Reglette 120=500 Core Definition & Schneider Product

This is an abbreviation of elettrico terminology used in French-speaking environments. It actually refers to the Schneider Acti9 Vigi C120 series 500mA residual current protection accessory (RCD/earth leakage add-on module).

Here:

Reglette means modular accessory / terminal strip.

120 indicates compatibility with the C120 series circuit breakers (frame size 125A).

=500 stands for the rated residual operating current of 500mA.

It is used to add earth leakage protection to high-current C120 circuit breakers, in compliance with IEC/EN 61009-2-1.

  1. Abbreviation vs. Official Model Number

“Reglette 120=500” is a common field abbreviation, corresponding to the following official Schneider full models by number of poles:

PolesOrder CodeModello completoTipo di protezione
2PA9N18567Vigi C120 2P 500mA AC typeElectromagnetic, instantaneous
3PA9N18568Vigi C120 3P 500mA AC typeElectromagnetic, instantaneous
4PA9N18571Vigi C120 4P 500mA AC typeElectromagnetic, instantaneous
4PA9N18599Vigi C120 4P 500mA A‑SI typeElectromagnetic, interference‑resistant
  1. Model Breakdown (using A9N18571 as example)
Segmento modelloSensoKey Description
A9Platform codeActi9 series low‑voltage distribution platform, for C120 breakers
NProduct typeCircuit breaker accessory (leakage module)
18571Function code18 = Vigi C120 series, 5 = 500mA sensitivity, 71 = 4P AC type
Vigi C120Series nameEarth leakage add‑on exclusively for C120 breakers, up to 125A
500mATripping currentTrips the breaker when leakage reaches 500mA
AC typeProtection classFor pure AC earth leakage; electromagnetic trip, no auxiliary power needed
  1. Core Technical Specifications (Official Standard)
ItemSpecificaApplication
Product typeModular RCD accessory (DIN‑rail mount)Mounted to the right of C120 breaker, shared mechanism
Compatible breakersActi9 C120H / C120L (80/100/125UN)Only for C120 series; not compatible with IC65 etc.
Rated operational current≤ 125AMatches breaker rating, max 125A load
Rated residual current500mA (fixed)For indirect contact protection; industrial equipment, motori
Trip typeElectromagnetic (ELM)Voltage‑independent, works even during power loss
Protection classAC type / A‑SI typeA‑SI = electromagnetic interference‑resistant for harsh industry
Tensione nominale230/400V eFor 3‑phase 4‑wire / single‑phase industrial systems
Insulation voltage500V eMeets LV distribution insulation requirements
Mounting35Guida DIN da mm, modular clipMechanically interlocked with C120 breaker
IndicatorRed mechanical fault indicatorVisible trip indication without tools
  1. Full Series List (Vigi C120)

By rated residual operating current:

Tripping Current2P Code3P Code4P CodeCaratteristiche
30mAA9N18563A9N18564A9N18565Personal protection, instantaneous
300mAA9N18569A9N18570A9N18572Equipment protection, instantaneous / time‑delay
500mAA9N18567A9N18568A9N18571Heavy industrial protection, instantaneous (this model)
500mA‑SIA9N18599Interference‑resistant, for VFDs, motori
  1. Applicazioni tipiche

The 500mA Vigi C120 module is designed for heavy industrial use to avoid nuisance tripping from normal leakage during motor starting or VFD operation:

ApplicationMotivoRecommendation
Large motor circuitsNormal leakage on start-up; 500mA avoids nuisance trips while protecting insulationUse with C120H 3P 100A for motors above 75kW
VFD drive systemsHarmonic leakage on VFD output; 500mA suits industrial conditionsUse A‑SI type (A9N18599) for better immunity
Industrial switchboard busbar3‑phase 4‑wire distribution; prevents fire from insulation agingUse with C120L 4P 125A as incomer protection
Construction temporary power500mA provides equipment protection in harsh environments2P for single‑phase welders; 3P for mixers
Capacitor banksTransient leakage during switching; 500mA reduces frequent trippingUse with C120H 3P 80A
  1. Selection & Installation Guidelines

6.1 Selection Principles

FactorRecommendationRisk
Sensibilità30mA for personnel; 300/500mA for equipment500mA in personnel zones creates shock risk
Poles2P for single‑phase; 3P for 3‑phase 3‑wire; 4P for 3‑phase 4‑wire3P in 3‑phase 4‑wire leaves neutral unprotected
Interference immunityA‑SI type (A9N18599) for VFD/motor systemsStandard AC type may mis‑trip or fail in EMI environments
Breaker matchOnly C120H/C120L (80–125A)Not compatible with IC65 / NSX

6.2 Installazione & Safety Rules

  1. Mechanical interlock: Must be interlocked with a C120 breaker; do not use standalone or with other series.
  2. Testing: Press the test button (T) monthly to verify correct operation.
  3. Cablaggio: Follow official diagrams strictly for phase and neutral connections.
  4. Environment: Indoor enclosure (IP20); outdoor use requires a protective box.
  5. Recommended Replacements

7.1 Schneider Upgraded Model

OriginalUpgraded ModelImprovement
A9N18571 (4P 500mA AC)A9N18599 (4P 500mA A‑SI)Higher electromagnetic immunity for automation

7.2 International Brand Equivalents

MarcaSeriesModello sostitutivoKey Matching Specs
Siemens5SM5SM3 344‑04P, 500mA, AC type, for 5SY6 125A
ABBDSDS203 M C125 A5003P, 500mA, AC type, for S200 125A
EatonNZMNZM1‑XR5003P, 500mA, AC type, for NZM1 125A

“Reglette 120=500” is the French abbreviation for Schneider’s Vigi C120 series 500mA earth leakage accessory, used to add industrial‑grade residual current protection to high‑current C120 circuit breakers.

Official recommended models:

A9N18567 (2P)

A9N18568 (3P)

A9N18571 (4P)

A9N18599 (4P, interference‑resistant)

Select based on pole number, immunity needs, and matching breaker. Always test after installation to ensure safe and stable operation of the industrial distribution system.