The IP8000 is a classic SMC mechanical E/P electro-pneumatic positioner (non-smart, no HART). It is designed for linear-stroke pneumatic diaphragm actuators. It receives a 4~20mA current signal and converts it into supply air pressure to drive コントロールバルブ. It replaces the older IP6000 series. The IP8100 in the same series is for rotary-stroke applications. The IP8001/IP8101 are smart versions with auto-tuning and share the same housing.
✅ Key Technical Specifications
| アイテム | IP8000 (Lever Type) |
| 入力信号 | DC 4~20mA, 入力抵抗: 235±15Ω |
| Supply Air Pressure | 0.14~0.7 MPa |
| Applicable Stroke | 10~85mm (linear valve stem) |
| 正確さ | Sensitivity ≤0.1%FS; Linearity ±1%FS; Hysteresis ≤0.75%FS; Repeatability ±0.5%FS |
| 侵入保護 | IP65 (IEC60529) |
| 周囲温度 | -20~80℃ for standard model; ExdⅡBT5 explosion-proof: -20~60℃ |
| Air Ports | Rc1/4 / G1/4 / 1/4NPT; Gauge port Rc1/8 |
| 電気接続 | G1/2, M20×1.5, 1/2NPT optional |
| 耐振動性 | No resonance within 5~200Hz |
| 取付規格 | Compliant with NAMUR, DIN/IEC 60534-6-1 brackets |
📌 Model Code Definition (IP8000-□□□)
IP8000: Lever-type mechanical electro-pneumatic positioner
- Pressure gauge specification: 0=0.3MPa, 3=1.0MPa
- 工事: Standard housing / ExdⅡBT5 explosion-proof terminal box
- 付属品: Restrictor pilot valve, yoke linkage, extended feedback lever, 等.
- Thread type, CE marking, special custom codes (例えば. X310=IP66)
🛠 Working Principle & 設置ガイドライン
- 原理: A 4~20mA current energizes the torque motor. The nozzle-flapper amplifies the signal to control the output air pressure of the pilot valve. The feedback lever captures the actual valve stem position to form a closed loop, ensuring valve position matches the input signal.
- Key Installation Rule: で 50% 信号 (12ミリアンペア), the feedback lever should form a 90° right angle with the valve stem. Select the internal feedback spring according to single-acting or double-acting actuators.
- 調整: Mechanical Zero and Span knobs. Supports split range operation. Equipped with manual/auto switching screw for manual air supply during commissioning.
⚠️ Common Troubleshooting
- Valve fails to move
No supply air or insufficient air pressure; 4~20mA wiring reversed; nozzle/restrictor blocked by dust; torque motor damaged.
- Oscillation / 狩猟
Incorrect feedback lever mounting angle; unstable supply air pressure; stuck pilot valve; excessive friction of valve packing.
- Poor linearity / Zero drift
Zero/span not calibrated; loose feedback linkage; air piping leakage; large ambient temperature variation.
- Insufficient output pressure
Foreign matter jamming pilot valve; leaking actuator diaphragm/cylinder; clogged air filter.
Maintenance Reminder: Cut off air supply and fully vent pressure before disassembly. Clean nozzle orifice with a 0.2mm fine wire. Apply TORAY SH45 silicone grease lightly when assembling O-rings.
📋 Model Selection & 代替案
IP8000: 機械式, linear stroke lever. For conventional control valves, 低コスト, 連絡がありません.
IP8100: 機械式, rotary cam, for butterfly and ball valves.
IP8001: Smart linear stroke. Auto-calibration, ハート, 故障診断, upgrade replacement for IP8000.
国内代替品: Domestic E/P positioners such as Wuzhong and Chuanyi. Verify bracket, air port and stroke matching.
📎 Typical Application Scenarios
Continuous regulation of flow, pressure and level on linear pneumatic diaphragm control valves in chemical, 水処理, 空調設備, 紙, 油 & gas pipelines. Explosion-proof versions ExdⅡBT5 are available for hazardous areas.
SMC IP8000 Electro-Pneumatic Valve Positioner — Application Scenarios
The IP8000 is a linear-stroke mechanical E/P positioner matching diaphragm linear pneumatic control valves. It converts 4~20mA analog signal into air pressure to drive valve stem for continuous process regulation. No HART communication.
🏭 Industry Applications
- 水 / 廃水処理
Inlet flow regulation, pH dosing line, 液面制御, aeration pressure regulation. Standard non-explosion model is sufficient; IP65 preferred for outdoor installation.
- 空調設備 & Heating Networks
Temperature control for primary/secondary side of heat exchangers, regulating steam/hot water linear control valves.
- Paper Industry
Pulp concentration control, white water flow, steam pressure regulation. Dust-prone workshop; air filtration is mandatory to prevent nozzle blockage.
- 化学工業 (Use ExdⅡBT5 explosion-proof IP8000 for hazardous zones)
Continuous regulation of flow, pressure and level in process pipelines. Explosion-proof housing required for solvents and light hydrocarbon hazardous areas.
注記: IP8000 is mechanical without smart diagnosis. Use IP8001 if HART and auto-tuning are required.
- 食べ物 & 飲料 / 医薬品 (Sanitary Service)
精製水, wash water and steam regulation, paired with sanitary linear control valves. Prefer clean instrument air.
- 力 & 火力発電所
Boiler feedwater, desuperheating and pressure reduction, condensate level control; auxiliary process control valves.
- 油 & Gas Storage & 交通機関 (Explosion-proof Version)
Pressure and flow regulation for crude/product pipelines, tank level control. Exd explosion-proof model for explosive hazardous areas.
✅ Suitable Valve Types
Single-acting / double-acting linear pneumatic diaphragm control valves (best match)
Cage guided valves, single-seat valves, cage control valves
❗ Butterfly valves, ball valves and other rotary valves require IP8100, IP8000 is not applicable.
📌 Application Characteristics
制御タイプ: Continuous modulating (not on/off valve). 4~~20mA corresponds to 0~~100% valve travel.
Air source: クリーン, ドライ, oil-free compressed air. Air filter regulator (空軍) must be installed upstream.
利点: シンプルな構造, 簡単なメンテナンス, good anti-EMI performance. Suitable for sites without bus communication requirements and limited budget.
制限事項: Mechanical feedback, no auto-calibration. Manual zero and span adjustment required; no fault diagnosis.
❌ 推奨されないシナリオ
- Severe oscillation, strong corrosive gas (extra housing protection required).
- Remote diagnosis, HART通信, auto-tuning required → upgrade to IP8001.
- Rotary butterfly / ball valves → select IP8100.
- ひどい粉塵, unpurified instrument air (high risk of nozzle clogging).
SMC IP8000 — Selection Checklist
Applicable to IP8000 linear mechanical electro-pneumatic positioner; Use IP8100 for rotary applications; IP8001 smart model has separate selection rules.
- アクチュエーター & Valve Basic Information
| チェック項目 | Selection Requirements & 備考 |
| Actuator Type | Linear stroke diaphragm pneumatic actuator (single-acting / 複動式). Not for rotary butterfly/ball valves. |
| Valve Stem Stroke | 10~85mm; confirm actual stroke. Out-of-range travel invalid; too small stroke degrades feedback lever accuracy. |
| Actuator Action | □ Single-acting (スプリングリターン), replace internal feedback spring inside positioner |
| □ Double-acting (no spring, bidirectional air supply), replace internal feedback spring | |
| バルブの種類 | Single-seat / cage / cage-guided modulating control valves; modulating service, not on/off valve |
| Stem Diameter & Mount Bracket | DIN/IEC 60534-6-1 / NAMUR standard. Verify feedback linkage and yoke accessories. Excessive stem wobble causes oscillation. |
- プロセス & 動作条件
| チェック項目 | Selection Requirements & 備考 |
| Process Media | 水, steam, 空気, general chemical fluids. Evaluate housing protection for highly corrosive media. |
| Explosion-proof Requirement | □ Standard non-explosion (safe area) |
| □ ExdⅡBT5 explosion-proof (危険区域, temperature limit: -20~60℃; standard model -20~80℃) | |
| 周囲温度 | 標準: -20℃~+80℃; 防爆: -20℃~+60℃. Heat insulation required for over-temperature sites. |
| Enclosure Protection | Standard IP65; IP66 optional (suffix X310). IP65+ recommended for outdoor, 湿気やほこりの多い環境. |
| 振動 | No resonance from 5~200Hz. Reinforce linkage under heavy vibration to avoid continuous hunting. |
| Control Requirement | 4~20mA analog continuous modulation; No HART, no auto-tuning. Manual zero/span calibration needed. |
- Air Supply System Check (Highest Failure Source)
| チェック項目 | Selection Requirements & 備考 |
| Supply Pressure Range | 0.14~0.7 MPa. Stable pressure; pressure fluctuation easily triggers valve oscillation. |
| Air Quality | ドライ, クリーン, oil-free compressed air. Pre-install air filter regulator (空軍) to remove water, oil and dust. Dust environment easily clogs nozzle. |
| Air Port Thread | G1/4 / Rc1/4 / 1/4NPT; gauge port Rc1/8. Confirm thread before ordering. |
- Electrical Check
| チェック項目 | Selection Requirements & 備考 |
| 入力信号 | DC 4~20mA; Input resistance 23515. Match signal source load capacity. |
| Electrical Entry | G1/2 / M20*1.5 / 1/2NPT. Explosion-proof model requires explosion-proof cable gland. |
| 配線 | 2-wire 4-20mA. Polarity matters; reversed polarity causes no operation. Shielded cable recommended for long distance, single-end grounding. |
- Auxiliary Accessories Selection
□ Pressure gauge: 0=0.3MPa, 3=1.0MPa (select based on output pressure range)
□ Feedback lever, yoke linkage (matched to actuator stroke)
□ Air filter regulator, air tubing
□ Mounting bracket and fasteners
□ Explosion-proof cable gland (mandatory for explosion-proof models)
- Exclusion Criteria (Do NOT select IP8000 if any applies)
- Rotary valve (butterfly / V-ball valve) → use IP8100
- HART通信, 遠隔診断, auto-tuning required → use IP8001
- Unpurified air source with heavy dust, oil and condensate
- Valve stroke >85mm or <10mm
- Heavy corrosion, heavy shock vibration without protective measures
- 選定例 (Model Code Reference)
IP8000-3 (1.0MPa gauge) + 防爆 + G1/4 air port + M20 electrical entry
IP8000-301: 1.0MPa gauge, standard housing, standard lever assembly
- 設置前検査
- Air piping fully purged to remove welding slag and debris.
- Feedback lever near 90° at 50% 信号 (12ミリアンペア).
- No leakage on actuator; packing friction shall not be excessive.
- Shielded cable grounding; separate routing from power cables to avoid VFD interference.
SMC IP8000 Electro-Pneumatic Valve Positioner — Maintenance Manual
Applicable to IP8000 mechanical linear E/P positioner; Pre-work safety: Disconnect 4~20mA signal, shut off air supply and vent pressure. Never open housing under pressure.
- Maintenance Intervals (毎日 / 四半期ごと / 年間)
1) Daily Routine Inspection (per shift / daily visual check)
- Check housing for air leakage, 結露, corrosion and loose fittings.
- Observe two pressure gauges for stable readings; watch for fluctuation/hunting.
- Check valve stem movement: smooth travel, no sticking or abnormal noise.
- Drain condensate from air filter regulator in a timely manner.
- Check mounting bracket, feedback linkage and bolts for looseness.
Warning sign: Gauge needle jumping continuously, valve hunting → inspect feedback mechanism or nozzle blockage first.
2) Quarterly Maintenance (毎 3 月)
- Inspect filter element of air filter regulator; replace if contaminated.
- Check feedback lever, yoke and pin shafts: apply minimal grease (Do NOT over-lubricate! Excess grease traps dust and clogs nozzle).
- Tighten hardware: positioner mounting bolts, tubing fittings and terminal blocks.
- 機能テスト: input 4mA, 12ミリアンペア, 20ミリアンペア, record zero and span deviation.
- Inspect cable and cable gland; ensure sealing intact, no water ingress.
3) Annual Overhaul (once per year; 毎 6 months under harsh conditions)
- Disassemble unit, clean internal housing, focus on nozzle, flapper and pilot valve restrictor (highest failure point).
- Disassemble and inspect O-rings; replace full seal kit if aged, hardened or cracked.
- Inspect torque motor coil for overheating discoloration; check nozzle-flapper gap.
- Re-calibrate zero and span, record calibration data.
- Inspect air tubing; replace aged hoses.
- Additional check for explosion-proof version: explosion joint surface undamaged, gasket intact, flameproof gap compliant.
Harsh service (ほこり, 湿度, wastewater, 紙): reduce maintenance interval by half.
- Key Component Maintenance
✅ Nozzle & Flapper (Most Common Fault Source)
- クリーニング: Use 0.2mm fine nylon/copper wire to gently clear nozzle orifice. Do not scratch nozzle surface with hard steel wire.
- Blow dust with dry compressed air at low pressure (≤0.2MPa). Never flush positioner internals with liquid.
- Flapper surface free of scratches and oil contamination. Scratches cause continuous hunting; replace nozzle-flapper assembly.
- 要件: Instrument air must be dry and oil-free. Oil film on nozzle-flapper causes drift and oscillation.
✅ Feedback Lever Assembly
- Apply only tiny amount of lubricant to pin shafts and pivots; no heavy grease.
- Check linkage for deformation; no sticking during stem movement.
- で 50% 信号 (12ミリアンペア), lever should stay near 90°. Readjust mounting if angle deviates largely.
✅ Seals (O-rings)
O-rings age and harden under large temperature fluctuation and continuous operation.
Apply thin layer of TORAY SH45 silicone grease when replacing O-rings, avoid over-application.
Prevent scratches on O-ring grooves during assembly.
✅ Electrical Section
- Inspect 4~20mA 2-wire terminals for oxidation and looseness; single-end grounding for shielded cable.
- Explosion-proof model: power cut before cover removal. Do not damage flameproof mating surface; seal gasket and cable gland must remain sealed.
- Separate signal cables from power cables to avoid VFD interference.
- Long-Term Shutdown Preservation (Out of service >1 月)
- Shut off air supply and vent pressure; disconnect 4-20mA signal.
- Set valve to mid-position (50% オープニング) to reduce long-term single-side spring stress.
- Drain condensate from air filter.
- Cover housing for dust protection to avoid dust accumulation on nozzle-flapper.
- Purge air piping and re-calibrate zero & span before recommissioning.
- 禁止されている操作 (重要な警告)
❌ Open positioner housing under pressure or powered condition
❌ Blast nozzle-flapper assembly with high-pressure compressed air
❌ Apply large amount of grease (traps dust and clogs nozzle)
❌ Flush internal parts with liquid (only wipe housing exterior with damp cloth)
❌ Force feedback lever; may deform torque motor and cam
❌ Use instrument air with oil, water and heavy contaminants
- Post-Maintenance Verification Procedure
Follow sequence after maintenance:
- Apply air supply, verify all air joints leak-free.
- Connect 4~20mA signal generator.
- 4mA → zero calibration; 20mA → span calibration; repeat 2~3 cycles.
- Test linearity at midpoint 12mA; confirm no oscillation or lag.
- Record calibration data and file maintenance log.
- Quick Fault Reference During Maintenance
- Valve hunting / small cycling: Dirty nozzle/flapper; wrong feedback lever angle; unstable supply air.
- Zero drift: Condensate in air; minor O-ring leakage; slight nozzle clogging.
- Insufficient output pressure: Stuck pilot valve; clogged air filter.
- Large hysteresis: Pivot sticking and high friction; excessive packing friction of actuator.
コンタクタ,サーキットブレーカー,センサー,エンコーダ,PLC,コンバータ




















NH42-63-318x560.png)