微信: +86-13184948252 ワッツアップ: 0086-13811255435 電子メール: kent@bestcontactor.com

について 接触 |

Power Fittings for 220 kV High-Voltage Transmission Lines - コンタクタ,サーキットブレーカー,ソーラーインバーター,電気メーター,太陽電池

電気/

Power Fittings for 220 kV High-Voltage Transmission Lines

名前Model/Spec
Composite Tension Insulator StringFXBW4-220/210
Twin‑Bundle Tension Clamp (crimp type)NY-400/35
Twin‑Bundle Yoke PlateL-12
Jumper ClampTJ-5
U‑ShackleU-10
Right‑Angle PlateZ-10
Grading & Corona RingFP-220
Vibration DamperFD-4

  • 製品詳細

These are critical components ensuring the safe and stable operation of power transmission systems, mainly classified into six core categories: Conductor and Ground Wire Systems, Insulators, Fittings, Tower and Foundation Accessories, Lightning Protection & Overvoltage Protection, and Cable Accessories. A structured breakdown is provided below:

  1. Conductor and Ground Wire Systems (Core Transmission Components)
Fitting Typeコア機能Common Models技術的パラメータApplication Notes
Aluminum Conductor Steel Reinforced (ACSR)Main power transmission, combining strength and conductivityLGJ-300/40, LGJ-400/35, LGJ-500/45220 kV lines typically use 2×300 mm² or 2×400 mm² bundled conductors; safety factor ≥ 2.5Corrosion-resistant types (例えば, JL/G1A, JL/G2A) shall be selected per environment; high-strength ACSR for long spans
OPGW Optical CableCommunication and line monitoring, doubles as ground wireOPGW-24B1-80, OPGW-36B1-100Short‑circuit current withstand ≥ 25 kA/0.5 s; tensile strength ≥ 120 kNUsed with ground wires; splice closures must be waterproof and moisture‑proof; splicing loss ≤ 0.05 dB
Ordinary Ground WireLightning protection, doubles as communication channelJLB20A-80, JLB40-100Galvanized steel strand, cross‑section ≥ 70 mm²Both ends must be reliably grounded; insulation clearance from phase conductors must be satisfied
  1. Insulators (Core Insulation and Isolation)

220 kV line insulators fall into two main types: suspension insulators and post insulators.

Key parameters: dry arc distance ≥ 2020 mm, specific creepage distance ≥ 25 mm/kV (general areas)

Material TypeCommon ModelsMechanical LoadFeaturesSuitable Scenarios
Composite InsulatorFXBW4-220/160, FXBW4-220/210160 kN, 210 kNLight (≈ 1/3 of porcelain), pollution‑flash resistant, maintenance‑freePolluted areas, high‑altitude areas, long‑span sections
Porcelain InsulatorXP-160, XP-210160 kN, 210 kNLow cost, mature and reliableOrdinary clean areas, plain areas
Glass InsulatorLXHY-160, LXHY-210160 kN, 210 kNSelf‑destructs at zero value, easy to inspectLines requiring frequent inspection
Post InsulatorZSW-220/8, ZSW-220/108 kN, 10 kNSupports busbars and equipment connectionsSubstation outlets, both sides of circuit breakers
  1. Power Fittings (Key Connection and Fixing Components)

Divided by function into clamps, connecting fittings, splicing fittings, and protection fittings, all complying with GB/T 2314‑2008.

1) Clamps (Core Conductor Fixing)

タイプCommon ModelsSuitable ConductorsGrip RequirementApplication Location
Suspension ClampXGU-4, XGU-5LGJ-300~630 mm² 12% of conductor breaking strengthStraight towers, allows small conductor movement
Tension ClampNY-300/40, NY-400/35LGJ-300~630 mm² 95% of conductor breaking strengthTension towers, terminal towers, full tension bearing
Jumper ClampTJ-4, TJ-5Jumper connectionsContact resistance ≤ 1.2 μΩJumper connections on both sides of tension towers

2) Connecting and Splicing Fittings

タイプCommon ModelsFunctionTechnical Requirement
Socket ClevisW-7A, W-10AConnects insulator string to towerFailure load ≥ 70 kN / 100 kN
Ball EyeQ-7A, Q-10AConnects insulator to fittingFailure load ≥ 70 kN / 100 kN
Splicing SleeveJY-300/40, JY-400/35Conductor splicingResistance after crimping ≤ 1.1 × conductor resistance
Grading RingFJ-220Improves voltage distribution on insulatorsDiameter 400–600 mm, installed at both ends of insulators

3) Protection Fittings

タイプCommon ModelsFunctionSuitable Conditions
Vibration DamperFD-4, FD-5Suppresses aeolian vibrationLines with span > 120 m; installation spacing calculated
Spacer DamperFG-4, FG-5Maintains bundled conductor spacing220 kV twin conductors, spacing 400 mm; 1 per 50–60 m
Corona RingFP-220Prevents corona dischargeHigh‑altitude, strong electric‑field areas
  1. Tower and Foundation Accessories (Support Structure)
Fitting TypeCommon ModelsFunction技術的パラメータ
Cross ArmHD220-1, HD220-2Mounts insulators and fittingsQ235/Q345 steel, hot‑dip galvanized for corrosion protection
Hoop ClampBG-16, BG-18Fixes cross arms, laddersMatches tower diameter; bolt strength ≥ 8.8
Anchor BoltM30~M64Fixes tower foundationGrade 45 steel, anti‑corrosion treated; tensile strength ≥ 600 MPa
Climbing LadderPT-220Access for tower maintenanceStep spacing 300 mm; handrail diameter 20 mm; load capacity ≥ 100 kg
  1. Lightning Protection and Overvoltage Protection Accessories
Fitting TypeCommon ModelsFunction技術的パラメータ
Metal Oxide Arrester (MOA)YH10WZ-204/532Limits lightning overvoltage定格電圧 204 kV; residual voltage ≤ 532 kV; discharge capacity 20 kA/2 ms
Grounding DeviceDischarges lightning currentHorizontal electrode: φ12 mm round steel; vertical electrode: 50×50 mm angle steel, L = 2.5 m; grounding resistance ≤ 10 Ω
Line Fault IndicatorXJ-220Indicates short‑circuit/earth faultOperating current: short‑circuit ≥ 100 あ, earth ≥ 5 あ; auto‑reset 1–24 h
  1. Cable Accessories (For Cable Lines Only)
Fitting TypeCommon ModelsFunctionSuitable Conditions
Cable TerminationWTY-220/1×1200Connects cable to overhead line/equipmentCross‑section 400–2500 mm²; lightning impulse withstand voltage ≥ 950 kV
JointYJJJ-127/220Cable splicingWaterproof rating IP68; operating temp −40~90 °C
Cross‑Bonding Grounding BoxNTJX-1Eliminates sheath induced voltage66–220 kV cables; equipped with sheath protector
Arrester Grounding BoxNTB-1Protects cable sheathBuilt‑in MOA; rated voltage 20 kV
  1. Key Points for Selection and Application of 220 kV High‑Voltage Line Fittings
  2. Voltage Matching: Rated voltage of all fittings ≥ 252 kV (max operating voltage of 220 kV system)
  3. Mechanical Strength: Safety factor ≥ 2.5 (conductors, fittings); 3.0 (絶縁体)
  4. Environmental Adaptation:

Polluted areas: specific creepage distance ≥ 31 mm/kV; composite insulators preferred

Coastal areas: metal parts with hot‑dip galvanizing + passivation or 316L stainless steel for salt‑fog resistance

Cold areas: cold‑resistant materials (brittle temperature ≤ −40 °C); heavy‑duty vibration dampers

  1. 設置仕様:

Fitting contact surfaces: remove oxide film + apply conductive paste; contact resistance ≤ 1.2 μΩ

Insulator string: horizontal offset ≤ 150 mm; vertical deviation ≤ 50 mm

Conductor sag error ≤ ±5%; phase‑to‑phase sag difference ≤ 200 mm

  1. Main Brands and Alternative Models
Fitting CategoryMain BrandsRecommended Model代替モデル
Composite InsulatorChangyuan Gaoneng, Jinguan ElectricFXBW4-220/210FXBW-220/210 (Xi’an Porcelain)
Tension ClampChina Electric Power Fittings Factory, Jiangsu ShenmaNY-400/35NLD-4 (bolt type, small section)
MOAXi’an XD, Henan PinggaoYH10WZ-204/532YH10W-200/500 (general type)
Cable TerminationTaikai Cable, Changlan ElectricWTY-220/1×1200WTG-220 (dry termination)

Selection of 220 kV high‑voltage line fittings must comprehensively consider voltage level, mechanical load, environmental conditions, and operational reliability. Key fittings shall pass State Grid Corporation qualification certification and comply with relevant GB and DL standards.

Below is a standardized bill of materials (BOM) のために 220 kV overhead lines, directly usable for construction, quotation, and procurement, sorted by Straight Tower, Tension Tower, Terminal Tower + Cable Outlet.

Defaults:

Voltage: 220 kV (max operating voltage 252 kV)

Conductor: twin‑bundle ACSR LGJ‑400/35 (most commonly used)

Insulator: composite insulator (pollution‑resistant, maintenance‑free, mainstream choice)

  1. Standard BOM for 220 kV Single‑Circuit Straight Tower

Per tower (3 phases, twin‑bundle per phase)

Item名前Model/SpecUnitQty目的
1Composite Suspension Insulator StringFXBW4-220/160set3Suspension for 3hase conductors
2Twin undle Suspension ClampXGS-5set6Suspension for 2 sub onductors per phase
3Ball EyeQ-10set6Connect insulator to clamp
4Socket ClevisW-10set6Connect insulator to cross arm
5Twin undle SpacerFG-400 (400 mm spacing)pcsAs per spanPrevent galloping, maintain bundle spacing
6Vibration DamperFD-4set122 sets per phase for aeolian vibration control
7Grading RingFJ-220set3Voltage grading at insulator ends, antiorona
  1. Standard BOM for 220 kV Tension Tower (Angle / Junction)

Per tower (3 phases, twin‑bundle per phase)

Item名前Model/SpecUnitQty目的
1Composite Tension Insulator StringFXBW4-220/210set62 strings per phase (double suspension)
2Twin‑Bundle Tension Clamp (crimp type)NY-400/35set6Fix tension end of conductor
3Twin‑Bundle Yoke PlateL-12pcs3Converge twin‑bundle conductors
4Jumper ClampTJ-5set6Jumper connection at tension tower
5U‑ShackleU-10set12Connect insulator to tower/clamp
6Right‑Angle PlateZ-10set12Directional connection
7Grading & Corona RingFP-220set6Voltage grading and anti‑corona for tension strings
8Vibration DamperFD-4set12Vibration damping for jumpers/conductors
  1. Fittings for 220 kV Terminal Tower → Substation Cable Outlet

Typical scheme: cable termination + arrester for GIS/main transformer connection

Item名前Model/SpecUnitQty目的
1220 kV Outdoor Cable TerminationWTY-220/1×630~1200 mm²set3Cable‑to‑overhead connection
2Line MOAYH10WZ-204/532phase3Limit lightning/switching overvoltage
3Equipment Clamp (compression type)SY-400set6Connect conductor to termination/arrester
4Cable Fixing Fitting220 kV 3‑core/single‑core clampsetseveralCable fixing on tower
5Grounding Flat Steel / Electrode−50×5 hot‑dip galvanizedmper designGrounding for arrester, cable sheath
  1. General for Whole Line: Ground Wire & Lightning Grounding Accessories

Suitable for OPGW or ordinary ground wire

Item名前Model/SpecUnit目的
1Ground Wire Suspension ClampXD-8setStraight suspension of ground wire
2Ground Wire Tension ClampND-8setTension fixing of ground wire
3Down Ground Leadφ12 hot‑dip galvanized round steelmTower grounding downlead
4Vertical Ground ElectrodeL50×50×5×2500 mmpcsReduce grounding resistance
5Grounding ClampJDX-8setConnect ground wire to grounding system

前へ:

返信を残す

伝言を残す