상표: Basler Electric (미국)
설명: Microprocessor-based digital automatic voltage regulator for brushless synchronous generator excitation control
Core replacement model: Marathon DVR2000E/DVR2000EC, pin and footprint compatible, plug-and-play retrofit
✅ Four Control Modes
- AVR Automatic Voltage Regulation (기본):Maintains constant generator terminal voltage, accuracy ±0.25% (at rated power factor and constant frequency)
- FCR Field Current Regulation:Manual excitation current control for commissioning and AVR fault backup, adjustable from 0~3Adc
- PF Power Factor Regulation:For grid paralleling, constant power factor control
- VAR Reactive Power Regulation:For grid paralleling, constant reactive power output control
😀 주요 전기 사양
Excitation Output (PWM): 75 Vdc/3 Adc continuous; Forcing 150 Vdc /7.5 Adc for 10s (at 200Vac input)
Minimum Excitation Winding Resistance: ≥18 Ω (critical selection parameter)
PMG Power Supply: 180–240 Vac, 200–360 Hz, 350 버지니아
Voltage Sensing: Single-phase/three-phase RMS sensing, supports 120/240/480/600Vac
Current Sensing: Single-phase CT, max 5A AC, for reactive droop, PF/VAR control
의사소통: Rear RS232 DB9 port, configuration software BESTCOMS™ BE2000E (V2.02.01) for parameter setup, waveform recording and parameter backup
인터페이스: 4 디지털 입력, 1 common alarm relay output; front panel HMI + LED status indicators, local parameter modification
🛡️ Protection & Function List
Soft Voltage Ramp: 1–120s adjustable, suppress voltage surge during startup
OEL Over Excitation Limit + Over Excitation Shutdown
V/Hz (Volts/Hertz) Limiting, Under-frequency Load Shedding
Generator Overvoltage Shutdown, Loss-of-Sensing Protection
Regulator Internal Over-temperature Protection
Excitation Crowbar Protection Circuit
Paralleling Functions: Reactive Droop Compensation, Reactive Differential Compensation for multi-generator parallel operation
High THD tolerance design, suitable for non-linear harmonic loads
📎 Supporting Documents (Basler Official)
BE2000E Bulletin Rev11
Instruction Manual Rev G
BESTCOMS Configuration Software
Generator Paralleling Technical White Paper
🧩 일반적인 응용 프로그램
Industrial diesel/gas brushless synchronous generator sets, standby power supplies, continuous-duty power stations, multi-unit grid paralleling projects. Widely used for retrofit replacement of original Marathon generators.
Basler BE2000E Fault Tree (OEL/OV/SENSE LOSS/OVERTEMP)
General Pre-rules: After fault latch-up, power off for ≥60 seconds to reset. Use BESTCOMS software first to capture fault snapshots, waveform records and real-time readings (excitation current, 여기 전압, terminal sensing voltage). Distinguish between Limit Alarm (LIMIT) and Shutdown Trip (SHUTDOWN). For grid-tied generators, de-parallel and shed loads before troubleshooting to avoid secondary accidents.
Protection Action Logic: Alarm relay AL1/AL2 closes; after trip, regulator reduces excitation, Crowbar circuit activates and voltage regulation output ceases.
- OEL Over Excitation Alarm/Over Excitation Shutdown
증상: OEL LED flashes; BESTCOMS shows excitation current out of limit. Two statuses: OEL Limit (current limiting, 여행 없음), OEL Shutdown (timeout latch-up)
OEL Alarm ON
단계 1: Verify generator operating condition
✅ Generator overload, heavy inductive load, excessive reactive power → Shed load, verify rated excitation current of generator
✅ Grid paralleling: Excessive PF/VAR setpoint, unbalanced reactive power sharing, incorrect droop setting → Switch to local AVR mode, check PF/VAR setting, CT wiring and CT ratio
✅ Low frequency/V/Hz action raises excitation (speed drop) → Check prime mover speed and governor
단계 2: Parameter check via BESTCOMS
OEL current threshold set too low → Re-set according to rated excitation winding current
OEL delay time set too short → Typical 5~10s; short-duration forcing is permitted, avoid 0s instant trip
Improper soft-start setting, startup surge triggers OEL → Extend soft ramp time
단계 3: Hardware circuit measurement (power off and locked out, test excitation winding)
Partial short/turn-to-turn short in excitation winding → Winding resistance far below nameplate minimum value; shorted winding causes high excitation current and repeated OEL
Loose excitation terminals, damaged insulation, earth leakage → Insulation resistance test
Abnormally high PMG supply voltage → Measure PMG input 180–240Vac, troubleshoot PMG if out of range
단계 4: Regulator hardware check
Excitation PWM power transistor breakdown/shorted → Continuous high excitation current and OEL latch-up
Replace BE2000E and re-test; if OEL recurs after replacement → Fault in exciter assembly
메모: OEL is rotor protection. Repeated OEL events will burn excitation rotor
- OV Generator Overvoltage Alarm
증상: OV LED ON; fixed 0.75s trip delay; threshold default 105~120% rated voltage, 소프트웨어 구성 가능
OV Alarm ON
단계 1: Distinguish true overvoltage vs false sensing alarm
Measure generator terminal voltage with multimeter and compare with BESTCOMS reading
Measured voltage actually high: True overvoltage
Measured voltage normal, software reads high: Sensing circuit fault, refer to SENSE LOSS branch
단계 2: Troubleshoot true overvoltage
Overvoltage at no-load startup: High voltage setpoint, excessive PID gain, failed soft ramp
Voltage overshoot after sudden load rejection: Mismatched PID (P/I/D), excessive transient gain
Prime mover speed runaway (governor failure) → Rectify diesel/gas engine governor first
Grid-tied unit: Voltage spike when reactive power is removed during de-paralleling
단계 3: Hardware inspection
Failed excitation Crowbar circuit, unable to discharge excitation energy
BE2000E power output transistor shorted, excitation uncontrolled
Excessive PMG supply voltage, excitation drive overflow
다시 놓기: 다음 시간 동안 전원 끄기 1 minute after OV latch-up. Do NOT repeatedly start the unit with recurring OV, risk of downstream equipment breakdown
- SENSE LOSS Loss of Sensing
증상: SENSE LOSS LED flashes; 보호 논리: configurable delay (0–25s) before trip, regulator de-excites to prevent catastrophic overvoltage caused by uncontrolled excitation without valid sensing
SENSE LOSS Alarm ON
단계 1: 전원 끄기, inspect voltage sensing circuit (most frequent fault point)
Broken sensing wire, 느슨한 터미널, 끊어진 퓨즈, 트립된 회로 차단기
Wrong phase sequence, reversed single-phase sensing wiring (BE2000E supports single/three-phase sensing; hardware wiring must match software mode)
Failed PT voltage transformer, PT ratio mismatch with setting, PT secondary open circuit
Sensing cable earth fault, 단락, 절연 손상
단계 2: Verify configuration in BESTCOMS
Wrong sensing mode: three-phase hardware with single-phase software setting, 또는 그 반대
Rated voltage setting mismatched with PT secondary output (예를 들어. 480V generator set as 600V)
LOS delay set too short, normal voltage fluctuation triggers trip
단계 3: Noise and grounding issues
Poor regulator grounding, routed together with power cables, heavy harmonic interference causes intermittent sensing dropout
Extreme high THD from rectifier loads; although the unit is THD tolerant, severe distortion can still trigger loss of sensing
단계 4: Regulator hardware judgment
Normal voltage present at sensing terminals but no reading in software → Internal sensing board damage on BE2000E
SENSE LOSS persists after regulator replacement → Fault in generator PT/secondary circuit
Critical Warning: Do NOT bypass SENSE LOSS protection for startup, risk of runaway overvoltage and equipment damage
- OVERTEMP Regulator Over Temperature
증상: OVERTEMP LED flashes; internal temperature sensor triggers over-temperature trip latch-up, protects IGBT/PWM power stage
OVERTEMP Alarm ON
단계 1: Ambient and heat dissipation (가장 흔한 원인)
Enclosed cabinet, 통풍이 잘 안됨, 높은 주변 온도, 직사광선
Heatsink clogged with dust and grease, airflow blocked by cables
Nearby heat sources (VFD, 접촉기) heating the AVR
단계 2: Continuous high excitation under load
Long-term high reactive power, continuous OEL limiting, power devices run hot
Low excitation winding resistance, excitation current constantly near 3A rating
Frequent excitation forcing (150V/7.5A 10s forcing cycle)
단계 3: Power supply and wiring
Sustained high PMG supply voltage, increased power stage loss and heat
Loose excitation output terminals, contact resistance heat conducted to regulator
접지 불량, common-mode interference causes abnormal heating of internal components
단계 4: Regulator hardware check
Drifted/failed internal temperature sensor (OVERTEMP alarm immediately after cold power-up)
Aged power devices, high leakage current, heat even at no-load
행동: Shut down and cool for 30min before retest; alarm triggers immediately after loading when cooled → Regulator damaged, 바꾸다
Standard General Troubleshooting Workflow for Site
- Lockout-tagout and isolate power; power off ≥60s to clear latched faults
- 전원 켜기, connect BESTCOMS, retrieve fault logs, waveform records and live measurements (excitation current, sensing voltage, 내부 온도)
- Fault classification: Operating condition/load/governor/grid issue → Parameter setting issue → External circuit (PT, PMG, excitation winding, CT) → Confirm regulator hardware failure only at last
- 수리 후: Test no-load operation first, then apply load gradually; for grid-tied units, complete AVR regulation and droop test before paralleling
Quick Reference Cheat Sheet
OEL = Excitation current too high (rotor/excitation circuit, excess reactive load, low limit threshold)
OV = Terminal voltage too high (속도, PID tuning, shorted excitation, load rejection surge)
SENSE LOSS = Voltage sensing signal missing (PT, sensing wiring, 구성, EMI noise)
OVERTEMP = AVR overheating (냉각 불량, continuous high excitation, faulty sensor/power device)
Basler Electric Digital Excitation Regulator (Digital AVR/DECS) 전체 모델 목록
/분류: BE Series (retrofit models, mainly for Marathon replacement), DECS Series (standard digital excitation controllers, mainstream stock). 상태: Active/Obsolete, description and typical application
- BE Series (개조 & 교체 모델, BE2000E belongs here)
| 모델 | 상태 | 간략한 설명 | 비고 |
| BE2000E | 활동적인 | PMG-fed digital AVR for brushless synchronous generators | Direct drop-in replacement for Marathon DVR2000E / DVR2000EC; PWM output 75Vdc/3A, RS232, BESTCOMS, 4 control modes (AVR/FCR/PF/VAR) |
| BE300PM | 활동적인 | Potting compact digital AVR | Replaces Marathon PM300, PMG supply, built-in OEL & under-frequency compensation, for harsh environment generators |
- DECS Series (Basler Mainstream Digital Excitation Control for Industrial & Power Stations)
레거시 모델 (Most Obsolete, Used for Retrofit)
| 모델 | 상태 | 간략한 설명 | 비고 |
| DECS-15 | 더 이상 사용되지 않음 | Entry-level compact digital AVR | Early small brushless generator sets |
| DECS-100 | 더 이상 사용되지 않음 | Classic compact digital excitation controller | 하위 모델: A11 / A15 / B11 / B15; PMG or terminal sensing supply, widely used on diesel generators, BESTCOMS software |
| DECS-200 | 더 이상 사용되지 않음 | Medium-duty excitation controller | Multiple excitation power sources, drives external power modules |
| DECS-200N | 더 이상 사용되지 않음 | Negative forcing version of DECS-200 | For grids with severe disturbance, requires fast de-excitation |
| DECS-300 | 더 이상 사용되지 않음 | Medium power station excitation controller | Grid paralleling, hydro / small turbine generator retrofit |
| DECS-400 | 더 이상 사용되지 않음 | Large static excitation master controller | High-power generators, legacy excitation system upgrade projects |
Current Active Flagship Models (Official Website Primary Offering)
| 모델 | 상태 | 간략한 설명 | 비고 |
| DECS-150 | 활동적인 | Economical all-round digital excitation controller | Small/medium diesel & gas generators, paralleling, 통합 보호, BESTCOMSPlus, 비용 효율적 |
| DECS-250 | 활동적인 | High-performance universal digital excitation controller | 인기 모델; supports PSS Power System Stabilizer, 프로그래밍 가능한 논리, auto PID tuning, grid-tied power stations, standby power, integrated generator protection |
| DECS-250E | 활동적인 | DECS-250 extended version | Expanded I/O, redundant interfaces, for large generator packages |
| DECS-250N | 활동적인 | DECS-250 negative forcing version | Negative excitation forcing, fast voltage suppression under grid disturbance |
| DECS-450 | 활동적인 | High-power premium excitation controller | 중간 & large steam / hydro generators, drives external power cabinets, redundant architecture, grid compliance, large power station retrofit |
| DECS-2100 | 활동적인 | Master excitation controller for large / megawatt-scale generators | Drop-in replacement for GE EX2000 and similar large excitation systems, core unit for excitation cabinet packages |
- Auxiliary Supporting Modules (Excitation Accessories, Not Standalone AVR)
VRM-2020: Remote Voltage Regulator Module (works with DGC-2020 genset controller)
ICRM-7/ICRM-15: PWM AVR excitation inrush current limiting protection module
MVC: Manual Voltage Control Unit (backup manual excitation if AVR fails)
- Selection Quick Guide for Replacement
- Direct replacement for Marathon DVR2000E → BE2000E (핀 & 장착 호환, priority choice)
- Standard diesel generator with budget constraint → DECS-150
- General paralleling application requiring PSS and rich protection → DECS-250/DECS-250N
- Hydro/steam high-power generators, excitation cabinet packages → DECS-450/DECS-2100
- Retrofit of old DECS-100/200/300/400 → Upgrade to DECS-250 or DECS-450 preferentially
- 소프트웨어 호환성
BE2000E: BESTCOMS (legacy version, V2.02.01)
DECS150/250/450: BESTCOMSPlus (new generation software)