Chint NA1-3200X-3200M/3P 기중차단기 - 접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지

위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

 Chint NA1-3200X-3200M/3P 기중차단기 - 접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지

회로 차단기/

Chint NA1-3200X-3200M/3P 기중차단기

  Code Segment Description NA1 Series code for Chint air circuit breakers (ACB) 3200 프레임 정격 전류: 3200에이 (maximum current specification of the breaker) X Breaking capacity grade: Class X (100그만큼); distinguished from standard type (80그만큼) and Class H (120그만큼) 3200 Rated operating current: 3200에이 (actual set working current) M Trip unit type: Intelligent trip ...

  • 제품 세부정보

 

코드 세그먼트설명
NA1Series code for Chint air circuit breakers (ACB)
3200프레임 정격 전류: 3200에이 (maximum current specification of the breaker)
엑스차단용량 등급: Class X (100그만큼); distinguished from standard type (80그만큼) and Class H (120그만큼)
3200Rated operating current: 3200에이 (actual set working current)
트립 유닛 유형: 지능형 트립 유닛 (미세학); distinguished from standard Type L and high-breaking Type H
3피극수: 3-폴 (3-phase circuit protection, without neutral pole)
  1. 핵심 기술 사양
매개변수 카테고리Technical Data
제품 유형Intelligent low-voltage air circuit breaker (ACB)
정격 작동 전압AC 400V/690V, 50헤르츠
프레임 전류 (아이유)3200에이
정격 작동 전류 (~ 안에)3200에이
Rated Ultimate Short-circuit Breaking Capacity (중환자실)100그만큼 (Class X @ 400V)
Rated Service Short-circuit Breaking Capacity (IC)100그만큼 (equal to Icu)
정격 단시간 전류 (Icw)80그만큼 (1에스)
트립 유닛Type M intelligent trip unit, 장시간 지연 과부하 기능, 단시간 지연 단락 및 순간 단락 보호
장착 유형Draw-out or fixed type (X series is generally draw-out)
Operation ModeManual or motorized (motor operating mechanism optional)
제어 회로 전압AC 220V/380V or DC 220V (선택 과목)
보조 연락처기준: 5아니요 + 5NC (확장 가능)
유입 방지IP30 (GB/T와 호환 4942.2)
적용 가능한 표준GB/T 14048.2, IEC/EN 60947-2
치수 (H×W×D)Draw-out type: 대략. 600mm×400mm×1000mm (refer to official manual for exact data)
무게대략. 80~100kg (varies by mounting type and accessory configuration)
  1. 핵심 기능

3.1 Intelligent Protection System

Three-stage protection: Long-time delay for overload (inverse time characteristic), short-time delay for short circuit (selectable fixed/inverse time), and instantaneous short-circuit protection, precisely matching power distribution system requirements.

Earth fault protection: Residual current protection optional, sensitivity adjustable from 0.03A to 1A.

Adjustable protection parameters: Flexible parameter configuration via intelligent controller to adapt to diverse load characteristics.

Fault recording: Automatically stores the latest 10 fault records including fault type, current value and time for rapid troubleshooting.

3.2 높은 신뢰성 설계

High Class X breaking capacity: 100kA short-circuit breaking capacity to ensure reliable disconnection under severe short-circuit faults and guarantee equipment safety.

Optimized arc extinguishing system: Adopts multi-break and longitudinal seam arc extinguishing technology for rapid arc extinction and fast recovery after breaking.

긴 서비스 수명: Mechanical durability up to 10,000 운영; electrical durability up to 5,000 운영.

Vibration and shock resistance: Compliant with GB/T 14048.2 to adapt to harsh industrial environments.

3.3 Flexible Expandability

Rich optional accessories: Shunt trip, undervoltage trip, closing solenoid, motor charging mechanism, 보조 접점, 알람 접점, key lock, 등.

Extended communication: Optional Modbus-RTU, Profinet, EtherNet/IP modules for remote monitoring and intelligent power distribution management.

Interlock functions: Cable interlock and connecting rod interlock available to meet electrical and mechanical interlock requirements.

  1. Compatible Equipment & 응용 시나리오

Compatible Equipment

Distribution transformer: Main protection switch for low-voltage side of transformers

Generator set: Protection switch for generator outgoing circuits

Busbar system: Bus section protection and tie control

Large motor: Incoming switch for Motor Control Center (MCC)

UPS system: Protection switch for UPS input and output circuits

응용 시나리오

  1. 산업용 배전: Main power distribution systems for factories, workshops and production lines.
  2. Commercial building power distribution: Main and floor power distribution for shopping malls, hotels and high-rise buildings.
  3. 데이터 센터: Mission-critical areas requiring high power supply reliability such as server rooms and cloud computing centers.
  4. New energy industry: Low-voltage power distribution systems for photovoltaic power stations and wind farms.
  5. 하부 구조: Power distribution systems for transportation hubs including airports, subways and railways.
  6. Model Comparison
모델차단 용량정격전류트립 유닛애플리케이션
NA1-3200-3200M/3P80그만큼 (기준)3200에이Type M IntelligentGeneral industrial distribution with low short-circuit current
NA1-3200X-3200M/3P100그만큼 (Class X)3200에이Type M IntelligentIndustrial sites with high short-circuit current and high breaking capacity requirements
NA1-3200H-3200M/3P120그만큼 (Class H)3200에이Type M IntelligentLarge industrial enterprises and grid connection points with extreme short-circuit current
NA1-3200X-2500M/3P100그만큼 (Class X)2500에이Type M Intelligent3200A frame with actual load current of 2500A
NA1-3200X-3200L/3P100그만큼 (Class X)3200에이Type L StandardGeneral scenarios with basic protection demands
  1. Cross-Brand Equivalent Model Comparison
친트지멘스슈나이더씨줄미쓰비시
NA1-3200X-3200M/3P3WL2N32 ETU25B 3PMT32H1 3P 3200A Micrologic 5.0EMAX2 E3S3200 R100 3PAE3200-SW 3P F 3200A
차단 용량100그만큼100그만큼100그만큼85그만큼
트립 유닛Type M IntelligentETU25B Intelligent미세학 5.0 지능적인Standard Intelligent Trip
장착 유형인출형 / 결정된인출형 / 결정된인출형 / 결정된인출형 / 결정된
의사소통Optional Modbus / ProfinetOptional Profinet / 이더넷/IPOptional Modbus / ProfinetOptional CC-Link / Profinet
  1. 선택 & Application Guidelines
  2. 차단용량 매칭: Select proper grade according to system short-circuit current calculation (Standard 80kA, Class X 100kA, Class H 120kA).
  3. Rated current selection: Determine operating current based on total load current and future expansion; optional ratings under 3200A frame: 2000에이, 2500에이, 3200에이.
  4. Trip unit selection: Type M intelligent trip for most industrial and commercial applications; Type L standard trip for simple protection requirements.
  5. 장착 유형: Draw-out type for easy maintenance and replacement (중요한 회로); fixed type for cost-effective general circuits.
  6. 작동 모드: Manual for small-capacity and infrequent operation; motorized for large-capacity, frequent operation and remote control.
  7. Accessory configuration: Select shunt trip, undervoltage trip, auxiliary contacts and communication modules as required by control and protection logic.
  8. 유지: Regularly inspect mechanical mechanisms, arc extinguishing chambers and contact wear to ensure long-term stable operation.

Chint NA1-3200X-3200M/3P Complete Accessory List & Selection Codes

  1. Core Control Accessories (Essential for Control Circuit)

1.1 션트 트립 (에프)

Used for remote breaker tripping, applicable to emergency shutdown and automatic control systems.

유형모델정격전압전력 소비애플리케이션Selection Code
Continuous (Default)NA1-F-3200XAC220V/230V460버지니아(AC220V)일반 산업 제어, infrequent operationF-AC220
AC380V/400V400버지니아(AC380V)F-AC380
DC110V70여(DC110V)F-DC110
DC220V140여(DC220V)F-DC220
Pulse Type (추천)NA1-FP-3200XAC220V/230V880버지니아(AC220V)Wind & solar power, ATS system, frequent operationFP-AC220
AC380V/400V1800버지니아(AC380V)FP-AC380
DC110V850여(DC110V)FP-DC110
DC220V880여(DC220V)FP-DC220

Selection Note: Pulse type: single power-on duration ≤ 2s, 최대 5 times/min; Continuous type: single power-on duration ≤ 2s to avoid component burnout.

1.2 저전압 트립 (큐)

Automatically trips the breaker under low grid voltage to prevent equipment overload damage.

유형모델정격전압Operating CharacteristicDelay TimeSelection Code
Instant Suction (Default)NA1-Q-3200XAC230VTrip at 70% 우리를, reliable trip at 35% 우리를InstantQ-AC230
AC400VQ-AC400
Delayed SuctionNA1-QD-3200XAC230V위와 동일1s/3s/5s (결정된)QD-AC230-1s
AC400VQD-AC400-3s
Self-suction DelayNA1-QZ-3200XAC230V위와 동일0.3s~7.5s (조절할 수 있는)QZ-AC230
AC400VQZ-AC400
Under-voltage Delay (UVTZ-1)NA1-UVTZ-1AC230VAutomatic reclosure after voltage recovery1s/3s/5sUVTZ-1-AC230
AC400V

Selection Note: 3200A frame adopts instant suction type as standard; self-suction type features wider delay range for voltage-fluctuation-sensitive equipment.

1.3 Closing Solenoid (엑스) / Closing Coil

For remote closing, matched with motor charging mechanism.

유형모델정격전압전력 소비애플리케이션Selection Code
Pulse Type (Mandatory for ATS)NA1-X-3200XAC220V/230VSame as shunt tripAutomatic control system, frequent closingX-AC220
AC380V/400VX-AC380
DC110VX-DC110
DC220VX-DC220

1.4 Motor Charging Mechanism (중)

Stores energy for breaker closing and provides closing power.

모델정격전압Charging TimeSelection Code
NA1-M-3200XAC220V/230V0.37kW≤15sM-AC220
AC380V/400VM-AC380
DC110VM-DC110
DC220VM-DC220
  1. 지능형 제어 & Communication Accessories

2.1 Intelligent Controller Upgrade

Type M is standard; upgraded versions with enhanced functions are optional.

모델특징애플리케이션Selection Code
Type 3MAdded voltage measurement and harmonic analysisPower quality monitoring required3중
Type HAdvanced protection with extended parameter settingsComplex power distribution systems & precise protection시간
Type 3HHighest configuration, full 3M+H functions + 이벤트 로깅Critical circuits & fault analysis3시간

2.2 통신 모듈 (Remote Monitoring)

모듈 유형모델Protocol기능Matching ComponentSelection Code
모드버스-RTUNA1-COM-MOD모드버스-RTUData acquisition & 원격 제어Not requiredCOM-MOD
Profibus-DPNA1-COM-DPProfibus-DPIndustrial fieldbus communicationST-DP protocol moduleCOM-DP+ST-DP
ProfinetNA1-COM-PNProfinetEthernet communicationPSU-1 power moduleCOM-PN+PSU-1
이더넷/IPNA1-COM-ENIP이더넷/IPEtherNet/IP communicationPSU-1 power moduleCOM-ENIP+PSU-1

2.3 Auxiliary Functional Modules

이름모델기능애플리케이션Selection Code
Power Supply UnitPSU-1Stable power supply for communication modulesMandatory for all Ethernet modulesPSU-1
Relay ModuleRU-1Signal amplification & contact expansion (AC250V/10A, DC28V/10A)High-power load controlRU-1
Under-voltage Delay ControllerUVTZ-1Delayed trip during temporary low voltageVoltage-sensitive equipmentUVTZ-1
  1. Auxiliary Contact System (상태 표시 & 제어)

NA1-3200X standard configuration: 4 sets of transfer contacts (4NO+4NC), 확장 가능.

유형모델연락처 구성평가애플리케이션Selection Code
3 sets TransferNA1-AX-3Z3아니요+3NCAC230V/5ABasic controlAX-3Z
4 sets Transfer (Default)NA1-AX-4Z4NO+4NCAC230V/5A표준 구성AX-4Z
5 sets TransferNA1-AX-5Z5NO+5NCAC230V/5AExtended controlAX-5Z
3아니요+3NCNA1-AX-333아니요+3NCAC230V/5ACustom control logicAX-33
4NO+4NCNA1-AX-444NO+4NCAC230V/5A표준 구성AX-44
5NO+5NCNA1-AX-555NO+5NCAC230V/5AComplex controlAX-55
6NO+6NCNA1-AX-666NO+6NCAC230V/5AOnly for Type M controller, cannot match suction undervoltage delayAX-66
  1. Mechanical Interlock & Safety Accessories

4.1 Mechanical Interlock (Misoperation Prevention)

유형모델기능애플리케이션Selection Code
Connecting Rod InterlockNA1-LK-LGMutual interlock for two breakers to prevent simultaneous closingBus tie & ATS systemLK-LG
Cable InterlockNA1-LK-GLRemote mechanical interlock, standard cable length: 2중ATS system with large cabinet spacingLK-GL
Key LockNA1-KEYMultiple configurations: 1-lock-1-key, 2-lock-1-keyUnauthorized operation preventionKEY-1-1
KEY-2-1
Button LockNA1-BLLock closing/tripping buttonsAccidental touch preventionBL

4.2 Door Interlock

유형모델기능애플리케이션Selection Code
Position Door InterlockNA1-DL-WZCabinet door locked at test/connected positionDraw-out breaker, electric shock preventionDL-WZ
Status Door InterlockNA1-DL-ZTCabinet door locked when breaker closedLive operation prevention for all typesDL-ZT

4.3 Other Safety Accessories

이름모델기능애플리케이션Selection Code
Transparent Protective CoverNA1-TPIP54 protection for operating mechanismDust environments & safety enhancementTP
CounterNA1-CTMechanical operation countingFrequent circuits & predictive maintenanceCT
Position IndicatorNA1-PSDraw-out position indication (Disconnect/Test/Connected)Draw-out breaker status monitoringPS
Phase BarrierNA1-PSBIsolate three-phase busbars to prevent phase short circuitInsulation improvementPSB
  1. 설치 & Connection Accessories

5.1 Main Circuit Accessories

이름모델평가애플리케이션Selection Code
Horizontal BusbarNA1-BUS-H3200에이Standard horizontal wiringBUS-H
Vertical L-type BusbarNA1-BUS-V3200에이수직 설치 & space savingBUS-V
Rotatable BusbarNA1-BUS-R3200에이Flexible wiring for draw-out breakersBUS-R

5.2 Secondary Circuit Accessories

이름모델기능애플리케이션Selection Code
Secondary ConnectorNA1-SPSecondary circuit connection for draw-out breakersQuick plug & unplugSP
Control FuseNA1-FU6에이, control circuit protectionMandatory for all control loopsFU-6A
  1. Complete Configuration Example

예:

NA1-3200X-3200M/3P, motorized draw-out type, AC220V, with shunt trip / undervoltage trip / closing solenoid + 5 sets transfer contacts + Profinet communication + connecting rod interlock

Complete Order Model:

NA1-3200X-3200M/3P Motorized Draw-out AC220 F-AC220 Q-AC230 X-AC220 AX-5Z COM-PN+PSU-1 LK-LG

  1. Accessory Application Notes
  2. Unified control voltage: Use identical voltage for shunt trip, undervoltage trip, closing solenoid and motor charging mechanism to simplify wiring.
  3. Communication matching: PSU-1 power module required for Profinet/EtherNet/IP; ST-DP module required for Profibus-DP.
  4. Auxiliary contact capacity: 5A@AC230V; use RU-1 relay module for high-power load control.
  5. Undervoltage trip requirement: Undervoltage trip coil must be powered on before breaker closing.
  6. Shunt trip specification: Single energization time ≤ 2s, frequency ≤ 5 times/min to avoid overheating damage.

 

이전: