industrial Sectors
| Industria | Attrezzatura | Special Requirement | Matching Advantage |
| Agricoltura | Irrigation pump & feed processor | Outdoor installation against grid voltage swing | Wide operating temp: -25°C~+60°C |
| Estrazione mineraria | Small conveyor & mine ventilation fan | Heavy startup + elevata tenuta al cortocircuito | 100kA elevato potere di interruzione |
| Cibo & Bevanda | Mixer & sterilization equipment | Sanitary & easy-clean layout | No exposed live parts for hygiene compliance |
| Pharma | Farmaceutico & cleanroom machinery | Precise control & basso tasso di fallimento | High accuracy thermal-magnetic trip characteristic |
III. Non-Recommended Applications (Avoidance Guide)
| Unsuitable Condition | Motivo | Alternative Solution |
| DC Circuit | Abnormal tripping characteristic under DC (rated only AC 50/60Hz) | Dedicated DC-rated Schneider circuit breakers |
| >30 Starts/Hour | Accelerated trip unit ageing & shortened service life | GV3ME enhanced series or match with soft starter |
| Altitude>2000m | Performance derating required | High-altitude specified breaker or add upstream protection |
| Strong Corrosive Atmosphere | Uncoated terminals prone to oxidation | Anti-corrosion coated model or protective enclosure |
| Explosion Hazard Zones | Standard version without ATEX certification | ATEX certified explosion-proof breakers |
| Single-Phase Motors | 3-pole structure cannot provide single-phase protection | GV2 single-phase motor breaker series |
- Detailed Field Application Cases
Case1: 22kW Fan Protection in Food Factory
Setup: 3×22kW centrifugal fans 380V/50Hz, independent control per unit
Schema: GV3P50 + LC1D65 contactor + GV3AE11 auxiliary contact
Logica: Manual/Auto switch; auto stop & alarm upon overload
Risultato: Triple protection realized; failure rate -40%, maintenance cost -30%
Case2: Submersible Sewage Pump Control at WWTP
Setup: 4×22kW submersible sewage pumps 380V/50Hz, alternating operation
Schema: GV3P50 + PLC interlock + level transducer
Condizione: Humid environment, 10~15 starts/hour frequent cycling
Risultato: Anti-stall burnout + remote auto-switching, improved system reliability
Case3: Central Air-conditioning for Shopping Mall
Setup: 3×22kW chilled water pumps with VFD control 380V/50Hz
Schema: GV3P50 + inverter + temperature sensor
Caratteristica: Speed auto-adjust by return water temp; coordinated protection by inverter + breaker under overload
Risultato: ≥30% energy saving, service life doubled, superior system stability
- Recommended Matching Components & Suggerimenti per la selezione
- Recommended Matching List
| Accessorio | Parte n. | Funzione | Valore |
| Contattore CA | LC1D65 | Remote control for frequent start-stop | Enable automatic control & reduce manual operation |
| Contatto ausiliario | GV3AE11 | 1NO+1NC signal output | Alarm feedback or PLC interlock |
| Relè di sovraccarico termico | LRD4363 | Optional secondary overload protection | Double motor protection for enhanced safety |
| Control Pushbutton | Serie XB4 | Manual start/stop | HMI & emergency shutdown function |
- Sizing Rules
- Power Match: 22kW (~44A @400V) optimally paired with GV3P50 (37–50A)
- Trip Setting: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
- Mount Clearance: ≥50mm gap to adjacent contactors; ≥10mm free space for heat dissipation
- Coppia di cablaggio: Cable terminal tightening torque fixed at 2.5Nm
- Ambient Derate: Declassare 1% rated current per every 1°C rise above +40°C ambient temperature