CA4KN: TeSys Kシリーズ control relay
31: 接点構成: 3 いいえ + 1 ノースカロライナ州
B: 24 V DC low-consumption coil with built-in bidirectional freewheeling diode
W3: Screw clamping terminals
コア技術パラメータ
コイル: 24 V DC low-power coil, integrated bidirectional peak suppression diode
Contact arrangement: 3 通常開 + 1 通常閉 (3NO+1NC), 4-ポール
従来熱電流 Ith: 10 あ (で 50 ℃)
定格絶縁電圧Ui: 690 V
Utilisation category: AC-15 / DC-13 (standard control circuit loads)
取り付け: DIN35 rail mounting or base plate fixing
配線: ネジ端子, 締め付けトルク 1.3 N・m
寸法: W45 mm × H58 mm × D57 mm
機械的耐久性: 20 100万操作
Recommended protection: 10 A gG fuse
起源: インドネシア
代表的な用途
PLC digital output expansion, signal isolation & 移行, logic interlocking, indicator lamp driving, small solenoid/coil actuation. It is an auxiliary control relay, not intended for high-power main circuits. It shares the same footprint as TeSys K contactors and can be installed side-by-side.
Cross-reference for Replacement & 選択
CA4KN22BW3: 2NO+2NC, 24 ワシントンDCで, ネジ端子
CA4KN40BW3: 4いいえ, 24 ワシントンDCで, ネジ端子
CA4KN31BN3: Spring-cage terminal version (replaces W3)
税関HSコード
HSコード: 85364190 (Electromagnetic relays, rated voltage ≤60 V)
一般的な代替品
国内代替品: チント / 美味しい 24 V DC control relays with 3NO+1NC contact configuration.
シュナイダー direct upgrade: other coil variants within the CA4KN series (例えば, 110 ワシントンDCで).
Typical Application Cases for CA4KN31BW3 (3NO+1NC, 24 V DC Low-Consumption Control Relay)
主な利点: built-in bidirectional freewheeling diode, コイル消費電力が低い, direct PLC DO driving; 3NO+1NC allows 3 output channels plus 1 feedback channel; AC-15/DC-13 rated, max operating frequency: 180 1分あたりのサイクル数.
場合 1: PLC Digital Output Port Expansion (最も一般的な)
シナリオ: Insufficient PLC DO points; DO ports have low current capacity (<0.5 あ) and need to drive multiple contactor coils and solenoid valves simultaneously.
配線: PLC 24 V DO connected to relay coil terminals A1/A2
Contact assignment:
NO1: Drive LC1D contactor coil
NO2: ドライブ 24 V DC solenoid valve
NO3: Run indicator lamp
NC1: Feedback to PLC DI for relay status monitoring (wire break / contact sticking diagnosis)
ハイライト: Low-power coil avoids overloading PLC outputs; built-in diode eliminates external surge suppression circuits; same TeSys K form factor for neat cabinet layout, standard panel builder solution.
産業: 工作機械, 包装機械, assembly line control cabinets.
場合 2: Auxiliary Logic Interlock & Status Collection for Main Contactors
シナリオ: Main LC1D contactors have insufficient built-in auxiliary contacts; additional interlocking, fault feedback and on/off indication are required.
Driving signal: Emergency stop circuit / safety relay output energises the CA4KN coil
Contact assignment:
NO1: Enable forward rotation circuit
NO2: Enable reverse rotation circuit
NO3: Contactor ON run lamp
NC1: Wired into reverse circuit for hardware interlock (prevents simultaneous forward & reverse operation)
注記: This is only control-circuit interlocking and cannot replace main-circuit electrical interlocks.
産業: Conveying equipment, 小型昇降機構, ファン & pump control panels.
場合 3: ファン & Damper Interlock Control for HVAC Air Handling Units
シナリオ: DDC controller outputs control damper actuators, fan contactors and alarm lamps, with one status feedback channel to the building BA system.
Driving signal: 24 V DC output from DDC energises CA4KN31BW3
Contact assignment:
NO1: Damper open command
NO2: Fan contactor coil
NO3: Running status lamp
NC1: DI input to BA system for stop / 故障フィードバック
利点: High noise immunity with built-in diode, suitable for frequent switching in weak-current building control loops; 広い動作温度範囲 (-25 ℃~ +50 ℃) for indoor plant rooms.
産業: ビルディングオートメーション, clean air conditioning, 外気処理ユニット.
場合 4: Primary & Standby Pump Rotation Control Relay
シナリオ: Level controller / PLC output switches main pump, standby pump and alarm circuits with independent status feedback.
論理: High water level signal energises the relay coil
NO1: Main pump start
NO2: Standby pump activation (coordinated with delay circuit)
NO3: Overflow alarm lamp
NC1: Relay fault detection signal to PLC
産業: Sewage lifting, 水処理, water supply control panels.
場合 5: Signal Expansion after Safety Relay Outputs
シナリオ: XPS safety relay has limited output contacts; safety OK signals need to be duplicated to inverter enable, alarm and HMI status channels.
Driving signal: Safety relay OK output energises CA4KN coil
NO1: Inverter STO / enable signal
NO2: Safety OK indicator lamp
NO3: HMI DI safety status input
NC1: Safety circuit trip alarm
Critical reminder: Safety judgment remains the responsibility of the XPS safety relay; CA4KN only serves as signal transfer and cannot be used as a safety component alone.
産業: 自動化された生産ライン, robot peripherals, cutting machinery.
場合 6: Isolated Passive Signal Transfer for Variable Frequency Drives / ソフトスターター
シナリオ: VFD relay output is a dry contact; multiple isolated signals need to be sent to PLC, local alarms and data loggers, with mixed AC/DC circuits.
Driving signal: VFD “走る” dry contact controls the relay coil
NO1: PLC DI running signal
NO2: Local AC220 V run indicator
NO3: Remote SCADA transmission signal
NC1: Stop status signal
価値: Galvanic isolation between 24 V coil side and contact side, preventing electrical noise from coupling into the VFD mainboard.
選択 & Application Best Practices (Frequent Engineering Pitfalls)
- 負荷の種類: Only for control circuit loads (接触器コイル, ソレノイド, インジケーターランプ); never for main power circuits. Rated thermal current: 10 あ, utilisation category AC-15.
- Coil note: BW3 = 24 V DC low-consumption with built-in bidirectional diode. Do NOT add external LAD4RC surge suppressors, as specified in Schneider official documentation.
- 端子: W3 = screw terminals; spring-cage alternative: CA4KN31BN3.
- Contact logic for 3NO+1NC: 3 output channels + 1 feedback channel, the most widely used contact allocation for automation panels.
- 取り付け: DIN35 rail installation; can be mounted side-by-side with LC1K contactors for consistent cabinet layout.
TeSys K Control Relays (CA2KN / CA3KN / CA4KN) – Full Model Coding Rule
完全なモデル形式: CAu KNvw + voltage code + terminal suffix
- u = Coil Type
CA2KN: ACコイル (50/60 Hz)
CA3KN: Standard DC coil (normal power consumption)
CA4KN: Low-consumption DC coil (built-in bidirectional freewheeling diode, PLC direct drive preferred; CA4KN31BW3 falls into this category)
- vw = Contact Combination (のみ 3 fixed configurations)
40: 4いいえ (4 通常開)
31: 3NO+1NC (3 開ける + 1 Closed, 最も人気のある)
22: 2NO+2NC (2 開ける + 2 Closed)
- 電圧コード + Terminal Suffix (Key Part)
W3: Screw clamping terminals
N3: スプリングケージ端子
サフィックス “3” = built-in surge suppression diode
接点構成 (のみ 3 Options for the Whole Series)
- 40 = 4NO
- 31 = 3NO+1NC (CA4KN31BW3 uses this configuration)
- 22 = 2NO+2NC
全モデルリスト: CA4KN Low-Consumption DC Coil (PLC Version, Built-in Diode)
コイル: DC low power, integrated bidirectional freewheeling diode; 端子: W3 screw / N3 spring cage
1) 24 ワシントンDCで (Most Popular: BW3 / BN3)
| 接点構成 | ネジ端子 (W3) | Spring Terminals (N3) |
| 4いいえ | CA4KN40BW3 | CA4KN40BN3 |
| 3NO+1NC | CA4KN31BW3 (Your Model) | CA4KN31BN3 |
| 2NO+2NC | CA4KN22BW3 | CA4KN22BN3 |
2) 48 ワシントンDCで (EW3 / EN3)
CA4KN40EW3 / CA4KN40EN3
CA4KN31EW3 / CA4KN31EN3
CA4KN22EW3 / CA4KN22EN3
3) 72 ワシントンDCで (SW3 / SN3)
CA4KN40SW3 / CA4KN40SN3
CA4KN31SW3 / CA4KN31SN3
CA4KN22SW3 / CA4KN22SN3
注記: CA4KN series only offers 12/24/48/72 V DC low-consumption variants; no AC coil versions. CA4KN was discontinued at the end of 2024; new projects shall adopt CA3KN models with suffix “3” as direct replacements.
CA3KN Standard DC Coil (Normal Power, Built-in Diode Suffix “3”)
Voltage Codes (スクリュー: BD/ED/FD…; 春: BD3/ED3…)
12 ワシントンDCで: JD / JD3
24 ワシントンDCで: BD / BD3 (Top replacement: CA3KN31BD3 for CA4KN31BW3)
48 ワシントンDCで: ED / ED3
110 ワシントンDCで: FD / FD3
125 ワシントンDCで: GD / GD3
220 ワシントンDCで: 医学博士 / MD3
Full Model Examples (3 Contact Types)
- 24 V DC screw terminals (with built-in diode)
CA3KN40BD3 (4いいえ)
CA3KN31BD3 (3NO+1NC, direct replacement for CA4KN31BW3)
CA3KN22BD3 (2NO+2NC)
- スプリングケージ端子: keep the voltage code unchanged, only adjust terminal suffix; 例えば, CA3KN31BD3 (スクリュー) and spring-cage variant share the same voltage code.
CA2KN AC Coil (50/60 Hz, Main Control Circuits)
Common Voltage Codes
24 Vと: B7
48 Vと: E7
110 Vと: F7
220/230 Vと: M7 / P7 (most used: CA2KN31P7)
380 Vと: Q7
Full Contact Models (ACコイル)
4いいえ: CA2KN40B7 / CA2KN40P7
3NO+1NC: CA2KN31B7 / CA2KN31P7
2NO+2NC: CA2KN22B7 / CA2KN22P7
Terminal Differentiation (W3/N3 vs Non-Suffix “3”)
- W3 = Screw clamping terminals (CA4KN31BW3)
- N3 = Spring-cage quick connect terminals (交換: CA4KN31BN3)
- Models without trailing “3”: No built-in diode; external RC snubber is mandatory for DC circuits – not recommended for direct PLC DO driving.
Discontinuation Replacement Solution (Field Retrofit)
オリジナルモデル: CA4KN31BW3 (24 V DC low-consumption, 3NO+1NC, ネジ端子)
✅ Direct drop-in replacement: CA3KN31BD3 (24 V DC 標準コイル + 内蔵ダイオード, 3NO+1NC, ネジ端子; identical footprint, plug-and-play interchange)
一般的な技術仕様 (Uniform for All TeSys K Control Relays)
Contact utilisation category: AC-15 / DC-13 (control circuit only)
従来の熱電流: 10 あ (で 50 ℃)
定格絶縁電圧: 690 V
取り付け: DIN35 rail or base plate fixing
全幅: 45 mm, same form factor as LC1K contactors for side-by-side mounting
機械的耐久性: 20 100万操作