This legacy Siemens SIRIUS front-mounted auxiliary contact features 1 通常閉 (ノースカロライナ州) 接触, compatible with 3TF3 / 3TF4 contactors. Original production discontinued on Oct 01, 2021 with no identical OEM replacement. Recommended drop-in alternative: domestic compatible 3TY7561-1AA00, or upgrade to 3RH2911-1AA01 for 3RT6 series contactors. Model Code Breakdown Code Segment Definition 3TX Base designation for ...

  • 製品詳細

This legacy Siemens SIRIUS front-mounted auxiliary contact features 1 通常閉 (ノースカロライナ州) 接触, compatible with 3TF3 / 3TF4 contactors. Original production discontinued on Oct 01, 2021 with no identical OEM replacement. Recommended drop-in alternative: domestic compatible 3TY7561-1AA00, or upgrade to 3RH2911-1AA01 for 3RT6 series contactors.

  1. モデルコードの内訳
コードセグメント意味
3TXBase designation for Siemens SIRIUS snap-on front auxiliary contact blocks
4001Contact configuration code: 1ノースカロライナ州 (single normally closed); 4010 = 1NO (single normally open)
-2あ取り付け & terminal specs: front snap-in installation, no contact status indicator window, captive screw clamp terminals (exclusively designed for 3TF3/3TF4 contactors)
状態Discontinued from Oct 01, 2021; OEM note: Product was deleted without replacement
  1. Core Electrical Specifications
アイテム価値備考
接点構成1ノースカロライナ州, positively drivenDesigned for safety circuit compliance
Conventional Thermal Current (Ith)10 あRated continuous operating current
AC-15 Breaking Capacity5.6 A @ 230 VACBreaking capacity for control circuits
3.6 A @ 400 VAC
2.2 A @ 690 VAC
定格絶縁電圧 (ウイ)690 VMaximum permissible operating voltage
インパルス耐電圧6 kVElectrical isolation safety rating
機械的耐久性10 100万操作Far exceeds service life of base contactor
電気的耐久性1 100万操作 (AC-15 duty)Under rated cyclic load
TerminationCaptive clamping screwsFor solid conductors: 0.75~2.5 mm²
侵入保護IP20Finger-safe & 防塵
動作温度-25℃~+55℃ストレージ: -55℃ ~ +80℃
準拠基準IEC60947-5-1, GB14048.5CE & RoHS certified
  1. Full Same-housing Model List (3TX4 Series)
注文コードContact LayoutMounting StyleMatching Contactor状態
3TX4001-2A1ノースカロライナ州Front snap-on3TF30~3TF34 / 3TF40~3TF45製造中止
3TX4010-2A1いいえFront snap-on同上製造中止
3TX3001-2A1ノースカロライナ州Side-mountedLegacy 3TB contactors製造中止
3TX3010-2A1いいえSide-mounted同上製造中止
3TX4002-2A2ノースカロライナ州Front snap-onHigh-current 3TF range製造中止
3TX4012-2A1NO+1NCFront snap-on同上製造中止
  1. Full Compatible Contactor List (Exclusive for Front Snap Fit)

Only applicable to below 3TF series, incompatible with newer 3RT / 3RV ranges:

3TF30: 3TF3000~3TF3090 (9A~12A)

3TF31: 3TF3100~3TF3190 (12A~16A)

3TF32: 3TF3200~3TF3290 (16A~25A)

3TF33: 3TF3300~3TF3390 (25A~32A)

3TF34: 3TF3400~3TF3490 (32A~40A)

3TF40~45: 3TF4000~3TF4590 (40A~95A)

> 注記: One contactor can mount 1 front block + 2 side auxiliary blocks simultaneously, max expansion up to 6 補助接点 (3NO +3NC).

  1. Replacement Selection Guide for Obsolete Item

5.1 Direct Drop-in Replacement (No Contactor Modification)

Replacement PNブランド接触互換性利点
3TY7561-1AA00Siemens domestic alternative1ノースカロライナ州Identical snap dimensionプラグアンドプレイ, 費用対効果の高い
3TX4001-2BLegacy Siemens1ノースカロライナ州Same function with indicator lampObsolete stock only, 高コスト
LC1-D Auxiliary Contactシュナイダーエレクトリック1ノースカロライナ州Requires adapter bracketEstablished brand, 安定したパフォーマンス

5.2 Full Unit Upgrade (3TF → 3RT6)

アップグレードオプションNew ContactorMatching Auxiliary Contact利点応用
標準アップグレード3RT6026~3RT60363RH2911-1AA01 (1ノースカロライナ州)長寿命, intelligent monitoringNew construction & equipment retrofit
機能拡張3RT6040~3RT60563RH2911-1AA01 + 3RH2911-1BA01Multi-contact combinationComplex control circuits
  1. アプリケーション環境 & Industrial Cases

✅ Approved Application Scenarios

  1. Motor Control Circuits: Fault feedback & star-delta interlock for 3TF contactors of fans & ウォーターポンプ
  2. PLC Interface: NC contact feeds contactor open/closed status into PLC digital input modules
  3. Safety Interlock: 非常停止 & access door protection; NC forced opening cuts control supply (EN準拠 60204-1)
  4. ステータス表示: Pilot lamp power switching; NC opens to turn off indicator when contactor energizes

❌ Forbidden Applications

  1. Direct main-circuit loading: Designed exclusively for control loops (coils, pilot lamps, PLC signals); never connect to power main circuit
  2. Harsh ambient: 避ける >60℃, 重い粉塵, corrosive chemical & non-enclosed cabinets (accelerates contact oxidation)
  3. High-frequency cycling: >10 サイクル/分; use solid-state relays instead
  4. DC heavy-load circuits: AC-15 rating invalid for DC-13 duty; select dedicated DC auxiliary contacts

産業応用事例

業界応用Contact Function
空調設備AC compressor contactorFault stop signal to building automation system
水処理Water pump motor controlOverload interlock with main contactor
General MachineryConveyor controlEmergency stop cut-off for safe shutdown
配電Backup power transferContactor status monitoring to prevent faulty switching
  1. 一般的な障害のトラブルシューティング
故障Root CauseRemedy
Open circuit / 接触不良1. Contact oxidation under humid condition1. Replace with compatible 3TY7561
2. 配線の緩み2. Retighten terminal screws
Contactor pulls in but NC fails to open1. Loose & fallen snap clip1. Reinstall and lock into position
2. Mechanical blockage inside block2. Replace block; inspect deformed contactor shaft
Contact arcing & burnout1. Exceeding AC-15 rated current1. Add intermediate relay for load expansion
2. High inductive surge from load2. Fit RC snubber circuit for surge suppression
Abnormal overheating1. High contact resistance at terminals1. Clean terminals & re-terminate
2. Excessive ambient temperature2. Improve ventilation or use high-temperature variant
  1. Quick Selection Mnemonic

4001 =NC, 4010 = NO; front snap exclusively for 3TF;<br>Obsolete → swap to 3TY; upgrade to 3RT with 3RH;<br>Only for control circuit, never main power, excellent for safety interlock!

  1. HSコード & 航空輸送のコンプライアンス

HSコード: 85365000 (Electrical switching apparatus for circuit protection)

Air Transport Classification: 非危険物, purely mechanical contacts with no lithium battery/supercapacitor, compliant with IATA DGR

CE認証: Complies with Low Voltage Directive 2014/35/EU; Certificate of Conformity available upon request

Application Scope of 3TX4001-2A (Front-mounted 1NC Auxiliary Contact)

Product Feature: Snap-on external 1NC contact for 3TF3/3TF4 contactors, rated AC-15, dedicated for secondary control circuit only, NOT permitted in main power circuit.

  1. Standard Common Applications

1.1 Motor Start-Stop Control (ファン, Water Pumps, エアコンプレッサー)

  1. Passive running status feedback

Contactor coil energizes → NC opens, sends closing/running feedback signal to PLC DI module; coil de-energizes → NC resets closed to transmit stop signal.

Typical usage: Chilled water pumps, cooling blowers, 循環ポンプ, central air-conditioning units.

  1. Electrical interlock protection

Mutual NC interlock between two contactors (forward/reverse or star-delta) to avoid simultaneous closing and phase short-circuit.

例: Star-delta motor starter interlock between star & delta contactors.

1.2 工作機械 & Automation Equipment (Lathe, Conveyor, Injection Molding Machine)

  1. Cabinet door interlock: NC of main contactor wired into safety loop; if contactor is welded closed, NC stays open to block equipment restart.
  2. Conveyor sequential interlock: Interlock between upstream & downstream conveyor contactors to prevent mechanical collision from misoperation.
  3. 故障警報: Normally closed NC in series with fault indicator lamp; lamp lights at standby/shutdown and goes off when contactor pulls in.

1.3 HVAC Industry (Central AC, Fresh Air Unit, Smoke Exhaust Fan)

  1. BA system signal collection: Fan contactor NC feeds start/stop remote data to building management controller.
  2. Fire smoke exhaust interlock: NC links with fire damper; damper shutdown cuts fan control circuit.

1.4 Water Treatment Equipment (Dosing Pump, Sewage Pump, Aeration Blower)

  1. Pump overload linkage: Thermal relay trip resets contactor, closed NC triggers audible-visual fault alarm.
  2. Duty/standby pump auto-switch: Main pump fault closes NC to activate backup pump automatically.

1.5 LV Power Distribution Panels

  1. Capacitor compensation cabinet: NC of switching contactor feeds capacitor switching status to reactive power regulator.
  2. ATS cabinet: Electrical interlock between normal & backup supply contactors to eliminate cross-source short-circuit risk.

1.6 Hoisting & Elevator Auxiliary Control

Brake contactor NC of overhead crane feeds brake open/closed feedback; also for cooling fan contactor status monitoring on elevators.

  1. Safety Circuit Exclusive Usage (Positively Driven Contact per Machinery Safety Standards)
  2. Emergency stop monitoring: Detects welded contactor fault; mechanically stuck contactor keeps NC open to lock control power off.
  3. Safety guard circuit: Equipment door opening de-energizes main contactor, closed NC locks startup circuit.
  4. Low-power Indicator & Small Relay Driving
  5. Standby pilot lamp: NC closed to light indicator at idle; NC opens to turn lamp off during equipment operation.
  6. Mini intermediate relay drive: NC switching controls relay coil to amplify load capacity.
  7. Prohibited Application List
  8. ❌ Never connect to 220V/380V main power loop; AC-15 rating only for control loads, cannot directly drive motor/heater high-power loads.
  9. ❌ Avoid >55℃, strong acid/alkali corrosion & unprotected open-air cabinets (accelerates contact oxidation & bad conduction).
  10. ❌ Unsuitable for heavy DC loads (no DC-13 rating; DC breaking easily causes arc burnout).
  11. ❌ Ban over 15 switching cycles per minute (fast mechanical wear; replace with solid-state relay).