Siemens 3RV2031-4KA10 Motor Protection Circuit Breaker

製品タイプ: SIRIUS 3RV2 series frame S2 motor protection circuit breaker (motor protector), active production model, made in Germany Model Code Explanation 3RV 2 0 31 4 K A 10 3RV: SIRIUS motor protection circuit breaker 2: 2nd generation of 3RV2 series 0: 標準バージョン, no pre-fitted auxiliary contacts 31: Frame size S2 4: 旅行 ...

  • 製品詳細

製品タイプ: SIRIUS 3RV2 series frame S2 motor protection circuit breaker (motor protector), active production model, made in Germany

  1. 型式コードの説明

3RV 2 0 31 4 K A 10

3RV: SIRIUS motor protection circuit breaker

2: 2nd generation of 3RV2 series

0: 標準バージョン, no pre-fitted auxiliary contacts

31: Frame size S2

4: Trip current rating code

K: Thermal setting range 62~73A

あ: ネジ端子

10: 標準遮断容量 (without additional contacts)

  1. Core Technical Data
アイテム仕様
フレームサイズS2, width 55mm, DINレール取付
3P
Thermal overload setting range62 ~ 73A (adjustable via front knob)
Instantaneous electromagnetic short-circuit trip949あ (修理済み)
旅行クラスクラス 10 (for normal motor starting; trips within 10s at 7.2× rated current)
定格動作電圧AC690V, DC250V
Rated ultimate short-circuit breaking capacity Icu@400V65の
接続タイプネジ端子
Built-in auxiliary contactsなし; auxiliary contact modules must be fitted separately
適用モータ出力 (AC400V)約. 37kW 3-phase motor
正味重量1.172kg
HS Customs Code85362090
  1. 保護機能
  2. 過負荷保護: Inverse-time thermal trip via bimetallic strip, motor overload protection and phase loss protection
  3. 短絡保護: Instantaneous electromagnetic trip for rapid short-circuit disconnection
  4. Front-mounted TEST pushbutton for manual tripping test of the mechanism
  5. Handle position indication: の上 / オフ / fault trip position; padlockable for lockout
  6. 配線 & 設置仕様

Main circuit conductor: マックス. 1×35mm² solid/stranded cable; 最大. 1×25mm² fine-stranded cable with ferrule

Tightening torque for main terminals: 3.0~4.5 N·m, M6ネジ

Accepts top-in or bottom-in wiring; DIN35mm rail mounting

Can be assembled with SIRIUS 3RT contactor to form a direct-on-line starter, constituting a motor protection starter unit

  1. 選択 & 交換情報

Same-series Replacement (Same Rating)

3RV2031-4KA15: Version with pre-fitted auxiliary contacts (1NO+1NC)

注記: 3RV2031-4KA10 has no built-in auxiliary contacts. For feedback signals, 3RV2901 auxiliary contact accessory must be mounted externally.

Domestic Alternative Reference

シーメンス local China 3RV5/3RV6 series equivalent: 3RV5031-4KA10 (domestic frame S2, 62~73A, ネジ端子, largely identical parameters)

  1. 代表的な用途

3-phase asynchronous motors, ファン, ウォーターポンプ, コンプレッサー, conveyor motor circuit protection

Motor starter circuits inside control cabinets, combined with contactors as starter assemblies

Motor protection for machine tools, 空調設備, 梱包, chemical automation equipment

  1. トラブルシューティングガイド
  2. Trips immediately upon motor start: Usually short-circuit trip. Check motor windings and cables for phase-to-phase or earth short circuit.
  3. Trips after running for some time: 過負荷. Recheck motor rated current and reset the adjustment knob; inspect for mechanical jamming.
  4. 閉められない: 機構の故障, or previous short-circuit trip not fully reset. Press TEST button to reset before closing.
  5. 中古品検査チェックリスト
  6. 外観: No cracked housing, burn marks, or overheating discoloration on terminals
  7. 機械的操作: Smooth handle operation; TEST button triggers trip correctly and resets properly
  8. Continuity: Main contacts conduct when closed and isolate when open; no internal short circuit
  9. 絶縁: Measure insulation resistance between phases and to earth using a megger

Siemens 3RV2031-4KA10 (フレームS2) 設置寸法

All 3RV2031 models of frame S2 share identical outer dimensions

Unit Overall Dimensions (幅×高さ×奥行き)

Width W: 55 mm (55mm cabinet space per unit)

Height H: 140 mm

Depth D: 149 mm (from rail mounting surface to front of operating handle)

取付方法

レール: DIN 35mm standard rail (あなたのもの 60715), clip-on mounting; optional screw locking

取付方向: any orientation (垂直, horizontal installation allowed)

Cabinet Clearances (放熱 / Electrical clearance)

Side-by-side mounting: 0mm gap allowed for adjacent units

Vertical clearance top & 底: ≥50mm at upper/lower terminal zones

Clearance to earthed cabinet metalwork: ≥10mm lateral clearance

Cabinet cutout (if door extension handle is used)

The 3RV2 unit is DIN-rail mounted inside the cabinet. If an extended door operating handle (別売り) が必要です:

Cutout width: 約. 48mm, cutout height: 約. 130mm

注記: No cabinet cutout required without extension handle; unit is fully installed inside enclosure on DIN rail.

補足事項

With 3RV2901 side-mounted auxiliary contact: overall width unchanged, slight increase in depth

When back-to-back assembled with 3RT contactor as starter: total depth equals sum of both components

Siemens 3RV2031-4KA10 Weight

✅ Net weight (unit only, no packaging): 1.17 kg (manufacturer nominal 1.172 kg; use 1.17kg on engineering drawings)

All S2 frame 3RV2031 models have similar weight, range 1.07~1.18 kg. Variations come from internal trip components; standard value for 3RV2031-4KA10 is 1.17 kg.

補足事項

  1. Excluding accessories: No 3RV2901 auxiliary contacts, door extension handles or other attachments. Weight increases slightly when accessories are fitted.
  2. Gross weight with factory carton: 約. 1.30 kg (for logistics estimation)
  3. Unit conversion: 1.17 kg ≈ 2.58 ポンド

Siemens 3RV2031-4KA10|Cross-brand Comparison + MPCB Product Series List

Reference device: 3RV2031-4KA10, frame S2, 55幅mm, 3P, 62~73A, ネジ端子, Class10, Icu@400V=65kA, 補助接点は内蔵されていません, for 37kW@400V motor

⚠️ Important notice: No fully pin-to-pin drop-in replacement available. The below are function/rating/frame equivalent selections. Cabinet mounting, アクセサリー, breaking capacity and instantaneous trip values must be verified. Protection coordination validation is mandatory before formal project replacement.

  1. Siemens Internal Cross-reference (Preferred Replacement)
モデル説明Difference vs 3RV2031-4KA10
3RV2031-4KA10Reference unit, imported Germany frame S2, 62~73A, ネジ端子, 補助接点は内蔵されていませんBase unit
3RV2031-4KA15同じ定格電流, fitted with 1NO+1NC auxiliary contactsComes with built-in aux contacts; rest parameters identical
3RV5031-4KA10Siemens China local frame S2, 62~73A screw terminalsParameters largely identical, slightly lower Icu, economical domestic version
3RV1031-4KA10Legacy 3RV1 frame S2, same current ratingOlder generation, 段階的に廃止された; similar outline but accessories not fully compatible

3RV2 frame size overview

S00: 45mm, max 16A, motor ≤7.5kW

S0: 45mm, max 40A, motor ≤18.5kW

S2: 55mm, max 80A, motor ≤37kW (frame of this model)

S3: 70mm, max 100A, motor ≤45~55kW

  1. Imported Brand Equivalent Cross-reference (62~73A, S2 frame class MPCB)
ブランド製品シリーズ同等モデルKey Parameter Notes & 違い
シュナイダーTeSys GV3 (GV3ME)GV3ME8056~80A adjustable, ロータリーノブ, 3P, ネジ端子; 55ミリフレーム, Class10. GV2 max 40A, GV2 cannot replace this model. Icu to be checked; instantaneous trip differs from Siemens
ABBMS series motor protection circuit breakerMS165-7360~73A adjustable, 3P, DINレール, 55ミリフレーム; MS165 is ABB equivalent to S2 frame. MS132 max 32A, insufficient rating, not suitable
イートン (モーラー)PKZ2 motor protectorPKZ2-7362~73A, 3P, rotary operation, S2 frame, Class10. PKZ1 small frame; PKZ2 corresponds to 3RV2 S2
オムロンBM series motor protection breakerBM6R-63Adjustment range near 62~73A, 3P; limited domestic adoption, verify breaking capacity during selection
  1. 国内ブランドの代替品 (Cost Reduction for Projects)
ブランドシリーズ同等モデル備考
チントNS2 seriesNS2-80 62~73ANS2 motor protection breaker, 55mm, Class10, ネジ端子
美味しいCDV6 seriesCDV6-80 62~73ASame function MPCB, economical domestic type, lower Icu vs imported brands
ネーデルNDM2-MNDM2-M80 62~73AHigh-end industrial domestic, より高い遮断容量, suitable for critical circuits
  1. MPCB Product Portfolio Overview by Brand (Thermal-Magnetic DIN Rail Motor Protection Circuit Breaker)

シーメンス

3RV2 (SIRIUS main import range: S00/S0/S2/S3, 0.1~100A)

3RV5 / 3RV6 (domestic economical range, S00/S0/S2)

3RV1 (legacy model, phasing out)

3VU (old compact type, max 63A)

シュナイダー

GV2: Small frame 45mm, 0.1~40A

GV3: Medium frame 55mm, 40~80A (counterpart to 3RV2 S2)

GV7: Large frame, 80~150A

ABB

MS116: Small frame

MS132: Medium frame, max 32A

MS165: 55mm frame up to 80A (counterpart to 3RV2 S2)

MO series (high breaking capacity version)

イートン (モーラー)

PKZ0 / PKZ1: Low current

PKZ2: S2 frame up to 80A

PKZ3: Large frame

Main Domestic Brands

Chint NS2

Delixi CDV6

Nader NDM2-M

Changshu CM1-M (motor protection variant)

  1. Risks for Replacement Selection (Critical for Engineering)
  2. Different instantaneous short-circuit trip (N factor): 3RV2031-4KA10 fixed at 949A. Schneider GV3 and ABB MS165 have different electromagnetic trip thresholds. Short-circuit protection coordination changes. Direct replacement may cause loss of selectivity.
  3. Ultimate breaking capacity Icu: 3RV2 is 65kA@400V. Domestic models generally have lower Icu and shall NOT be used for circuits with high prospective short-circuit current.
  4. 機械的インターロック & contactor assembly: 3RV2 can directly snap onto 3RT contactor to form starter. Cross-brand devices cannot mechanically clip together, separate mounting brackets required.
  5. Auxiliary contact accessory systems are incompatible; mounting depth, terminal torque and maximum cable cross-section differ.
  6. UL/CE certification: No arbitrary brand replacement for export machines.
  7. Recommended Selection Rules

Cabinet retrofit, minimal modification: Siemens 3RV5031-4KA10 (domestic same-brand replacement)

Import brand substitution: Schneider GV3ME80 / ABB MS165-73, short-circuit protection coordination recheck required

Non-critical domestic circuit cost saving: Chint NS2-80 / Delixi CDV6-80