The IP8000 is a classic SMC mechanical E/P electro-pneumatic positioner (non-smart, no HART). It is designed for linear-stroke pneumatic diaphragm actuators. It receives a 4~20mA current signal and converts it into supply air pressure to drive valvole di controllo. It replaces the older IP6000 series. The IP8100 in the same series is for rotary-stroke applications. The IP8001/IP8101 are smart versions with auto-tuning and share the same housing.
✅ Specifiche tecniche principali
| Articolo | IP8000 (Tipo di leva) |
| Input Signal | DC 4~20mA, Resistenza in ingresso: 235±15Ω |
| Supply Air Pressure | 0.14~0.7 MPa |
| Applicable Stroke | 10~85mm (linear valve stem) |
| Precisione | Sensitivity ≤0.1%FS; Linearità ±1%FS; Hysteresis ≤0.75%FS; Ripetibilità ±0,5%FS |
| Protezione dall'ingresso | IP65 (IEC60529) |
| Temperatura ambiente | -20~80℃ for standard model; ExdⅡBT5 explosion-proof: -20~60℃ |
| Air Ports | RC1/4 / G1/4 / 1/4TNP; Gauge port Rc1/8 |
| Collegamento elettrico | G1/2, M20×1,5, 1/2NPT optional |
| Resistenza alle vibrazioni | No resonance within 5~200Hz |
| Mounting Standard | Compliant with NAMUR, DIN/IEC 60534-6-1 parentesi |
📌 Definizione del codice modello (IP8000-□□□)
IP8000: Lever-type mechanical electro-pneumatic positioner
- Pressure gauge specification: 0=0.3MPa, 3=1.0MPa
- Costruzione: Standard housing / ExdⅡBT5 explosion-proof terminal box
- Accessori: Restrictor pilot valve, yoke linkage, extended feedback lever, ecc.
- Thread type, Marcatura CE, special custom codes (per esempio. X310=IP66)
🛠 Working Principle & Linee guida per l'installazione
- Principio: A 4~20mA current energizes the torque motor. The nozzle-flapper amplifies the signal to control the output air pressure of the pilot valve. The feedback lever captures the actual valve stem position to form a closed loop, ensuring valve position matches the input signal.
- Key Installation Rule: A 50% segnale (12mA), the feedback lever should form a 90° right angle with the valve stem. Select the internal feedback spring according to single-acting or double-acting actuators.
- Regolazione: Mechanical Zero and Span knobs. Supports split range operation. Equipped with manual/auto switching screw for manual air supply during commissioning.
⚠️ Risoluzione dei problemi comuni
- Valve fails to move
No supply air or insufficient air pressure; 4~20mA wiring reversed; nozzle/restrictor blocked by dust; torque motor damaged.
- Oscillation / A caccia
Incorrect feedback lever mounting angle; unstable supply air pressure; stuck pilot valve; excessive friction of valve packing.
- Poor linearity / Deriva zero
Zero/span not calibrated; loose feedback linkage; air piping leakage; large ambient temperature variation.
- Insufficient output pressure
Foreign matter jamming pilot valve; leaking actuator diaphragm/cylinder; clogged air filter.
Maintenance Reminder: Interrompere l'alimentazione dell'aria e scaricare completamente la pressione prima dello smontaggio. Pulire l'orifizio dell'ugello con un filo sottile da 0,2 mm. Applicare leggermente grasso al silicone TORAY SH45 durante il montaggio degli O-ring.
📋 Selezione del modello & Alternative
IP8000: Meccanico, leva a corsa lineare. Per valvole di controllo convenzionali, basso costo, nessuna comunicazione.
IP8100: Meccanico, camma rotante, per valvole a farfalla e a sfera.
IP8001: Corsa lineare intelligente. Calibrazione automatica, HART, diagnosi dei guasti, sostituzione dell'aggiornamento per IP8000.
Alternative domestiche: Posizionatori E/P domestici come Wuzhong e Chuanyi. Verifica staffa, corrispondenza della porta dell'aria e della corsa.
📎 Scenari applicativi tipici
Regolazione continua del flusso, pressione e livello su valvole di controllo pneumatiche lineari a membrana nel settore chimico, trattamento dell'acqua, HVAC, carta, olio & gasdotti. Sono disponibili versioni antideflagranti ExdⅡBT5 per aree pericolose.
Posizionatore della valvola elettropneumatico SMC IP8000: scenari applicativi
The IP8000 is a linear-stroke mechanical E/P positioner matching diaphragm linear pneumatic control valves. It converts 4~20mA analog signal into air pressure to drive valve stem for continuous process regulation. No HART communication.
🏭 Industry Applications
- Acqua / Trattamento delle acque reflue
Inlet flow regulation, pH dosing line, liquid level control, aeration pressure regulation. Standard non-explosion model is sufficient; IP65 preferred for outdoor installation.
- HVAC & Heating Networks
Temperature control for primary/secondary side of heat exchangers, regulating steam/hot water linear control valves.
- Industria della carta
Pulp concentration control, white water flow, steam pressure regulation. Dust-prone workshop; air filtration is mandatory to prevent nozzle blockage.
- Industria chimica (Use ExdⅡBT5 explosion-proof IP8000 for hazardous zones)
Regolazione continua del flusso, pressure and level in process pipelines. Custodia antideflagrante richiesta per aree pericolose contenenti solventi e idrocarburi leggeri.
Nota: IP8000 è meccanico senza diagnosi intelligente. Utilizzare IP8001 se sono richiesti HART e la sintonizzazione automatica.
- Cibo & Bevanda / Farmaceutico (Servizio Sanitario)
Acqua purificata, regolazione acqua di lavaggio e vapore, abbinato a valvole di controllo lineare sanitario. Preferire l'aria pulita dello strumento.
- Energia & Centrali termoelettriche
Acqua di alimentazione della caldaia, desurriscaldamento e riduzione della pressione, controllo del livello della condensa; valvole ausiliarie di controllo del processo.
- Olio & Stoccaggio del gas & Trasporti (Versione antideflagrante)
Regolazione della pressione e del flusso per condotte di greggio/prodotti, controllo del livello del serbatoio. Modello antideflagrante Exd per aree pericolose esplosive.
✅ Tipi di valvole adatti
A semplice effetto / valvole di controllo pneumatiche a membrana lineare a doppio effetto (migliore corrispondenza)
Valvole guidate a gabbia, valvole a singola sede, valvole di controllo a gabbia
❗Valvole a farfalla, le valvole a sfera e altre valvole rotative richiedono IP8100, IP8000 non è applicabile.
📌 Application Characteristics
Tipo di controllo: Continuous modulating (not on/off valve). 4~~20mA corresponds to 0~~100% valve travel.
Air source: Pulito, Asciutto, oil-free compressed air. Air filter regulator (AFR) must be installed upstream.
Vantaggi: Struttura semplice, facile manutenzione, good anti-EMI performance. Suitable for sites without bus communication requirements and limited budget.
Limitazioni: Feedback meccanico, no auto-calibration. Manual zero and span adjustment required; no fault diagnosis.
❌ Scenari non consigliati
- Severe oscillation, strong corrosive gas (extra housing protection required).
- Diagnosi remota, HART communication, auto-tuning required → upgrade to IP8001.
- Rotary butterfly / ball valves → select IP8100.
- Polvere pesante, unpurified instrument air (high risk of nozzle clogging).
SMC IP8000 — Selection Checklist
Applicable to IP8000 linear mechanical electro-pneumatic positioner; Use IP8100 for rotary applications; IP8001 smart model has separate selection rules.
- Attuatore & Valve Basic Information
| Controlla l'articolo | Requisiti di selezione & Osservazioni |
| Tipo di attuatore | Linear stroke diaphragm pneumatic actuator (single-acting / doppio effetto). Not for rotary butterfly/ball valves. |
| Valve Stem Stroke | 10~85mm; confirm actual stroke. Out-of-range travel invalid; too small stroke degrades feedback lever accuracy. |
| Actuator Action | □ Single-acting (ritorno primaverile), replace internal feedback spring inside positioner |
| □ Double-acting (no spring, bidirectional air supply), replace internal feedback spring | |
| Valve Type | Single-seat / cage / cage-guided modulating control valves; modulating service, not on/off valve |
| Stem Diameter & Mount Bracket | DIN/IEC 60534-6-1 / NAMUR standard. Verify feedback linkage and yoke accessories. Excessive stem wobble causes oscillation. |
- Processo & Condizioni operative
| Controlla l'articolo | Requisiti di selezione & Osservazioni |
| Process Media | Acqua, vapore, aria, general chemical fluids. Evaluate housing protection for highly corrosive media. |
| Explosion-proof Requirement | □ Standard non-explosion (safe area) |
| □ ExdⅡBT5 explosion-proof (zona pericolosa, limite di temperatura: -20~60℃; standard model -20~80℃) | |
| Temperatura ambiente | Standard: -20℃ ~ +80 ℃; A prova di esplosione: -20℃ ~ +60 ℃. Heat insulation required for over-temperature sites. |
| Protezione della custodia | IP65 standard; IP66 optional (suffix X310). IP65+ recommended for outdoor, ambienti umidi e polverosi. |
| Vibrazione | No resonance from 5~200Hz. Reinforce linkage under heavy vibration to avoid continuous hunting. |
| Control Requirement | 4~20mA analog continuous modulation; No HART, no auto-tuning. Manual zero/span calibration needed. |
- Air Supply System Check (Highest Failure Source)
| Controlla l'articolo | Requisiti di selezione & Osservazioni |
| Supply Pressure Range | 0.14~0.7 MPa. Stable pressure; pressure fluctuation easily triggers valve oscillation. |
| Air Quality | Asciutto, pulito, oil-free compressed air. Pre-install air filter regulator (AFR) to remove water, oil and dust. Dust environment easily clogs nozzle. |
| Air Port Thread | G1/4 / RC1/4 / 1/4TNP; gauge port Rc1/8. Confirm thread before ordering. |
- Electrical Check
| Controlla l'articolo | Requisiti di selezione & Osservazioni |
| Input Signal | DC 4~20mA; Resistenza d'ingresso 23515. Match signal source load capacity. |
| Electrical Entry | G1/2 / M20*1.5 / 1/2TNP. Explosion-proof model requires explosion-proof cable gland. |
| Cablaggio | 2-wire 4-20mA. Polarity matters; reversed polarity causes no operation. Shielded cable recommended for long distance, messa a terra single-end. |
- Selezione degli accessori ausiliari
□ Manometro: 0=0.3MPa, 3=1.0MPa (selezionare in base al campo di pressione di uscita)
□ Leva di feedback, yoke linkage (adattato alla corsa dell'attuatore)
□ Regolatore del filtro dell'aria, tubo dell'aria
□ Staffa di montaggio e dispositivi di fissaggio
□ Pressacavo antideflagrante (obbligatorio per i modelli antideflagranti)
- Criteri di esclusione (NON selezionare IP8000 se applicabile)
- Valvola rotativa (farfalla / Valvola a sfera a V) → utilizzare IP8100
- HART communication, diagnosi remota, è necessaria la regolazione automatica → utilizzare IP8001
- Fonte d'aria non purificata con polvere pesante, olio e condensa
- Corsa della valvola >85mm o <10mm
- Forte corrosione, forti vibrazioni da shock senza misure protettive
- Esempio di selezione (Riferimento al codice modello)
IP8000-3 (1.0Manometro MPa) + a prova di esplosione + Porta aerea G1/4 + Ingresso elettrico M20
IP8000-301: 1.0Manometro MPa, alloggiamento standard, gruppo leva standard
- Ispezione pre-installazione
- Tubazioni dell'aria completamente spurgate per rimuovere scorie e detriti di saldatura.
- Leva di feedback vicino a 90° a 50% segnale (12mA).
- Nessuna perdita sull'attuatore; packing friction shall not be excessive.
- Shielded cable grounding; separate routing from power cables to avoid VFD interference.
SMC IP8000 Electro-Pneumatic Valve Positioner — Maintenance Manual
Applicable to IP8000 mechanical linear E/P positioner; Pre-work safety: Disconnect 4~20mA signal, shut off air supply and vent pressure. Never open housing under pressure.
- Intervalli di manutenzione (Quotidiano / Trimestrale / Annuale)
1) Daily Routine Inspection (per shift / daily visual check)
- Check housing for air leakage, condensazione, corrosion and loose fittings.
- Observe two pressure gauges for stable readings; watch for fluctuation/hunting.
- Check valve stem movement: smooth travel, nessun grippaggio o rumore anomalo.
- Drain condensate from air filter regulator in a timely manner.
- Check mounting bracket, feedback linkage and bolts for looseness.
Warning sign: Gauge needle jumping continuously, valve hunting → inspect feedback mechanism or nozzle blockage first.
2) Manutenzione trimestrale (ogni 3 mesi)
- Ispezionare l'elemento filtrante del regolatore del filtro dell'aria; sostituire se contaminato.
- Controllare la leva di feedback, giogo e alberi dei perni: applicare una quantità minima di grasso (NON lubrificare eccessivamente! Il grasso in eccesso intrappola la polvere e ostruisce l'ugello).
- Stringere l'hardware: bulloni di montaggio del posizionatore, raccordi per tubi e morsettiere.
- Prova funzionale: ingresso 4 mA, 12mA, 20mA, registrare la deviazione dello zero e dello span.
- Ispezionare il cavo e il pressacavo; garantire che la tenuta sia intatta, nessuna penetrazione d'acqua.
3) Revisione annuale (una volta all'anno; ogni 6 mesi in condizioni difficili)
- Smontare l'unità, alloggiamento interno pulito, concentrarsi sull'ugello, valvola a cerniera e limitatore della valvola pilota (punto di fallimento più alto).
- Smontare e ispezionare gli O-ring; sostituire il kit completo di guarnizioni se invecchiato, indurito o rotto.
- Ispezionare la bobina del motore di coppia per individuare eventuali scolorimenti da surriscaldamento; controllare la distanza tra ugelli e lamelle.
- Ricalibrare lo zero e lo span, registrare i dati di calibrazione.
- Ispezionare il circuito respiratorio; sostituire i tubi invecchiati.
- Controllo aggiuntivo per versione antideflagrante: superficie del giunto di esplosione intatta, guarnizione intatta, conforme allo spazio ignifugo.
Servizio duro (polvere, umidità, acque reflue, carta): ridurre della metà gli intervalli di manutenzione.
- Manutenzione dei componenti chiave
✅ Ugello & Flapper (Fonte di errore più comune)
- Pulizia: Utilizzare un filo sottile di nylon/rame da 0,2 mm per pulire delicatamente l'orifizio dell'ugello. Non graffiare la superficie dell'ugello con filo di acciaio duro.
- Soffiare la polvere con aria compressa secca a bassa pressione (≤0,2MPa). Non lavare mai le parti interne del posizionatore con liquidi.
- Superficie della cerniera priva di graffi e contaminazioni d'olio. I graffi causano continue battute d'arresto; sostituire il gruppo ugello-deflettore.
- Requisito: L'aria dello strumento deve essere secca e priva di olio. Il velo d'olio sulla lamella dell'ugello provoca derive e oscillazioni.
✅ Gruppo leva di feedback
- Applicare solo una piccola quantità di lubrificante agli alberi dei perni e ai perni; nessun grasso pesante.
- Controllare il collegamento per eventuali deformazioni; nessun inceppamento durante il movimento dello stelo.
- A 50% segnale (12mA), la leva dovrebbe rimanere vicino a 90°. Readjust mounting if angle deviates largely.
✅ Seals (O-ring)
O-rings age and harden under large temperature fluctuation and continuous operation.
Apply thin layer of TORAY SH45 silicone grease when replacing O-rings, avoid over-application.
Prevent scratches on O-ring grooves during assembly.
✅ Electrical Section
- Inspect 4~20mA 2-wire terminals for oxidation and looseness; messa a terra single-end per cavo schermato.
- Explosion-proof model: power cut before cover removal. Do not damage flameproof mating surface; seal gasket and cable gland must remain sealed.
- Separate signal cables from power cables to avoid VFD interference.
- Long-Term Shutdown Preservation (Out of service >1 mese)
- Shut off air supply and vent pressure; disconnect 4-20mA signal.
- Set valve to mid-position (50% apertura) to reduce long-term single-side spring stress.
- Drain condensate from air filter.
- Cover housing for dust protection to avoid dust accumulation on nozzle-flapper.
- Purge air piping and re-calibrate zero & span before recommissioning.
- Operazioni vietate (Avvertenze importanti)
❌ Open positioner housing under pressure or powered condition
❌ Blast nozzle-flapper assembly with high-pressure compressed air
❌ Apply large amount of grease (traps dust and clogs nozzle)
❌ Flush internal parts with liquid (only wipe housing exterior with damp cloth)
❌ Force feedback lever; may deform torque motor and cam
❌ Use instrument air with oil, water and heavy contaminants
- Post-Maintenance Verification Procedure
Follow sequence after maintenance:
- Apply air supply, verify all air joints leak-free.
- Connect 4~20mA signal generator.
- 4mA → zero calibration; 20mA → span calibration; repeat 2~3 cycles.
- Test linearity at midpoint 12mA; confermare l'assenza di oscillazioni o ritardi.
- Registrare i dati di calibrazione e archiviare il registro di manutenzione.
- Riferimento rapido ai guasti durante la manutenzione
- Caccia alle valvole / piccolo ciclismo: Ugello/deflettore sporco; Angolo errato della leva di feedback; aria di alimentazione instabile.
- Deriva zero: Condensa nell'aria; lieve perdita dell'O-ring; lieve intasamento degli ugelli.
- Insufficient output pressure: Valvola pilota bloccata; clogged air filter.
- Grande isteresi: Incollaggio del perno e attrito elevato; eccessivo attrito della guarnizione dell'attuatore.
Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore




















NH42-63-318x560.png)