状態: NO LONGER FOR SALE
Flat Pack FP series ultrasonic distance sensor, single transducer. アプリケーション: bin level, liquid level, long-range object detection, anti-collision and positioning.
✅ Model Code Explanation
UC6000: UC series ultrasonic sensor, maximum measuring range 6000 mm
FP: Flat Pack rectangular housing (80×80×61 mm, different from 30GM cylindrical version)
E6: 2 PNP switching outputs, NO/NC software programmable
R2: Equipped with RS232 serial port + synchronization interface, parameter configuration via ULTRA3000 PC software
P5: Terminal block wiring (not M12 connector)
📋 Key Technical Specifications
| アイテム | 仕様 |
| 測定範囲 | 800 … 6000 mm (0.8 う~ん 6 メートル) |
| Blind Zone | 0 … 800 mm |
| Transducer Frequency | 約. 65 kHz |
| Standard Reflector Target | 100×100 mm flat plate |
| 供給電圧 | 15…30 V DC, ripple 10%ss |
| 無負荷電流 | ≤60 mA |
| 出力 | 2 PNP switching outputs, NO/NC選択可能; 最大. 200 チャンネルあたりの電流, short-circuit/overload protection, voltage drop ≤3 V |
| シリアルインターフェース | RS232, 9600 baud, パリティなし, 8 データビット, 1 ストップビット |
| Synchronization | Bidirectional sync port, multi-sensor synchronization for crosstalk suppression, 最大. sync frequency ≤10 Hz |
| 解決 | <1 mm |
| 繰り返し精度 | ≤0.1% of full scale |
| ヒステリシス | ≤1% of set distance, プログラム可能な |
| Temperature Drift | ≤2% (内蔵温度補償) |
| Response Delay | 分. 180 MS; デフォルト 360 MS; dynamic mode 270 MS |
| 保護クラス | IP65 |
| 動作温度 | -25 ~ +70 ℃; ストレージ -40 ~ +85 ℃ |
| ハウジング材質 | PBT thermoplastic; Transducer: epoxy resin + hollow microspheres + polyurethane foam |
| 重さ | 320 g |
| 配線方法 | Terminal compartment, 最大. wire cross-section 2.5 mm² |
| LEDインジケーター | 緑: 力; 黄色: Two output states; 赤: 故障 / interference alarm |
✨ Product Features
- Two independent PNP switch points, configurable via DIP switch or RS232 software
- Built-in temperature compensation to reduce ranging error caused by ambient temperature
- Reverse polarity protection and short-circuit protection
- Multi-transducer synchronization supported to eliminate ultrasonic crosstalk
- PC software ULTRA 3000 for parameter read/write, 校正と診断
- Rectangular flat housing, easy for flat mounting on brackets or cabinets
🛠️ Typical Applications
Silo level monitoring, wastewater tank liquid level, anti-collision for large conveying equipment, long-range object detection for stacker cranes, warehouse space positioning.
⚠️ Replacement Selection Guide (Original discontinued)
- UC6000-FP-E7-R2-P5: Same FP housing, output changed to NPN, same range and dimensions
- New IO-Link version: UB6000-F42 series (角型ハウジング, IOリンク, 6 m range, successor for old FP series)
- Cylindrical alternative: UC6000-30GM-E6R2-V15 (M30 cylindrical, 6 m range, 2 PNP outputs, RS232, M12コネクタ)
📌 Troubleshooting (Common issues for this model)
- Red LED flashing: Weak echo / heavy ambient noise. Check transducer surface for condensation, ほこり, strong airflow; increase response time.
- Fluctuating distance reading: Multiple sensors operating in the same area → enable sync line; or adjust mounting angle to avoid multiple reflections.
- RS232 communication failure: Confirm serial parameters 9600,N,8,1. Note the sensor uses non-standard RS232 voltage levels, requires dedicated adapter, cannot connect directly to PC serial port.
- Switch outputs not activating: Verify NO/NC configuration, correct wiring for PNP load, ensure load current ≤200 mA.
ULTRA3000 Configuration Procedure (For UC6000-FP-E6-R2-P5)
Important prerequisite: ULTRA3000 is dedicated ペッパール+フックス software for legacy ultrasonic sensors. Only compatible with Windows XP / Win7 (32/64少し). Direct execution on Win10/11 is unstable; Win7 virtual machine recommended.
Fixed serial parameters: 9600 baud, N,8,1 (パリティなし, 8 データビット, 1 ストップビット). The sensor uses non-standard RS232 levels. Do NOT connect directly with ordinary USB-to-RS232 adapters. Pepperl+Fuchs dedicated R2 level converter cable is required.
- Hardware Wiring Preparation (FP housing P5 terminal box version)
- Power the sensor with DC15~30V, power on and confirm green power LED is steady ON.
- Open sensor terminal box, route RS232 signals of R2: TXD, RXD, GND
Sensor TXD → Adapter RXD
Sensor RXD → Adapter TXD
Common GND connection is mandatory; communication failure is highly likely without common ground
- Connect dedicated RS232 adapter to PC serial / USB-to-serial port (P+F R2 level conversion is mandatory; generic RS232 modules cannot communicate)
- For multi-sensor synchronization: parallel sync wires. Sync line can be left disconnected during commissioning.
- DIP switch setting: Enable R2 serial port, set corresponding DIP to OFF to activate RS232 communication (DIP on PCB inside FP housing).
90% of communication failures are caused by: missing P+F dedicated level adapter, crossed TX/RX reversed, no common ground, R2 serial port disabled via DIP.
- Software Installation & Serial Port Identification
- Install ULTRA3000 following setup wizard; English UI only (no Simplified Chinese).
- Open Device Manager and check COM port number (USB-to-serial creates virtual COM).
- Launch ULTRA3000, enter main window, open menu【Serial Port】.
- Select corresponding COM port, fixed parameters: 9600 / なし / 8 /1.
- Click Connect to establish connection. If successful, software reads sensor model, firmware version and factory parameters. If failed, check hardware above.
Four core panels in main interface:
Graph: Real-time distance curve, echo waveform, switch point markers
パラメータ: All adjustable parameters
画面: Live measured distance, output status, LED simulation
Command: Low-level serial command debugging
- Read Original Sensor Parameters (Recommended first step)
- After successful communication, click【Read from sensor】to upload current sensor parameters to software.
- Use【Save to file】to save parameter file (.par) for backup for future recovery.
- Core Parameter Configuration (UC6000-FP-E6-R2-P5, dual PNP outputs)
Go to Parameter panel and adjust key settings:
4.1 測定範囲 & Blind Zone
Min distance: fixed at 800 mm (blind zone, cannot be lower)
Max distance: 6000 mm
You may reduce maximum range for your application to improve response speed and noise immunity.
4.2 Switch Output Q1, 第2四半期 (2 PNP channels)
Each channel can be configured independently:
Switch point 1 (near point)
Switch point 2 (far point)
動作モード:
Window mode: Output active between two thresholds (widely used for level measurement)
Single point mode: Trigger when distance above / below threshold
出力論理: NO Normally Open / NC Normally Closed (for PNP outputs)
ヒステリシス: 推奨 1% of set distance to suppress jitter
例 (高い + low bin level dual alarm)
Q1: Window mode for low level; 第2四半期: Single point mode for high level.
4.3 応答時間 & Filtering (Anti-jitter, airflow interference)
応答時間: Min.180 ms, デフォルト 360 MS; extend to 540 ms for dusty / high airflow environments
フィルター: Moving average filter. Higher filter count = more stable reading, slower response
Sound velocity: Built-in temperature compensation, normally no manual adjustment needed; manual calibration available for high-precision applications.
4.4 Synchronization (Multi-transducer anti-crosstalk for overlapping detection zones)
Sync mode: シングル (single sensor) / マスター / スレーブ
Multi-sensor setup: 1 マスター, others Slave. Max sync frequency ≤7Hz divided by sensor count; まで 5 transducers.
4.5 診断 & アラーム
Echo loss: Echo loss threshold
Fault behaviour: Hold / drop outputs when echo is lost.
- Download Parameters to Sensor
- After finishing parameter setup, click【Write to sensor】to write settings into sensor.
- After writing, software automatically reads back parameters, verify written values match configured values (critical check).
- Execute【Store User Configuration】SUC to permanently save parameters into sensor Flash memory.
⚠️ Without SUC save, parameters revert to factory defaults after power cycle! This is the most common mistake.
- Online Debugging & 較正 (Graph panel)
- Open Graph real-time plot, observe echo waveform and identify spurious echoes (sidewall reflection, multi-reflection caused by dust).
- Move reflector target to near and far setpoints to verify Q1/Q2 output status; simulated LEDs in software change synchronously.
- If distance reading jumps:
Increase filtering and extend response time
Check mounting angle to avoid sidewall reflections
Enable synchronization for multiple sensors
- ロギング:【Record measurement】, export curve for failure analysis.
- Disconnect & Field Commissioning
- Close serial connection in ULTRA3000.
- Disconnect RS232 debug cable; keep sensor powered with normal wiring for operation.
- Field test: block / remove reflector target to verify switching action of 2 PNP outputs.
Common Communication Troubleshooting for ULTRA3000
- Connect failed, cannot read sensor
DIPスイッチを確認してください, confirm R2 serial port enabled
TX/RX crossed, common ground connected; P+F R2 level adapter is mandatory for communication
COM port occupied by other software, close serial assistant tools
- Parameters written successfully, but reset to factory after power cycle
→ SUC save (Store User Configuration) was skipped
- Unstable distance reading, messy echo waveform
→ Airflow, ほこり, sidewall reflections; increase filtering, enable synchronization, adjust mounting angle
- Software reads distance correctly, but Q1/Q2 outputs do not trigger
→ Check NO/NC logic, PNP load wiring, hysteresis and window mode settings
補足: Low-level Command Mode (Command panel for advanced debugging)
Raw P+F serial commands can be sent directly to read/write parameters, suitable for automated script debugging e.g. distance reading and switch point modification.
UC6000-FP-E6-R2-P5 Terminal Box RS232 Pin Definition
適用機種: UC6000-FP-E6-R2-P5 (P5 = built-in terminal box, non-M12 version)
Important reminder: The sensor R2 interface uses Pepperl+Fuchs proprietary non-standard RS232 voltage levels, not standard PC RS232. Pepperl+Fuchs R2 level converter is required; generic USB-to-RS232 cannot communicate.
- Terminal Numbering & Signal Definition inside Terminal Compartment
Open sensor housing terminal chamber, terminal block signals:
| 端子番号. | 信号名 | 説明 |
| 1 | DC+ | Power supply positive: DC15~30V |
| 2 | DC 0V (GND) | パワーマイナス / common ground, mandatory common ground for RS232 communication |
| 3 | Q1 (PNP Output 1) | 1st switching output, NO/NC software configurable, 最大. 200 ミリアンペア |
| 4 | 第2四半期 (PNP Output 2) | 2nd switching output, NO/NC software configurable, 最大. 200 ミリアンペア |
| 5 | SYNC (Sync Signal) | Multi-sensor sync wire, master-slave sync; leave floating for single sensor |
| 6 | RXD (Sensor Receive) | Sensor RXD ↔ Adapter TXD (cross wiring) |
| 7 | TXD (Sensor Transmit) | Sensor TXD ↔ Adapter RXD (cross wiring) |
| 8 | RS232 GND | Serial ground, must be shorted to power 0V for common ground |
✅ Communication Wiring Rule (致命的)
Sensor TXD(7) ↔ Adapter RXD
Sensor RXD(6) ↔ Adapter TXD
Sensor RS232 GND(8) ↔ Adapter GND, and short to power 0V (ターミナル 2).
Communication will almost certainly fail if only TX/RX are wired without GND.
✅ Commissioning state: DIP1=OFF, 他はすべてオフ.
DIP1 can be switched ON to close serial port and reduce interference during normal operation without debugging.
- Pepperl+Fuchs R2 Level Converter (Matching Hardware)
モデル: K-ADP-R2 (P+F dedicated R2 level converter)
One side: connect sensor terminals 6,7,8 (送信/受信/GND)
Other side: standard RS232 level, connect to PC serial / USB-to-RS232
Without K-ADP-R2, generic USB-to-RS232 cannot detect sensor serial signal.
- Pre-power Wiring Checklist
- 力: 端子 1 & 2, DC15~30V. 極性を観察してください. Reverse polarity protection exists but inspection is still required.
- コミュニケーション: 端子 6 &7 cross-connected; terminal8 shorted to power 0V for common ground.
- Synchronization: Leave terminal5 floating for single sensor; parallel all SYNC terminals for multi-sensor network.
- ディップスイッチ: DIP1 set OFF to enable R2 serial port.
- 出力配線: Q1/Q2 are PNP type. Connect one end of load to Q1/Q2, the other end to 0V.
- LED Indicator Description (LEDs outside terminal box)
緑色のLED: Steady ON = Power OK; OFF = No power / 電源障害
黄色のLED: Output status, lights up when Q1/Q2 is activated
赤色LED: 故障警報; flashing = weak echo / abnormal signal; steady ON = hardware fault