Schneider RM17TG00 Phase Sequence & Phase Loss Monitoring Relay

RM17: Harmony RM17 series three-phase monitoring relay TG: Monitors phase sequence and phase loss only (no voltage unbalance, overvoltage or undervoltage functions) 00: 1 切替接点 (1C/O) バージョン; RM17TG20 in the same series is the 2C/O dual-contact model ✅ Core Functions Monitors three phases L1/L2/L3: Phase sequence error (逆相, motor reverse rotation protection) 段階 ...

  • 製品詳細

RM17: Harmony RM17 series three-phase monitoring relay

TG: Monitors phase sequence and phase loss only (no voltage unbalance, overvoltage or undervoltage functions)

00: 1 切替接点 (1C/O) バージョン; RM17TG20 in the same series is the 2C/O dual-contact model

✅ Core Functions

Monitors three phases L1/L2/L3:

  1. Phase sequence error (逆相, motor reverse rotation protection)
  2. Phase loss fault (loss of two or more phases; single-phase weak voltage drop will NOT trigger)

セルフパワー, energized directly from L1/L2/L3, no additional auxiliary 電源 必須

📋 Key Technical Specifications

アイテムパラメータ
Monitoring Voltage Range208~480 VAC (operating limit 183~528VAC)
頻度50/60Hz ±10%
出力接点1C/O (1 通常開 + 1 通常閉)
Rated Contact Current5A @250VAC, max.1250VA
Power-up Start Delay≤650ms
Fault Response Time≤130ms
消費電力≤22VA @400VAC 50Hz
取り付け35mm DINレール, width 17.5mm (1 モジュール)
インジケータ黄色のLED: ON under normal condition, OFF in fault state
認証CE, 過電圧カテゴリ III, IEC60255

🔌 Terminal Wiring Definition

Upper terminals: L1, L2, L3 → Connect to three-phase power supply

Lower contact terminals:

11: 一般

14: 通常開 (いいえ) (closed in normal state, open under fault)

12: 通常閉 (ノースカロライナ州) (通常の状態では開いています, closed under fault)

With correct three-phase supply and proper phase sequence: リレーが通電する, LED ON; 位相損失 / reversed phase → relay de-energizes, LEDオフ

🛠️ Typical Application Scenarios

Hoisting equipment, エレベーター, コンベアライン, water pump sets, preventing motor reverse rotation

エアコンプレッサー, chiller unit three-phase power protection

Portable equipment power access detection, emergency power switching judgment

⚠️ Troubleshooting Points

  1. LEDオフ: No power on three-phase incoming lines or loose wiring;
  2. LED fails to energize after power-up: Most likely reversed phase sequence, swap any two L phases;
  3. Single-phase voltage drop will not trigger RM17TG00. TG series only detects complete phase loss and does not monitor voltage unbalance. For unbalance/overvoltage & 不足電圧保護, select RM17TE series.

🧩 Same-series Comparison & 代替リファレンス

RM17TG00: 1C/O, 相順 + 位相損失

RM17TG20: 2C/O dual changeover contacts, 相順 + 位相損失

RM17TE00: With voltage unbalance, 過電圧, 不足電圧, phase loss and phase sequence (full-featured model)

📌 Notes

No potentiometer for threshold adjustment, fixed logic without adjustment knobs;

For three-phase 3-wire system only;

Dry contact output for PLC DI or contactor coil interlock circuit.

シュナイダー RM17TG20 Troubleshooting Document

該当する: RM17TG00 / RM17TG20 three-phase phase sequence & phase loss relay

安全上のご注意: High-voltage work must follow power cut & voltage verification. Use qualified high-voltage multimeter and wear insulated protective gear for three-phase voltage measurement.

Product Principle Review: Only monitors phase sequence and complete loss of two or more phases; single-phase voltage drop and voltage unbalance will not trigger protection. Self-powered from L1/L2/L3. 正常な状態: yellow LED ON, both contact sets energized; Fault state: yellow LED OFF, both contact sets de-energized

  1. Pre-check Preparation
  2. ツール: デジタルマルチメータ, cross screwdriver, insulating gloves
  3. 型式の確認: RM17TG20, rated monitoring voltage 208~440VAC (limit 183~484VAC), long-term operation above 440VAC is not permitted
  4. System Confirmation: Three-phase 3-wire system, no neutral wire connected; this model cannot detect single-phase drop in 3P4W system
  5. Basic Status Description: ≤650ms initialization delay after power on; fault response ≤130ms; relay stays de-energized when fault exists, auto-recovers once fault cleared
  6. Troubleshooting by Fault Symptom

症状 1: Yellow LED completely off after power-up, relay contacts no action

説明: No indicator light after energizing, 連絡先 11/14 そして 21/24 fail to close

  1. 電源を切る, inspect L1/L2/L3 terminals: Check for looseness, oxidation or poor crimping; clean dust and copper oxide on terminals
  2. 電源を入れる, measure line-to-line voltage L1-L2, L2-L3, L1-L3 at relay upper terminals with multimeter

Any line voltage <183V: Undervoltage on power supply, relay cannot operate; check upstream circuit breaker, fuse and cable breakage

No voltage on two or more phases: Upstream phase loss fault, repair power supply circuit

  1. LED still OFF with all three-phase voltages normal:

Check miswiring of L1/L2/L3; confirm power cables are not connected to contact terminals

Inspect module appearance: Cracked housing, burn marks or carbonized terminals → internal damage, replace relay directly

Cross test: Remove relay and connect to known good three-phase supply; if LED remains off, relay is defective

症状 2: Three-phase supply normal, LED stays off, relay continuously reports fault (contacts not energized)

Most frequent on-site fault: Reversed phase sequence

  1. Measure three line voltages and confirm all values between 183~484VAC with balanced three-phase voltage
  2. 電源を切る, swap any two incoming L phases (例えば. L1 and L3)
  3. Re-energize and observe LED:

LED ON and contacts close: Fault resolved, root cause reversed phase sequence

LED still OFF after twice phase swap: proceed to next step

  1. Check for virtual connection with induced voltage: Multimeter shows normal voltage but voltage collapses under load. TG series cannot identify weak single-phase drop, but will trigger phase loss alarm if single-phase voltage falls below 100V
  2. Still invalid: Relay internal failure, replace for test

症状 3: LED is ON, but no signal on output contact circuit (no PLC feedback / contactor fails to act)

Power monitoring circuit healthy, fault lies in secondary dry contact circuit

RM17TG20 has two independent changeover contact sets: 11/12/14 そして 21/22/24, both act synchronously

  1. Power off and verify contact wiring:

11, 21: Common terminals

14, 24: 通常開 (いいえ) (closed when energized; open under fault)

12, 22: 通常閉 (ノースカロライナ州) (open when energized; closed under fault)

  1. 電源を入れる (relay normal state, LED ON), measure continuity with multimeter:

11 & 14, 21 & 24: should conduct; 11 & 12, 21 & 22: should be open

  1. Manually create fault (reverse phase sequence), LEDオフ:

11 & 14, 21 & 24: 開ける; 11 & 12, 21 & 22: 行為

  1. Asynchronous action between two contact sets (one closed, one open): Internal contact damage, must replace relay
  2. Contact status correct but no signal on downstream circuit: Check PLC DI module, external interlock circuit, broken secondary wiring or blown fuse

症状 4: Random false tripping during motor operation (LEDオフ, protection trip)

  1. Monitor three-phase voltage, focus on voltage dip during motor starting:

⚠️ Important Limitation: RM17TG only detects complete loss of two phases; single-phase voltage dip will not trigger protection. Random tripping is mostly caused by instantaneous two-phase power loss or poor connection

  1. Inspect main circuit contactor, thermal relay terminals and cable lugs for loose connections, overheating and poor contact under high current
  2. Check power cables: ケーブルの損傷, earth fault or risk of phase-to-phase short circuit
  3. EMI Troubleshooting: Relay routed in parallel with power cables; relocate RM17TG away from VFDs and contactors, use separate cable trunking or shielding
  4. Confirm supply voltage does not exceed RM17TG20 upper limit 440VAC; use RM17TG00 for 480VAC application
  5. Cross replacement test: If fault disappears after installing new relay, original relay is aged and damaged

症状 5: Relay does not alarm with single-phase cut-off (protection no action)

This is NOT a fault, it is inherent design limitation!

RM17TG series only detects loss of ≥2 phases. Single-phase disconnection and single-phase voltage drop cannot trigger protection

If single-phase loss, voltage unbalance, 過電圧 & undervoltage protection required: Replace with RM17TE00 multi-function monitoring relay

Ⅲ. Quick Self-check Procedure (On-site Maintenance Checklist)

✅ Step1: 電源を切る, inspect appearance and wiring (端子, burn marks, 緩み)

✅ Step2: Power on and measure L1-L2 / L2-L3 / L1-L3 line-to-line voltages

✅ Step3: Observe LED status to locate fault domain (電源 / 相順 / relay itself)

✅ Step4: Power off and swap two L phases to verify reversed phase sequence

✅ Step5: Power off and test continuity of two contact sets to confirm switching logic

✅ Step6: Cross replace relay to confirm whether fault comes from relay or external wiring

  1. Common Misconceptions
  2. ❌ Misconception: Relay should protect on single-phase loss

✅ Note: TG series only detects loss of two or more phases; single-phase breakage is not detected.

  1. ❌ Misconception: Front panel adjustment knobs are available for threshold setting

✅ Note: RM17TG has no potentiometer, threshold fixed.

  1. ❌ Misconception: Two contact sets can act independently

✅ Note: Two contact sets operate synchronously; asynchronous action indicates relay damage.

  1. ❌ Misconception: Can be used in 3P4W system (with neutral wire)

✅ Note: For three-phase 3-wire only, neutral wire must NOT be connected.

  1. Replacement Criteria (Replace relay if any condition met)
  2. L1/L2/L3 supply voltage normal, LED remains OFF after phase sequence swap
  3. Two contact sets act asynchronously, contacts burnt or fail to switch
  4. Housing or terminals show black burn marks, bulging or carbonization
  5. Fault eliminated after installing new relay under same power condition
  6. メンテナンスの推奨事項
  7. Periodic inspection: Tighten L1/L2/L3 input terminals and contact terminals quarterly to prevent vibration-induced looseness
  8. 周囲条件: Operating temperature -20~+60℃; avoid heavy dust, humid or corrosive gas environment
  9. クリーニング: Clean module surface dust with dry brush after power cut, liquid cleaner prohibited
  10. 耐用年数: Mechanical life of contacts >10 百万サイクル; electrical life approx.100,000 cycles at 5A@250VAC

Schneider RM17 Series Three-phase Monitoring Relay Full List (Harmony Zelio, 35mm DINレール, 17.5mm 1-module width)

All models are self-powered from L1/L2/L3, no auxiliary supply required, 5A@250VAC dry contact output, for three-phase 3-wire system

  1. RM17TG (ベーシックモデル: 相順 + phase loss only, no adjustment knobs, fixed threshold)
モデル連絡先電圧範囲コア機能代表的な用途
RM17TG001C/O (1 切り替え)208~480VACPhase sequence error, ≥2 phases loss protection; No unbalance / 以上&不足電圧Single interlock, water pump and general motor protection
RM17TG202C/O (2 independent changeover)208~440VACPhase sequence error, ≥2 phases loss protection; No unbalance / 以上&不足電圧Hardware interlock + PLC alarm, hoisting, elevator

TG Series Features: No potentiometer, no adjustment window on housing, only yellow status LED; Single-phase voltage drop will not trigger alarm

  1. RM17TT / フェイシング / TU / TE (Multi-function adjustable type, transparent cover with adjustment knobs)
モデル連絡先電圧範囲監視機能
RM17TT001C/O208~480VAC位相損失 + 相順; rated voltage selectable, delay adjustable; No voltage unbalance, 過電圧/不足電圧Basic adjustable phase sequence & 位相損失, suitable for multi-voltage site
RM17TA001C/O208~480VAC位相損失 + 相順 + three-phase voltage unbalance; unbalance threshold & delay adjustable; No over/undervoltageMotor winding protection, detect three-phase asymmetry
RM17TU001C/O208~480VAC位相損失 + 相順 + undervoltage monitoring; undervoltage threshold & delay adjustable; No overvoltage, no unbalancePower supply drop monitoring, generator set, incoming power supervision
RM17TE001C/O208~480VACフル機能: phase loss+phase sequence+voltage unbalance+overvoltage+undervoltage, multiple potentiometers adjustable, true RMS measurementChiller, air compressor, UPS switching, full protection requirement

Ⅲ. RM17 Series Single-phase / DC Voltage Monitoring (同じシリーズ, non three-phase)

モデルタイプMonitoring Range連絡先
RM17UAS14DC Voltage9~15VDC1C/O
RM17UAS16AC/DCユニバーサル20~80V AC/DC1C/O
RM17UAS15AC/DCユニバーサル65~260V AC/DC1C/O
RM17UBE SeriesSingle-phase AC Over & 不足電圧24~240VAC1C/O
RM17UB310Single-phase Voltage Monitoring200~240VAC1C/O
  1. Model Suffix Coding Definition (RM17Txx00)

TG: 基本タイプ, fixed threshold, no adjustment knob, 相順 + 位相損失

TT: Adjustable basic model, 相順 + 位相損失, voltage range selectable

フェイシング: T + Asymmetry voltage unbalance detection

TU: T + Undervoltage monitoring

TE: Total full functions (相順, 位相損失, アンバランス, 過電圧, 不足電圧)

00: 1C/O output

20: 2C/O dual independent changeover contacts (only available for TG series)

  1. Quick Selection Table (Three-phase models)
要件推奨モデル
Only phase sequence+phase loss, single contact output, 480V applicationRM17TG00
Phase sequence+phase loss, dual independent dry contacts for interlock + アラームRM17TG20
Phase loss+phase sequence, multi-voltage option, delay requiredRM17TT00
Phase loss+phase sequence+three-phase unbalance (motor asymmetry protection)RM17TA00
Phase loss+phase sequence+undervoltage monitoringRM17TU00
完全な保護: phase loss+phase sequence+unbalance+overvoltage+undervoltageRM17TE00
  1. Common General Specifications
  2. 取り付け: 35mm DINレール, 1 モジュール (17.5mm);
  3. 出力ロジック: Relay energized (power normal) → contacts closed; fault → contacts open (fail-safe type);
  4. 電源: Self-powered directly from L1/L2/L3, no neutral wire, three-phase 3-wire system only;
  5. 応答時間: TG fixed ≤130ms; TT/TA/TU/TE fault delay manually adjustable;
  6. 接点の定格: 5A 250VAC resistive load; for PLC DI and contactor interlock circuit, not for direct driving of high-power loads

Ⅶ. 交換 & Upgrade Reference

RM17TG00 ↔ RM17TG20: identical function, only contact quantity differs

RM17TT00 → RM17TA00: add voltage unbalance detection

RM17TA00 → RM17TE00: add overvoltage and undervoltage window monitoring

Legacy RM22TG series is substitute series (同じ機能, different form factor)