Legacy MEC series, 22AFフレーム, 3-要素 (3-phase phase-loss protection type). Direct plug-in fit for GMC-9/12/18/22 contactors. Classic LS small-power motor thermal relay. 代替機種: MT-32/3H
✅ コア仕様
旅行クラス: クラス10A (standard motor protection)
補助接点: 1a1b (1いいえ + 1ノースカロライナ州)
保護機能: 過負荷, ロックされたローター, 3-phase phase-loss protection (advantage of 3-element design)
工事: バイメタルストリップ, 温度補償, trip-free mechanism
定格絶縁電圧Ui: 690V
リセットモード: 手動リセット (with TEST button)
Independent mounting: Optional bracket AZ-22H
📋 Full Current Range List for GTH-22/3
| モデルコード | 電流レンジの設定 |
| GTH-22/3 0.16 | 0.1~0.16A |
| GTH-22/3 0.21 | 0.16~0.25A |
| GTH-22/3 0.33 | 0.25~0.4A |
| GTH-22/3 0.5 | 0.4~0.63A |
| GTH-22/3 0.8 | 0.63~1A |
| GTH-22/3 1.3 | 1~1.6A |
| GTH-22/3 2.1 | 1.6~2.5A |
| GTH-22/3 3.3 | 2.5~4A |
| GTH-22/3 5 | 4~6A |
| GTH-22/3 6.5 | 5~8A |
| GTH-22/3 7.5 | 6~9A |
| GTH-22/3 8.5 | 7~10A |
| GTH-22/3 11 | 9~13A |
| GTH-22/3 15 | 12~18A |
| GTH-22/3 19 | 16~22A |
🔁 交換情報
Factory upgraded replacement: MT-32/3H (identical current ratings, direct replacement for GTH-22/3)
区別: GTH-22/2 is 2-element, without phase-loss protection, do not interchange
📌 Wiring Notes
主回路: 1/2/3 で, 4/5/6 外, connected in series between contactor outlet and motor
補助接点: 95-96 (ノースカロライナ州, wired into contactor coil circuit); 97-98 (いいえ, 故障警報用)
Current setting: Align dial pointer with motor full-load current (フロリダ州)
- 端子の定義 & Standard Start-Stop Wiring for GTH-22/3
端子マーク:
主回路: 1, 3, 5 (incoming); 2, 4, 6 (outgoing), wired in series after contactor T1/T2/T3 and before motor
補助接点:
95-96: NC ノーマルクローズ (must be wired in contactor coil circuit; opens on overload to stop motor)
97-98: いいえ ノーマルオープン (for alarm lamp / PLC fault input)
Front panel buttons: テスト (simulated trip), リセット (リセット); GTH-22/3 is factory set to manual reset only, no auto-reset selector (different from some domestic thermal relays)
Standard Start-Stop Wiring Sequence (380V Motor)
- Circuit breaker → Contactor KM main contacts L1/L2/L3
- KM output T1/T2/T3 → GTH-22/3 terminals【1, 3, 5】
- GTH-22/3 terminals【2, 4, 6】→ Motor 3-phase terminals
- 制御回路: Power supply → Stop button NC → 95 → 96 → Start button NO → KM coil A1/A2; KM auxiliary NO for latching
- 警報回路: 97-98 in series with alarm lamp / intermediate relay, powered from control supply
プラグインのインストール: Snap directly onto the bottom of GMC-9/12/18/22 contactors. DIN rail independent mounting requires bracket AZ-22H.
✅ Offline Test Method (電源オフ)
Use multimeter continuity mode:
正常な状態: 95-96 conducts; 97-98 開ける
Press TEST button: 95-96 開く, 97-98 閉まる; release TEST, RESET button must be pressed to restore
- トラブルシューティング表 (GTH-22/3 3-element phase-loss protected type)
注意事項: GTH-22/3 is Class 10A. It protects against overload, locked rotor and phase loss ONLY. It cannot provide short-circuit protection. Short-circuit protection shall be implemented by fuse or circuit breaker.
| 症状 | 根本的な原因 | 検査 & 救済策 |
| モーターの過負荷 / ロックされたローター, thermal relay does not trip or protect | 1. Setting current too high2. Heating element burnt or internal solder joint open3. 機構が詰まっている, bimetallic strip deformed4. Wrong frame size (current range oversized) | 1. Align setting dial with motor nameplate rated current (フロリダ州; +5%~10% allowed for frequent start)2. Measure continuity of main circuit phases 1-2, 3-4, 5-6 with multimeter; replace if open3. Activate TEST button to verify contact switching; replace if TEST fails4. Confirm model is GTH-22/3 (3-element with phase-loss protection), not GTH-22/2 |
| Motor runs at normal load, nuisance tripping, trips immediately on startup | 1. Setting current too low2. Loose terminal connection, 過熱 (terminal heat triggers premature bimetallic action)3. High cabinet ambient temperature, mounted too close to hot contactor4. Long motor starting time (high inertia load)5. 3-phase supply phase loss (GTH-22/3 trips on phase loss) | 1. Recheck motor rated current and adjust setting upwards2. 電源を切る, retighten all main circuit screws; inspect conductors for oxidation or discoloration3. Keep clear of heat sources, 通気性を改善する; increase setting by 5% if ambient >40℃4. For long-start loads, consider Class20 thermal relay5. Measure 3-phase supply voltage, check for missing phase or broken cable |
| つまずいた後, RESET button cannot reset the relay | 1. Internal trip mechanism jammed or damaged2. Bimetallic strip not cooled down (2~5 min cooling required; hot state prevents reset)3. Auxiliary contacts welded together | 1. Wait for cooling then retry reset; replace if still unable to reset after cooling2. 測定 95-96 連続; replace if remains open after reset |
| Control circuit dead, contactor cannot pull in | 1. Thermal relay tripped, 95-96 open2. Loose or broken wiring on 95/963. Auxiliary contacts eroded and high resistance | 1. Reset relay first, then test continuity of 95-962. Re-terminate control wiring; replace relay if contacts are heavily burnt |
| Random tripping after running for a period, restarts after cooling | 1. Hidden motor overload, bearing seizure, excessive load2. Undersized cable, high voltage drop, terminal overheating3. Unbalanced 3-phase current | 1. Measure 3-phase running current with clamp meter, compare against setting value2. Inspect motor bearings, impeller and gearbox for binding3. If current imbalance >10%, investigate supply voltage and motor winding |
Ⅲ. Special Notes for GTH-22/3
- 3-要素 (/3) ≠ 2-element (/2):GTH-22/3 has phase-loss protection; GTH-22/2 does not, cannot substitute
- Phase-loss protection principle: If one phase is lost, the other two phases draw elevated current, the two corresponding heating elements heat and bend the bimetallic strips to trigger trip. It is thermal accumulation, not instantaneous voltage detection.
- Conductor sizing: Main circuit conductors must be sized for rated current; thin wiring causes false tripping from self-heating.
- Avoid frequent TEST operation, which accelerates internal mechanism wear.
- Replacement model MT-32/3H shares identical terminal assignment and wiring logic, ダイレクトスワップ.
- Quick On-site Troubleshooting Sequence
- Isolate power → Visual inspection: 火傷跡, burnt odor, overheated terminals
- Multimeter test: main circuit phase continuity, auxiliary contact normal state
- Activate TEST to confirm trip action and reset function
- 電源を入れる, clamp meter test 3-phase running current, cross-check setting
- Measure 3-phase voltage, check phase loss and imbalance
- Rule out motor and mechanical load faults before confirming thermal relay failure
Overload Protection Principle of Bimetallic Thermal 過負荷リレー (GTH-22/3 type)
基本原則: Current thermal effect + bimetallic strip thermal deformation, simulating motor thermal characteristics for delayed overload protection. It cannot provide instantaneous short-circuit protection.
- コアコンポーネント: バイメタルストリップ
Two metal strips with different thermal expansion coefficients are clad together:
Active layer: higher expansion rate
Passive layer: lower expansion rate
At ambient temperature: フラット, mechanism latched, 95-96 NC contact closed.
- Action Sequence on Overload
- Motor current flows through heating element, higher current generates more heat;
- Heat transfers to bimetallic strip;
- Differential expansion causes the strip to bend toward the low-expansion side;
- Sustained overcurrent accumulates bending displacement until trip threshold is reached;
- Mechanical latch releases: 95-96 NC接点が開く, cutting contactor coil supply and stopping motor; 97-98 NO contact closes for fault signal.
特徴: 逆時間特性
Larger overload current → faster heating and shorter trip time. Mild overload requires long duration to trip, matching motor allowable short-time overload. For Class10A: trips within 4~10s at 10× setting current.
- Additional Phase-loss Protection Principle of GTH-22/3 (3-要素)
Basic 2-element relays only monitor two phases.
GTH-22/3 has independent heating elements and bimetallic strips for all three phases:
When one supply phase is lost, the remaining two phases carry excess current, both heating elements bend and trigger accelerated trip.
Phase-loss protection is still thermal accumulation, not instantaneous voltage detection.
- Built-in Temperature Compensation (GTH series)
Internal compensation bimetallic strip offsets ambient temperature influence, preventing false tripping in hot cabinet or cold environment when current is normal.
- Reset Principle
つまずいた後, the bimetallic strip must cool and spring back to original shape.
GTH-22/3 is manual reset: after full cooling, press RESET to re-latch the mechanism and restore contact status.
- 主な制限事項 (Field Critical)
✅ Protected conditions: sustained overload, ロックされたローター, 位相損失, continuous excess current
Not protected: 短絡 (short-circuit current is too high; the relay will burn before the strip bends. Short-circuit protection via breaker/fuse)
Not protected: 瞬間突入電流 (starting current is bypassed by inverse time delay)
LS (Legacy GTH + New MT Series) Thermal Relay ↔ Contactor Compatibility Chart
注意事項: Direct plug-in fit. Independent DIN rail mounting requires bracket (AZ / UZ series). /3 = 3-element with phase-loss protection; /2 = 2-element without phase-loss protection.
- Legacy GTH Series (including GTH-22/3)
| Thermal Relay Model | Direct Plug-in Contactor | 備考 |
| GTH-22/2, GTH-22/3 | GMC-9, GMC-12, GMC-18, GMC-22 | Max setting 22A; bracket AZ-22H for standalone mounting |
| GTH-40/2, GTH-40/3 | GMC-32, GMC-40 | Max setting 34A |
| GTH-85/2, GTH-85/3 | GMC-50, GMC-65, GMC-75, GMC-85 | Max setting 74A |
| GTH-100/2, GTH-100/3 | GMC-100, GMC-125 | Max setting 107A |
| GTH-150/2, GTH-150/3 | GMC-150 | Max setting 130A |
| GTH-220/2, GTH-220/3 | GMC-180, GMC-220 | Max setting 200A |
| GTH-400/2, GTH-400/3 | GMC-300, GMC-400 | Max setting 320A |
- New MT Series (GTH Replacement, メタソル)
| Thermal Relay Model | 適合コンタクタ | Replaces Legacy | Standalone Bracket |
| MT-32/3H | MC-9b, MC-12b, MC-18b, MC-22b, MC-32a, MC-40a | GTH-22/3, GTH-40/3 | UZ-32 |
| MT-63/3H | MC-50a, MC-65a | GTH-85 | UZ-63 |
| MT-95/3H | MC-75a, MC-85a, MC-100a | GTH-100 | UZ-95 |
| MT-125/3H | MC-125a | GTH-150 | UZ-125 |
| MT-200/3H | MC-150a, MC-185a, MC-220a | GTH-220 | UZ-200 |
Ⅲ. Common Pitfalls for GTH-22/3
- GTH-22/3 only plugs into GMC-9/12/18/22, cannot directly fit GMC32 and above contactors.
- Current rating = adjustable range, not contactor rating. Contactor rated current must be ≥ motor rated current.
- Upgrade path: GTH-22/3 → MT-32/3H. Same terminal definition and contact logic, but new contactors are MC series instead of old GMC.
- Bracket incompatibility: AZ-22H for old GTH; UZ-32 for new MT-32, cannot interchange.
- クイック選択ルール
Motor rated current ≤22A: Old scheme GMC-9~~22 + GTH-22/3; New scheme MC-9b~~22b + MT-32/3H
Setting Current Adjustment Procedure for LS GTH-22/3 Thermal Relay
- Setting Principle
Setting Current = Motor Nameplate Full-Load Current (フロリダ州)
Continuous-duty standard motor: set exactly to nameplate FLA
ファン / pump general loads: set to nameplate value
Frequent start, heavy-start or long acceleration loads: +5% ~ +10% of FLA, do not exceed 1.1×
Intermittent short-cycle motor: can reduce slightly, minimum ≥0.9× FLA
注記: The dial scale of GTH-22/3 is adjustable range, not fixed value. The value aligned by the pointer is the setpoint.
- 調整手順 (GTH-22/3)
- Power off for safety (always power off before adjustment to avoid live terminal exposure)
- Open the front protective cover
- Rotate the central adjustment dial with indicator pointer
- Align pointer to target setting current
- Refit cover
- 電源を入れる, test run, verify 3-phase current with clamp meter
例:
Motor nameplate FLA = 5.2A → Select GTH-22/3 5 (4~6A range), align pointer to 5.2.
Ⅲ. On-site Verification (致命的)
調整後, run motor at full load and measure 3-phase current with clamp meter:
Measured stable current ≈ setting value: 普通
Continuous running current far below setting: protection is loose, overload may not trip
Frequent tripping near rated current: check setting, モーターの過負荷, hot terminals or high ambient temperature
- よくある誤解
- Set by contactor rated current: wrong, always reference motor nameplate
- Turn dial to maximum end: removes effective overload protection
- Increase setting heavily to accommodate starting inrush: inverse time characteristic is designed to withstand starting surge, no large over-set required
- Adjust setting to fix 3-phase imbalance: imbalance must be traced to supply, cable or motor winding, not thermal relay setting
- Temperature Compensation Impact
GTH has built-in temperature compensation. If cabinet ambient temperature is persistently above 40℃, relay trips easier at same current; ある 5% upward setting is acceptable. If ambient <0℃, setting can be reduced slightly.
- Supplementary Notes for GTH-22/3
TEST button only simulates trip, it does not change the current setting value
Adjustment only changes overload trip threshold, phase-loss protection function remains active