ABB AF265-30-11-13 Contactor

주문번호: 1SFL547002R1311Material No.: 10157171 시리즈: AF-Series 3-Pole Contactor with Universal AC/DC Electronic Coil Model Code Decoding Model Segment Description AF AF‑series, wide‑range universal AC/DC electronic coil, built‑in surge suppression; no external RC network or varistor required 265 Rated operational current 265A under AC‑3 @400V; 기존 열 전류 (AC‑1): 400에이 30 3-폴, all main contacts Normally‑Open ...

  • 제품 세부정보

주문번호: 1SFL547002R1311Material No.: 10157171

시리즈: AF-Series 3-극 접촉기 with Universal AC/DC Electronic Coil

  1. Model Code Decoding
모델 세그먼트설명
AF‑series, wide‑range universal AC/DC electronic coil, built‑in surge suppression; no external RC network or varistor required
265Rated operational current 265A under AC‑3 @400V; 기존 열 전류 (AC‑1): 400에이
303-폴, all main contacts Normally‑Open (아니요); no main Normally‑Closed (NC) 콘택트 렌즈
11Built‑in auxiliary contacts: 1NO +1NC
‑13코일 코드: 100‑250 V AC/DC (50/60 헤르츠 + DC compatible)

✅Key Features: Single coil supports AC 100-250 V & DC 100-250 V; high tolerance to voltage fluctuation; low holding power consumption; silent operation.

  1. 핵심 전기 사양
Number of Main Poles3피 (3 main NO contacts)
Motor current AC‑3 (400 다섯)265 에이; Motor rating 132 kW
Resistive load AC‑1400 에이
정격절연전압 Ui1000 다섯(IEC) /600 다섯(UL)
정격 전류 내전압 Uimp8 kV
코일 제어 전압100‑250 V AC/DC 50/60 Hz‑DC
보조 접점1아니요+1NC (front‑mounted, non‑removable)
기계적 내구성5 million operating cycles
최대 작동 주파수300 작업/시간
Pick‑up voltage80 % of lower coil rated voltage; Drop‑out voltage 55 % of lower coil rated voltage

III. 환경 & 기계적 매개변수

작동 주변 온도 (without thermal relay)‑40 ℃ ~ +70 ℃; ‑25 ℃ ~ +55 ℃ with thermal overload relay
보관온도‑40 ℃ ~ +70 ℃
Altitude without derating≤3000 m; derating required above 3000 m
전체 치수 (폭×높이×깊이)140 mm × 225 mm × 180 mm
순중량3.9 kg
터미널 유형주회로: 부스바 / bolt‑type terminals; 제어 회로: 나사 터미널
장착 방법Vertical DIN‑rail or back‑plate screw mounting, sideways or inverted mounting strictly prohibited

인증: CCC, CE, UKCA, EAC, DNV marine certification; 기능적 안전성: SIL2, ISO13849-1 Cat.B.

  1. In-Depth Operating Principle

AF-series contactors adopt electronic rectifier-type coil, different from traditional AC contactors:

  1. Apply 100-250 V AC or DC to A1/A2; internal electronic circuit rectifies input to DC for driving electromagnetic coil.
  2. High instantaneous power for pull-in, then switch to low DC holding power; much lower coil heating than conventional AC coils.
  3. On-board built-in TVS surge absorber dissipates back-EMF upon coil de-energization. Do NOT connect external RC networks or varistors in parallel; external devices may cause malfunction or permanent damage.
  4. DC-magnetized armature eliminates 50 Hz AC hum noise.

터미널 정의

Main circuit line-side: 1L1, 3L2, 5L3; load-side: 2T1, 4T2, 6T3

코일: A1, A2 (non-polar for AC & DC)

보조 접점: 13-14 (아니요); 21-22 (NC)

  1. Standard Packing List & 옵션 액세서리

Standard Delivery

  1. AF265-30-11-13 Contactor Unit ×1
  2. 제품 매뉴얼, certificate of compliance

❗Not included: 열과부하 계전기, 기계적 인터록, auxiliary add-on blocks, terminal safety shield.

Separately-ordered Accessories

종범기능
TA275 DUMatching thermal overload relay (80‑275 A)
CAL19‑11Side‑mount auxiliary contact block (1아니요+1NC)
VM265기계적 인터록 (for reversing duty)
AF‑MTPMain circuit terminal protective cover
  1. 브랜드 간 호환성 & 교체 참조

⚠️Verify coil rating 100-250 VAC/DC and AC-3 265 A rating before replacement.

원래 모델Direct‑fit Equivalent비고
씨줄 AF265‑30‑11‑13A265‑30‑11 (Legacy EH265)Old EH‑series coils are AC‑only / DC‑only; coils cannot be interchanged directly
Competitor EquivalentsSiemens 3RT1066‑6AP36; Schneider LC1D245M7No native 100‑250 V wide‑range AC/DC coil for Siemens/Schneider; select correct coil variant

Ⅶ. 일반적인 애플리케이션 시나리오

  1. 팬 & pump large-size motor starting (공조, central air-conditioning, 수처리)
  2. Air compressor, extruder motor control (110-132 kW three-phase motors)
  3. 커패시터 뱅크 스위칭 (match AC-1 400 A rating)
  4. Forward/reversing and star-delta main circuits
  5. 선박 & export-oriented equipment: compatible with global control voltages (120 VAC /220 VAC universal)

Ⅷ. Selection Pitfalls & Hard Restrictions

  1. ❌Do NOT add external surge suppressors (RC networks, 배리스터, 다이오드). Built-in surge protection provided; external devices cause coil damage or failure to open.
  2. ❌Sideways or inverted mounting forbidden; only upright vertical installation permitted.
  3. ❌Derating is mandatory above 3000 m altitude; otherwise contact overheating and burnout may occur.
  4. ❌Not suitable for high-frequency switching (>300 작업/시간); use vacuum contactors for frequent-duty applications.
  5. ✅Wide control voltage tolerance: reliable pull-in within 80-250 V.
  6. 문제 해결
징후근본 원인치료
Contactor will not pull‑inNo voltage across A1‑A2; 느슨한 연결; internal electronic coil board failureMeasure voltage A1‑A2; retighten terminals; replace complete unit (AF coil cannot be replaced separately)
Chattering / intermittent pull‑inControl voltage below 80 % minimum limit; excessive power‑supply rippleEnsure input voltage ≥80 V; rule out insufficient PLC output drive capacity
Excessive main‑circuit terminal heatingInsufficient bolt torque; 초과 적재; 접촉 침식 / 타고 있는Retorque busbar bolts; check load current; replace contactor for severe contact ablation
Contacts remain closed after de‑energization (sticking)주요 접점 용접; residual induced voltage on control wiringInvestigate short‑circuit conditions on load side; eliminate induced residual voltage in control cables

중요한: The AF-series coil electronic board is integrated inside the unit; coil faults require complete contactor replacement; spare coil assemblies are not available.

ABB AF265-30-11-13 Operating Instructions (Compiled Manual)

Corresponding original manual document No.: 1SFC100008M0201, applicable frame size: AF190-205-265-305-370 series

주문번호: 1SFL547002R1311Coil rating: 100-250 V AC/DC

⚠️Safety Warning: Installation and commissioning must be performed by qualified electrical personnel. Disconnect all upstream power supply prior to any wiring or maintenance work. Do NOT apply high-voltage dielectric test across A1/A2 coil terminals; electronic coil board will suffer permanent breakdown damage.

Table of Contents

  1. 제품개요
  2. 모델 & 터미널 정의
  3. 설치사양
  4. 배선 & 조임 토크
  5. Coil Operating Instructions (AF Electronic Coil Key Notes)
  6. Commissioning Procedure
  7. Accessory Mounting
  8. 유지보수 일정 & Inspection Items
  9. 결함 문제 해결
  10. 금지된 작업
  11. Access to Original PDF Manual
  12. 제품개요

AF265-30-11-13 is a 3-pole contactor with integrated wide-range electronic coil and built-in surge suppression. External RC / varistor suppressors are prohibited.

AC-3-400 V: 265 에이, motor rating 132 kW

AC-1 resistive: 400 에이

내장형 보조 접점:1아니요(13-14)+1NC(21-22)

Coil rating:100-250 V AC/DC; pull-in ≥80 %Uc; drop-out ≤55 %Uc

기계적 내구성:5 million cycles; max operating frequency 300 작업/시간

작동 온도:-40 ℃~+70 ℃ (without thermal relay); no derating ≤3000 m altitude.

  1. 터미널 정의
Circuit터미널 번호.설명
Main circuit line‑side1L1, 3L2, 5L33‑phase power input
Main circuit load‑side2T1, 4T2, 6T3모터 / load connection
코일A1, A2Non‑polar for AC/DC; rated for 100‑250 V AC/DC
Built‑in auxiliary NO13‑14Normally‑Open
Built‑in auxiliary NC21‑22Normally‑Closed

CAL19-11 auxiliary add-on block can be fitted on the left side of unit.

  1. 설치사양
  2. 장착 방향: vertical upright installation only (main terminals vertical up-down). Sideways or inverted mounting is strictly forbidden.
  3. Two installation options:

Back-plate screw fixing: 4 pcs M8 bolts

DIN35 mm rail mounting (For large-frame AF265, screw mounting is preferred over rail-mount).

  1. Cabinet heat dissipation: Multiple units can be mounted side-by-side without gaps; no derating up to 70 ℃ ambient. Derating is mandatory for altitude >3000 m.
  2. Suggested minimum cabinet dimension: ≥900×750×300 mm, to ensure adequate top-bottom ventilation.
  3. Prevent metal chips and drilling dust from entering contactor enclosure during installation.
  4. 배선 & 조임 토크 (Most overheating originates from insufficient torque)
Terminal LocationBolt SizeRecommended Tightening Torque케이블 요구 사항
Main circuit L/T terminalsM1224 N·m구리 버스바 / ATK300 lugs; 75 ℃ rated copper conductors; direct aluminum conductor connection prohibited
Coil A1‑A2M41.2‑1.5 N·m0.75‑2.5 mm² copper wire
보조 접점M41.2 N·m0.75‑2.5 mm² copper wire

ATK300 crimped lugs are recommended for main circuit. Fit AF-MTP terminal safety shield over bare live conductors for touch-protection.

  1. Coil Operating Instructions (AF Electronic Coil Key Notes)
  2. A1/A2 coil terminals are non-polar; either AC or DC 100-250 V may be applied directly.
  3. Built-in on-board TVS surge suppression. External RC snubber, varistor or freewheeling diode are strictly forbidden. External surge devices will burn coil board or cause failure to open.
  4. 풀인: reliable closing ≥80 % ×100 V = 80 V.
  5. 탈락: reliable opening ≤55 %Uc.
  6. Low holding power consumption; silent operation, no hum.
  7. ❗Electronic coil board is integrated within main unit. Coil cannot be replaced separately; full-unit replacement required upon coil failure.
  8. Dielectric withstand test: Never perform hipot test across A1-A2 coil terminals; will destroy electronic circuit.
  9. 시운전 단계
  10. All power disconnected; verify full wiring and torque values; confirm arc-chamber cover is fully seated and intact.
  11. Confirm control supply voltage matches -13 coil rating (100-250 VAC/DC).
  12. Keep main 3-phase supply disconnected; energize only control circuit for no-load functional test:

Apply voltage to A1-A2: contactor shall pull-in promptly; de-energize for immediate release without chattering.

Verify auxiliary contact logic: 13-14 open/close, 21-22 close/open as expected.

  1. Proceed to energize main power only after successful no-load test, perform loaded trial-run.
  2. Run under full load for minimum 30 minutes; measure terminal temperature rise; acceptable housing temperature rise ≤60 K.
  3. Accessory Mounting
  4. CAL19-11 (side-mount auxiliary block): Slide into left-hand side slot of contactor until fully latched; adds 1NO+1NC contacts.
  5. VM265 mechanical interlock: for forward-reverse interlock application; two contactors required as pair.
  6. TA275-DU thermal overload relay: bottom-mount installation; relay operating temperature range -25~+55 ℃.
  7. AF-MTP main-circuit terminal safety shield, prevents accidental touch of live busbars.

All accessories are separately-ordered, not included as standard delivery.

  1. 정기 유지 관리 & 점검

Perform only with full power disconnected! 유지보수 간격: every 12 months for clean environment; every 6 months for dusty / high-vibration conditions.

  1. Retighten all main-circuit terminals to specified torque.
  2. Inspect arc-chamber cover for cracks, carbon deposits or metal powder accumulation; replace arc-chamber for severe burning.
  3. Inspect main contact erosion; replace complete unit for heavy wear or contact welding. No separate contact spare-parts available for AF265.
  4. Clean external dust. Do NOT blow compressed-air directly into enclosure, metal dust may damage internal coil electronics.
  5. Verify cabinet ambient temperature and unobstructed ventilation paths.
  6. Functional test of auxiliary contact switching.

메모: AF190-AF370 frame units have no serviceable separate contact assemblies; full-unit replacement required upon contact damage.

  1. Troubleshooting Table
징후원인치료
Contactor will not pull‑inNo voltage A1‑A2; 느슨한 연결; internal electronic coil failureMeasure A1‑A2 voltage; retighten terminals; replace full unit
Chattering / repeated bouncingControl voltage below 80 % minimum; insufficient PLC output drive; induced residual voltage in control wiringVerify supply voltage; upgrade PLC drive capacity; eliminate induced residual voltage
Will not open after de‑energization (sticking)Main‑contact welding; residual induced voltage on control circuit; incompletely‑removed external surge componentsLocate load‑side short‑circuit fault; eliminate induced voltage; fully remove external RC / varistor devices
Excessive heating at main terminalsInsufficient bolt torque; undersized cable / 부스바; overload conditionRetorque fasteners; recalculate conductor ampacity; measure actual load current
Coil burns immediately upon energizationHipot test applied to A1‑A2; external surge devices; supply voltage exceeds 250 V upper limitForbid hipot on coil terminals; remove external surge components; limit control voltage within rated 100‑250 V range
  1. 금지된 작업

❌Sideways or inverted mounting forbidden;

❌Hipot / megger test on A1/A2 coil terminals forbidden;

❌External RC snubber, varistor or freewheeling diode forbidden;

❌Do not exceed 300 operations/hour switching frequency;

❌Operation without derating for altitude >3000 m forbidden;

❌Do not attempt to disassemble internal coil electronic assembly; no serviceable spare-parts.

  1. Access to Original PDF Manual
  2. Visit ABB official product webpage, search order number 1SFL547002R1311 → Downloads section, download datasheet and Operating Instructions.
  3. Document reference numbers: Operating instruction: 1SFC100008M0201 (multilingual including Chinese); Service manual 1SFC101044M0201.