Contattore Schneider LC1E1801

Model code explanation: LC1E = TeSys E series contactor; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 contatto normalmente chiuso (1NC) ⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, fully compatible in mounting, terminal layout and performance. Key Specifications Main ...

  • Dettagli del prodotto

Model code explanation: LC1E = TeSys E series contattore; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 contatto normalmente chiuso (1NC)

⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, fully compatible in mounting, terminal layout and performance.

Specifiche chiave

Contatti principali: 3P, 3NO

AC-3 (motor duty): 18A@400V; AC-1 (carico resistivo): 25UN

Potenza del motore: 7.5kW @ 380/400V; 4kW @ 220V; 9kW @ 440V

Tensione di isolamento Ui: 690V; Tensione di tenuta ad impulso Uimp: 6kV

Contatto ausiliario: 1NC (Normalmente chiuso)

Montaggio: Guida DIN / base plate screw mounting

Dimensioni complessive: W45mm × H74mm × D80mm, net weight ≈0.3kg

Classe di protezione: IP20; Temperatura operativa: -5~+55℃; No derating up to 3000m altitude

Vita meccanica: 10 milioni di operazioni; Vita elettrica AC-3: 1.2 milioni di operazioni; Frequenza operativa massima: 1800 cicli/ora

Coil suffix definitions (complete model number)

LC1E1801B5: AC24V, 50Hz

LC1E1801F5: AC110V, 50Hz

LC1E1801M5: AC220V, 50Hz (most common in China)

LC1E1801Q5: AC380V, 50Hz

Suffisso 7 = 50/60Hz universal; suffisso 6 = 60Hz only

Consumo energetico della bobina (M5 220V example)

Inrush VA: 95VA; Sealed holding VA: 8.5VA; Coil heat dissipation: 2~3W

Tensione di eccitazione: 0.85~1.1Uc; Tensione di caduta: 0.3~0.6Uc

Coppia di serraggio & calibro del filo

Torque for main circuit and control circuit terminals: 1.2 N·m

Filo pieno: 1.5~6mm²; Filo intrecciato (con ghiera): 1~4mm²

Matching selection reference

Relè di sovraccarico termico abbinato: LRD07 / LRN07 (current range suitable for 18A)

Accessori: LA1EN auxiliary contact block, LA9D coil surge suppressor, mechanical interlock block

Alternativa domestica: CJX2-1801 (similar outline, pay attention to mounting hole and marking differences)

Guida alla risoluzione dei problemi

  1. Coil energized but no pull-in: Check if coil voltage is within 0.85~1.1Uc; inspect broken coil wire and loose terminals
  2. Pulled in but main circuit no continuity: Main contact erosion, saldatura a contatto, cablaggio allentato
  3. Buzzing / chiacchierando: Sottotensione, large harmonic distortion, dust accumulated on core faces
  4. Failed to drop out after power-off: Welded main contacts, core stuck by oil and dirt

Detailed Installation Procedure for Schneider LC1E1801 Contactor

⚠️ Safety precondition: Operated by qualified electricians; cut off all power supply and verify zero voltage before installation. LC1E1801: 3P main contacts with built-in 1NC auxiliary contact. Marcatura del terminale: Main circuit L1/L2/L3 (line side, incoming), T1/T2/T3 (lato di carico, outgoing); Coil A1, A2; Contatto ausiliario: 95, 96 (1NC)

  1. Preparazione pre-installazione
  2. Verificare la tensione della bobina: LC1E1801M5=AC220V, Q5=AC380V, F5=AC110V. Coil rated voltage must match control circuit voltage to avoid coil burnout.
  3. Ispezione visiva: No shell cracks, intact terminals, armature moves freely without jamming when pressed manually.
  4. Utensili: 2 Cacciavite a croce, spelafili, multimetro, chiave dinamometrica; 35mm standard DIN rail or mounting base plate.
  5. Wire specification

Main circuit solid wire: 1.5~6mm²; Stranded wire with ferrule: 1~4mm²

Circuito di controllo (A1/A2, contatti ausiliari): 0.75~1.5mm²

Coppia di serraggio: 1.2 N·m (avoid over-tightening to prevent thread stripping, or loose connection causing overheating)

  1. Environmental check: Cabinet temperature -5℃~+55℃, keep away from dust, moisture and oil. Mount vertically upright. Do NOT install upside down or horizontally.
  2. Fissaggio (2 methods: Guida DIN / base plate screw mounting)

Metodo 1: 35Montaggio su guida DIN da mm (preferito)

  1. The contactor has upper hooks and a spring locking clip at the bottom.
  2. Hook the upper notch onto the top edge of the DIN rail first.
  3. Press the bottom of the contactor down until you hear a click, the bottom clip locks onto the rail.
  4. Shake lightly to confirm firm fixation. Rimozione: Use a flat screwdriver to pry down the bottom clip and pull out the contactor.

Metodo 2: Screw mounting on insulated base plate (no rail)

  1. Mark and drill holes on the insulated plate according to the rear mounting holes (for M4 screws).
  2. Insert screws diagonally, pre-tighten, then torque evenly in diagonal sequence; do not force one side to avoid casing deformation.
  3. Accessory Fitting (Opzionale: LA1EN auxiliary block, mechanical interlock etc.)
  4. Top auxiliary contact block: Align with the slots on top of contactor, push vertically down until latched.
  5. Thermal relay LRD/LRN: Clip directly underneath the contactor, align positioning slots; the linkage will engage automatically.
  6. Surge suppressor LA9D: Clip beside coil terminals A1/A2, absorbs back EMF to protect PLC output points.
  7. Wiring Sequence (Main circuit → Auxiliary contacts → Coil control circuit)

Standard routing: Line side on top, load side on bottom. L1/L2/L3 on top for three-phase supply; T1/T2/T3 at bottom for load (motore).

  1. Cablaggio del circuito principale

Strip insulation 5~6mm, avoid loose copper strands; ferrules are mandatory for stranded wire.

Keep phase sequence L1→T1, L2→T2, L3→T3 as per drawing.

Torque screws to 1.2N·m; only one conductor per terminal.

  1. Built-in auxiliary contact (95-96, NC)

Terminali 95-96: Conductive when coil de-energized, open when contactor pulls in. Usually used in stop circuit or fault feedback for motor control.

If NO contact is required, add LA1EN auxiliary block.

  1. Coil A1, A2 (circuito di controllo)

A1 and A2 have no polarity for AC. For AC220V: one to live, one to neutral; for AC380V: connect to two different phases.

Wire in series with start/stop pushbuttons, thermal relay NC contact or PLC outputs.

Route control wires separately from power cables to reduce interference.

Terminal summary:

L1/L2/L3 (Supply In), T1/T2/T3 (Load Out), A1 A2 (Bobina), 95-96 (Built-in 1NC)

  1. Ispezione pre-accensione
  2. Controllo visivo: All terminals tightened, no exposed copper, no short circuit risk, no loose strands touching adjacent terminals.
  3. Continuity test with multimeter:

De-energized state: No continuity between L-T; 95-96 auxiliary contact is conductive.

Manually press armature to simulate pull-in: L-T becomes conductive, 95-96 si apre.

  1. Double-check coil voltage; separate power supply for main circuit and control circuit.
  2. Messa in servizio all'accensione
  3. Energize control circuit only, keep main power off: Press start button, contactor should pull-in smoothly without chattering or buzzing; release stop button for reliable drop-out.

Chiacchiere: Bassa tensione di alimentazione, loose wiring or dirty core surfaces.

  1. After control circuit test passes, energize main circuit and run on load.
  2. Temperature check after 10min running: No obvious overheating at terminals (temperature rise indicates poor connection).
  3. Note di installazione & Divieti
  4. Keep minimum clearance ≥10mm between contactor and fuse / MCB for heat dissipation.
  5. Minimum spacing ≥5mm between multiple contactors; increase spacing for high ambient temperature.
  6. Do not plug or remove auxiliary blocks when energized.
  7. Do not trap wire insulation inside terminal clamps; copper must be fully clamped.
  8. LC1E discontinued, spare replacement: LC1N1801, same mounting size and terminal definition.
  9. Common Installation Faults

No pull-in after energized: Wrong A1/A2 voltage, broken control wire or open button circuit

Buzzing when pulled in: Sottotensione, dust or rust on magnetic core faces

Cannot drop out after power cut: Welded main contacts or core jammed by oil

Schneider Easy TeSys E (LC1E / EasyPact TVS) Series Full List

Nota importante: LC1E series fully discontinued in July 2020. Sostituzione diretta: LC1N series, dimensioni di montaggio e disposizione dei terminali identiche.

Regola modello: LC1E + current code + auxiliary contact code (10=1NO; 01= 1 NC) + coil suffix

Coil suffix description:

B5=AC24V 50Hz; F5=AC110V 50Hz; M5=AC220V 50Hz; Q5=AC380V 50Hz

B7/F7/M7/Q7=50/60Hz universal; BD=24 V CC; 6=60Hz only

  1. 3P LC1E Contactors (AC-3 @400V)
Modello baseCorrente AC-3Motor Rating @400VBuilt-in Auxiliary Contact
LC1E06106UN2.2kW1NO
LC1E06016UN2.2kW1NC
LC1E09109UN4kW1NO
LC1E09019UN4kW1NC
LC1E121012UN5.5kW1NO
LC1E120112UN5.5kW1NC
LC1E181018UN7.5kW1NO
LC1E180118UN7.5kW1NC (your referenced model)
LC1E251025UN11kW1NO
LC1E250125UN11kW1NC
LC1E321032UN15kW1NO
LC1E320132UN15kW1NC
LC1E381038UN18.5kW1NO
LC1E380138UN18.5kW1NC
LC1E401140UN18.5kW1NA+1NC
LC1E501150UN22kW1NA+1NC
LC1E651165UN30kW1NA+1NC
LC1E801180UN37kW1NA+1NC
LC1E951195UN45kW1NA+1NC
LC1E120120UN55kWNessun integrato, add auxiliary block separately
LC1E160160UN75kWNessun integrato, add auxiliary block separately
LC1E200200UN90kWNessun integrato, add auxiliary block separately
LC1E300300UN160kWNessun integrato, add auxiliary block separately

Example complete model: LC1E1801M7 = 18A, 1NC, AC220V 50/60Hz universal

  1. Matching LRE Thermal Overload Relays (plug-on fit for LC1E)

LRE01N~LRE35N (for 06~38A); LRE322N~LRE365N (for 40~300A)

LRE01N: 0.1~0.16A

LRE02N: 0.16~0.25A

LRE03N: 0.25~0.4A

LRE04N: 0.4~0.63A

LRE05N: 0.63~1A

LRE06N: 1~1,6 A

LRE07N: 1.6~2,5 A

LRE08N: 2.5~4A

LRE09N: 4~6A

LRE10N: 6~10A

LRE12N: 10~16A

LRE14N: 16~24A

LRE16N: 24~36A

LRE21N: 28~36A

LRE22N: 36~48A

LRE322N: 55~70A

LRE323N: 63~80A

LRE353N: 80~104A

LRE355N: 104~135A

LRE365N: 130~165A

  1. E-series Accessories
  2. LA1EN: Top-mounted auxiliary contact block (1NO / 1NC, stackable)
  3. LAEM1: Modulo di interblocco meccanico (for two contactor interlocking)
  4. LA9D: Soppressore di picchi della bobina (RC network / varistore, PLC output protection)
  5. LAEB1N / LAEB3N: Thermal relay independent base (when not mounted under contactor)
  6. LA1EBN: Timed auxiliary contact block (in ritardo / ritardo di disattivazione)
  7. 2P / 4P LC1E (single phase, illuminazione & carico resistivo, Servizio AC-1)

LC1E0920: 2P 9A

LC1E2520: 2P25A

LC1E0940: 4P 9A

LC1E2540: 4P25A

LC1E4040: 4P 40A

4P versions commonly used for HVAC, lighting and heating resistive loads

  1. Cross Reference Table
Old LC1E ModelDirect Replacement LC1N
LC1E0601/0610LC1N0601 / LC1N0610
LC1E0901/0910LC1N0901 / LC1N0910
LC1E1201/1210LC1N1201 / LC1N1210
LC1E1801/1810LC1N1801 / LC1N1810
LC1E2501/2510LC1N2501 / LC1N2510
LC1E3201/3210LC1N3201 / LC1N3210
LC1E3801/3810LC1N3801 / LC1N3810
LC1E40~95LC1N40~95