전체 제품 이름: SIRIUS Classic side-mounted 보조자 연락하다 (lateral auxiliary switch)
Suitable for legacy 3RV1 motor protection circuit breakers, frame sizes S00 / S0 / S2 / S3; 나사식 터미널, 1아니요+1NC (1 평상시 열려 있음 + 1 평상시 닫혀 있음)
수명주기: 더 이상 사용되지 않음 (Phase-out). It is an accessory for the older 3RV1 platform; the manufacturer promotes the upgraded 3RV2 platform.
주요 사양
연락처 구성: 1아니요 + 1NC
설치: Lateral side mounting (distinguished from front-mounted 3RV1901-1E)
배선: 나사 클램프 단자
접점등급: AC-12, 최대. 6에이 / 240뷔와; commonly used for 24VAC/DC, 220VAC signal feedback in control circuits
보호: IP20
애플리케이션: Passive feedback of circuit breaker ON/OFF status for PLC, indicator lamps and circuit interlocks
Compatible breaker bodies: 3RV10, 3RV11, 3RV13, 3RV14, 3RV16 and other legacy 3RV1 motor protectors; not directly compatible with the new 3RV2 series
모델 코드 설명
3RV1: Legacy SIRIUS motor protection circuit breaker series
3RV19: Accessory group for the 3RV1 series
01: Auxiliary switch
1에이: Lateral mounting, 1아니요+1NC, 나사 터미널
교체 옵션 (중요한)
- If migrating to 3RV2 circuit breakers: Front auxiliary contact 3RV2901-1E (1아니요+1NC, 나사); lateral type 3RV2901-2E (2아니요+2NC)
- If keeping the existing 3RV1 breaker body: 재고만 있음 / second-hand 3RV1901-1A is available; 3RV29xx accessories cannot be fitted onto legacy 3RV1 breakers
- Other accessories of the same series for reference:
3RV1901-1E: 전면 장착형 보조 접점, 1아니요+1NC
3RV1901-1J: Lateral, 2아니요
3RV1901-1C: Lateral, 2NC
Full Accessory List for 지멘스 3RV1 (Legacy SIRIUS Motor Protection CB)
Compatible bodies: 3RV10 / 3RV11 / 3RV13 / 3RV14 / 3RV16; frame S00, S0, S2, S3; entire series obsolete. Accessories fit only 3RV1 bodies and cannot be installed on 3RV2
Terminal distinction: -1xxx = screw terminals; -2xxx = spring-cage terminals
- 보조 연락처 (Status feedback, reflects CB ON/OFF position)
| 주문 번호. | 장착 위치 | 연락처 구성 | 비고 |
| 3RV1901-1A | Lateral | 1아니요+1NC | Model inquired, 나사식 터미널 |
| 3RV1901-1B | Lateral | 2아니요+2NC | 나사 |
| 3RV1901-1C | Lateral | 2NC | 나사 |
| 3RV1901-1J | Lateral | 2아니요 | 나사 |
| 3RV1901-2A | Lateral | 1아니요+1NC | 스프링 케이지 |
| 3RV1901-2B | Lateral | 2아니요+2NC | 스프링 케이지 |
| 3RV1901-2C | Lateral | 2NC | 스프링 케이지 |
| 3RV1901-1E | 앞쪽 (횡축) | 1아니요+1NC | 나사, most common front type |
| 3RV1901-1F | 앞쪽 | 2아니요 | 나사 |
| 3RV1901-1D | 앞쪽 | 2NC | 나사 |
| 3RV1901-1G | 앞쪽 | 1아니요+1NC | For low-current / electronic circuits, dust-resistant |
| 3RV1901-0H | Dust cover for front auxiliary contact | — | Protective cap, 팩 10 |
한정: Maximum one lateral auxiliary contact per 3RV1 breaker; 전면 장착 + lateral can be used together.
- Fault Signal Switch (Trip signal, distinguishes overload / 단락, not equal to standard auxiliary contact)
| 주문 번호. | 연락처 구성 | 비고 |
| 3RV1921-1M | 1아니요+1NC | Fault contact, actuates only on overload or short-circuit trip; no action during manual ON/OFF. For PLC fault alarm. |
- 저전압 해제 (UVT, trip on loss of supply)
| 주문 번호. | 코일 전압 |
| 3RV1902-1AB0 | AC24V 50Hz |
| 3RV1902-1AF0 | AC110V 50Hz |
| 3RV1902-1AP0 | AC230V 50Hz |
| 3RV1902-1DC0 | DC24V |
- 션트 릴리스 (SHT, 원격 트리핑)
| 주문 번호. | 코일 전압 |
| 3RV1903-1AB0 | AC24V |
| 3RV1903-1AF0 | AC110V |
| 3RV1903-1AP0 | AC230V |
| 3RV1903-1DC0 | DC24V |
Release rule: Undervoltage release and shunt release are mutually exclusive, cannot be fitted on the same breaker.
- Door-coupled Rotary Operating Mechanism (External cabinet operation, IP65, 자물쇠로 잠글 수 있는)
| 주문 번호. | Shaft Length | Compatible Frame |
| 3RV1926-0B | 130mm | S0 / S2 / S3 |
| 3RV1926-0K | 330mm | S0 / S2 / S3 |
기능: Cabinet door cannot be opened when CB is closed; lockable in OFF position to prevent accidental closing.
- Busbar Modules (Main circuit interconnection for side-by-side mounting)
S00 / S0 Frame
| 주문 번호. | 목적 |
| 3RV1915-1AB | Busbar for 2 breakers |
| 3RV1915-1BB | Busbar for 3 breakers |
| 3RV1915-1CB | Busbar for 4 breakers |
| 3RV1915-1DB | Busbar for 5 breakers |
| 3RV1915-3AB | 2 breakers (with space for accessories) |
| 3RV1915-3BB | 3 breakers (with space for accessories) |
| 3RV1915-3CB | 4 breakers (with space for accessories) |
S2 Frame
| 주문 번호. | 목적 |
| 3RV1935-1A | 2 breakers |
| 3RV1935-1B | 3 breakers |
| 3RV1935-1C | 4 breakers |
| 3RV1935-3A | 2 breakers (with space for accessories) |
- Contactor Link Module (Direct assembly for 3RV1+3RT1 starter group, no extra busbar)
| 주문 번호. | Compatible Assembly |
| 3RA1941-1B | 기계 & electrical link for 3RV1.41 + 3RT1.4 starter combination |
- 물개, 커버 & Other Mechanical Accessories
| 주문 번호. | 설명 |
| 3RV1920-1A | 씰 키트, prevents unauthorised adjustment of current setting dial |
| 3RV1910-1A | Extended terminal cover |
Cross Reference for Migration to 3RV2 Platform
| Legacy 3RV1 Part No. | 3RV2 Replacement |
| 3RV1901-1A (Lateral 1NO+1NC, 나사) | 3RV2901-1A |
| 3RV1901-1E (Front 1NO+1NC, 나사) | 3RV2901-1E |
| 3RV1921-1M (Fault signal switch) | 3RV2921-1M |
주요 선택 참고 사항
- 표준 보조 접점 (3RV1901): Only indicate handle position, cannot distinguish fault trip. Fault alarm requires 3RV1921-1M.
- 저전압 릴리스: The breaker must be closed before supply is restored; it trips automatically when supply fails. 션트 릴리스: Trips when energised.
- Busbars have two versions: standard and accessory-space type. If auxiliary contacts are fitted on the side, select suffix 3AB/3BB/3CB.
- Only stock items are available for purchase; manufacturer no longer accepts new production orders.
Operating Principle of 3RV1901-1A (Mechanically Synchronised Position Auxiliary Switch)
Core summary: Pure mechanical linkage, contact state follows the mechanical position of the 3RV1 handle synchronously. It only reflects ON / OFF status and cannot detect overload or short-circuit faults.
It is a passive snap-on auxiliary contact module clipped to the side of the 3RV1 motor protection circuit breaker. No electromagnetic components or trip detection mechanism inside.
- Mechanical Linkage Structure
The operating mechanism of the breaker handle and main contacts has a drive cam. Once 3RV1901-1A is fully engaged, its internal lever bears against this cam:
Handle movement → cam displacement → actuates internal rocker mechanism of auxiliary contact
Internal double-break silver bridge contact, 전환 접점 1개 (콜로라도:1아니요+1NC) with snap-action spring to ensure clean switching without chatter.
작동 상태
- Circuit Breaker ON
Handle switched to ON position, cam fully advanced: NO closed, NC open
→ ON signal to PLC, run indicator lamp energised
- Circuit Breaker OFF (Manual opening)
Handle switched to OFF position, cam retracts: NO open, NC closed
→ Stop status feedback
- Circuit Breaker Tripped by Overload / Short-Circuit
⚠️ 중요: 넘어진 후, the handle rests in the intermediate trip position. The handle mechanism also drives the cam, so 3RV1901-1A switches to OFF state (NO open, NC closed).
✅ Limitation: This contact alone cannot tell whether opening is manual or fault-induced.
👉 Separate fault alarm requires 3RV1921-1M (fault signal switch). It has an independent trip plunger and only switches state on overload/short-circuit trip; no action on manual ON/OFF.
- 전기적 특성
패시브 건식 접촉, no internal power supply; it is simply a mechanical switch to route low-current signals for PLC digital inputs, lamps and interlock circuits.
Utilisation category AC-12: 6에이 / 240뷔와. Designed exclusively for control signal circuits, not permitted for main power circuits.
Contact timing: Switches nearly synchronously with the main breaker contacts, no advance or delayed action (slightly different from contactor auxiliary contacts).
- Comparison with 3RV1921-1M (Common Pitfall in Selection)
| 부품 번호. | Actuation Source | Distinguish manual OFF vs fault trip | 애플리케이션 |
| 3RV1901-1A | Cam from handle mechanism | ❌ No, same contact state for both cases | Position feedback, run indication, general interlock |
| 3RV1921-1M | Independent plunger from thermal / magnetic trip unit | ✅ Yes, state changes only on fault trip | 결함 경보, fault logging, fault interlock shutdown |
- Installation Constraints & 추가 참고사항
Lateral mounting. Maximum one lateral auxiliary contact (3RV1901-1A) per 3RV1 breaker; one front auxiliary contact (3RV1901-1E) may be added together.
Poor snap fit causes the internal lever to lose engagement with the cam: handle moves but auxiliary contact does not toggle (most frequent site fault).
Insulated housing separates high-voltage main circuit from signal contacts, meeting low-voltage isolation requirements.
Common Site Misconception
❌ 오해: 3RV1901-1A is a fault contact and triggers alarm when tripped
✅ Correction: It is only a position contact. An open signal from this contact to PLC merely means the breaker is not closed. Combine it with 3RV1921-1M using AND/OR logic to discriminate fault trip.