| 코드 세그먼트 | 설명 |
| NA1 | Series code for Chint air circuit breakers (ACB) |
| 3200 | 프레임 정격 전류: 3200에이 (maximum current specification of the breaker) |
| 엑스 | 차단용량 등급: Class X (100그만큼); distinguished from standard type (80그만큼) and Class H (120그만큼) |
| 3200 | Rated operating current: 3200에이 (actual set working current) |
| 중 | 트립 유닛 유형: 지능형 트립 유닛 (미세학); distinguished from standard Type L and high-breaking Type H |
| 3피 | 극수: 3-폴 (3-phase circuit protection, without neutral pole) |
- 핵심 기술 사양
| 매개변수 카테고리 | Technical Data |
| 제품 유형 | Intelligent low-voltage air circuit breaker (ACB) |
| 정격 작동 전압 | AC 400V/690V, 50헤르츠 |
| 프레임 전류 (아이유) | 3200에이 |
| 정격 작동 전류 (~ 안에) | 3200에이 |
| Rated Ultimate Short-circuit Breaking Capacity (중환자실) | 100그만큼 (Class X @ 400V) |
| Rated Service Short-circuit Breaking Capacity (IC) | 100그만큼 (equal to Icu) |
| 정격 단시간 전류 (Icw) | 80그만큼 (1에스) |
| 트립 유닛 | Type M intelligent trip unit, 장시간 지연 과부하 기능, 단시간 지연 단락 및 순간 단락 보호 |
| 장착 유형 | Draw-out or fixed type (X series is generally draw-out) |
| Operation Mode | Manual or motorized (motor operating mechanism optional) |
| 제어 회로 전압 | AC 220V/380V or DC 220V (선택 과목) |
| 보조 연락처 | 기준: 5아니요 + 5NC (확장 가능) |
| 유입 방지 | IP30 (GB/T와 호환 4942.2) |
| 적용 가능한 표준 | GB/T 14048.2, IEC/EN 60947-2 |
| 치수 (H×W×D) | Draw-out type: 대략. 600mm×400mm×1000mm (refer to official manual for exact data) |
| 무게 | 대략. 80~100kg (varies by mounting type and accessory configuration) |
- 핵심 기능
3.1 Intelligent Protection System
Three-stage protection: Long-time delay for overload (inverse time characteristic), short-time delay for short circuit (selectable fixed/inverse time), and instantaneous short-circuit protection, precisely matching power distribution system requirements.
Earth fault protection: Residual current protection optional, sensitivity adjustable from 0.03A to 1A.
Adjustable protection parameters: Flexible parameter configuration via intelligent controller to adapt to diverse load characteristics.
Fault recording: Automatically stores the latest 10 fault records including fault type, current value and time for rapid troubleshooting.
3.2 높은 신뢰성 설계
High Class X breaking capacity: 100kA short-circuit breaking capacity to ensure reliable disconnection under severe short-circuit faults and guarantee equipment safety.
Optimized arc extinguishing system: Adopts multi-break and longitudinal seam arc extinguishing technology for rapid arc extinction and fast recovery after breaking.
긴 서비스 수명: Mechanical durability up to 10,000 운영; electrical durability up to 5,000 운영.
Vibration and shock resistance: Compliant with GB/T 14048.2 to adapt to harsh industrial environments.
3.3 Flexible Expandability
Rich optional accessories: Shunt trip, undervoltage trip, closing solenoid, motor charging mechanism, 보조 접점, 알람 접점, key lock, 등.
Extended communication: Optional Modbus-RTU, Profinet, EtherNet/IP modules for remote monitoring and intelligent power distribution management.
Interlock functions: Cable interlock and connecting rod interlock available to meet electrical and mechanical interlock requirements.
- Compatible Equipment & 응용 시나리오
Compatible Equipment
Distribution transformer: Main protection switch for low-voltage side of transformers
Generator set: Protection switch for generator outgoing circuits
Busbar system: Bus section protection and tie control
Large motor: Incoming switch for Motor Control Center (MCC)
UPS system: Protection switch for UPS input and output circuits
응용 시나리오
- 산업용 배전: Main power distribution systems for factories, workshops and production lines.
- Commercial building power distribution: Main and floor power distribution for shopping malls, hotels and high-rise buildings.
- 데이터 센터: Mission-critical areas requiring high power supply reliability such as server rooms and cloud computing centers.
- New energy industry: Low-voltage power distribution systems for photovoltaic power stations and wind farms.
- 하부 구조: Power distribution systems for transportation hubs including airports, subways and railways.
- Model Comparison
| 모델 | 차단 용량 | 정격전류 | 트립 유닛 | 애플리케이션 |
| NA1-3200-3200M/3P | 80그만큼 (기준) | 3200에이 | Type M Intelligent | General industrial distribution with low short-circuit current |
| NA1-3200X-3200M/3P | 100그만큼 (Class X) | 3200에이 | Type M Intelligent | Industrial sites with high short-circuit current and high breaking capacity requirements |
| NA1-3200H-3200M/3P | 120그만큼 (Class H) | 3200에이 | Type M Intelligent | Large industrial enterprises and grid connection points with extreme short-circuit current |
| NA1-3200X-2500M/3P | 100그만큼 (Class X) | 2500에이 | Type M Intelligent | 3200A frame with actual load current of 2500A |
| NA1-3200X-3200L/3P | 100그만큼 (Class X) | 3200에이 | Type L Standard | General scenarios with basic protection demands |
- Cross-Brand Equivalent Model Comparison
| 친트 | 지멘스 | 슈나이더 | 씨줄 | 미쓰비시 |
| NA1-3200X-3200M/3P | 3WL2N32 ETU25B 3P | MT32H1 3P 3200A Micrologic 5.0 | EMAX2 E3S3200 R100 3P | AE3200-SW 3P F 3200A |
| 차단 용량 | 100그만큼 | 100그만큼 | 100그만큼 | 85그만큼 |
| 트립 유닛 | Type M Intelligent | ETU25B Intelligent | 미세학 5.0 지능적인 | Standard Intelligent Trip |
| 장착 유형 | 인출형 / 결정된 | 인출형 / 결정된 | 인출형 / 결정된 | 인출형 / 결정된 |
| 의사소통 | Optional Modbus / Profinet | Optional Profinet / 이더넷/IP | Optional Modbus / Profinet | Optional CC-Link / Profinet |
- 선택 & Application Guidelines
- 차단용량 매칭: Select proper grade according to system short-circuit current calculation (Standard 80kA, Class X 100kA, Class H 120kA).
- Rated current selection: Determine operating current based on total load current and future expansion; optional ratings under 3200A frame: 2000에이, 2500에이, 3200에이.
- Trip unit selection: Type M intelligent trip for most industrial and commercial applications; Type L standard trip for simple protection requirements.
- 장착 유형: Draw-out type for easy maintenance and replacement (중요한 회로); fixed type for cost-effective general circuits.
- 작동 모드: Manual for small-capacity and infrequent operation; motorized for large-capacity, frequent operation and remote control.
- Accessory configuration: Select shunt trip, undervoltage trip, auxiliary contacts and communication modules as required by control and protection logic.
- 유지: Regularly inspect mechanical mechanisms, arc extinguishing chambers and contact wear to ensure long-term stable operation.
Chint NA1-3200X-3200M/3P Complete Accessory List & Selection Codes
- Core Control Accessories (Essential for Control Circuit)
1.1 션트 트립 (에프)
Used for remote breaker tripping, applicable to emergency shutdown and automatic control systems.
| 유형 | 모델 | 정격전압 | 전력 소비 | 애플리케이션 | Selection Code |
| Continuous (Default) | NA1-F-3200X | AC220V/230V | 460버지니아(AC220V) | 일반 산업 제어, infrequent operation | F-AC220 |
| AC380V/400V | 400버지니아(AC380V) | F-AC380 | |||
| DC110V | 70여(DC110V) | F-DC110 | |||
| DC220V | 140여(DC220V) | F-DC220 | |||
| Pulse Type (추천) | NA1-FP-3200X | AC220V/230V | 880버지니아(AC220V) | Wind & solar power, ATS system, frequent operation | FP-AC220 |
| AC380V/400V | 1800버지니아(AC380V) | FP-AC380 | |||
| DC110V | 850여(DC110V) | FP-DC110 | |||
| DC220V | 880여(DC220V) | FP-DC220 |
Selection Note: Pulse type: single power-on duration ≤ 2s, 최대 5 times/min; Continuous type: single power-on duration ≤ 2s to avoid component burnout.
1.2 저전압 트립 (큐)
Automatically trips the breaker under low grid voltage to prevent equipment overload damage.
| 유형 | 모델 | 정격전압 | Operating Characteristic | Delay Time | Selection Code |
| Instant Suction (Default) | NA1-Q-3200X | AC230V | Trip at 70% 우리를, reliable trip at 35% 우리를 | Instant | Q-AC230 |
| AC400V | Q-AC400 | ||||
| Delayed Suction | NA1-QD-3200X | AC230V | 위와 동일 | 1s/3s/5s (결정된) | QD-AC230-1s |
| AC400V | QD-AC400-3s | ||||
| Self-suction Delay | NA1-QZ-3200X | AC230V | 위와 동일 | 0.3s~7.5s (조절할 수 있는) | QZ-AC230 |
| AC400V | QZ-AC400 | ||||
| Under-voltage Delay (UVTZ-1) | NA1-UVTZ-1 | AC230V | Automatic reclosure after voltage recovery | 1s/3s/5s | UVTZ-1-AC230 |
| AC400V |
Selection Note: 3200A frame adopts instant suction type as standard; self-suction type features wider delay range for voltage-fluctuation-sensitive equipment.
1.3 Closing Solenoid (엑스) / Closing Coil
For remote closing, matched with motor charging mechanism.
| 유형 | 모델 | 정격전압 | 전력 소비 | 애플리케이션 | Selection Code |
| Pulse Type (Mandatory for ATS) | NA1-X-3200X | AC220V/230V | Same as shunt trip | Automatic control system, frequent closing | X-AC220 |
| AC380V/400V | X-AC380 | ||||
| DC110V | X-DC110 | ||||
| DC220V | X-DC220 |
1.4 Motor Charging Mechanism (중)
Stores energy for breaker closing and provides closing power.
| 모델 | 정격전압 | 힘 | Charging Time | Selection Code |
| NA1-M-3200X | AC220V/230V | 0.37kW | ≤15s | M-AC220 |
| AC380V/400V | M-AC380 | |||
| DC110V | M-DC110 | |||
| DC220V | M-DC220 |
- 지능형 제어 & Communication Accessories
2.1 Intelligent Controller Upgrade
Type M is standard; upgraded versions with enhanced functions are optional.
| 모델 | 특징 | 애플리케이션 | Selection Code |
| Type 3M | Added voltage measurement and harmonic analysis | Power quality monitoring required | 3중 |
| Type H | Advanced protection with extended parameter settings | Complex power distribution systems & precise protection | 시간 |
| Type 3H | Highest configuration, full 3M+H functions + 이벤트 로깅 | Critical circuits & fault analysis | 3시간 |
2.2 통신 모듈 (Remote Monitoring)
| 모듈 유형 | 모델 | Protocol | 기능 | Matching Component | Selection Code |
| 모드버스-RTU | NA1-COM-MOD | 모드버스-RTU | Data acquisition & 원격 제어 | Not required | COM-MOD |
| Profibus-DP | NA1-COM-DP | Profibus-DP | Industrial fieldbus communication | ST-DP protocol module | COM-DP+ST-DP |
| Profinet | NA1-COM-PN | Profinet | Ethernet communication | PSU-1 power module | COM-PN+PSU-1 |
| 이더넷/IP | NA1-COM-ENIP | 이더넷/IP | EtherNet/IP communication | PSU-1 power module | COM-ENIP+PSU-1 |
2.3 Auxiliary Functional Modules
| 이름 | 모델 | 기능 | 애플리케이션 | Selection Code |
| Power Supply Unit | PSU-1 | Stable power supply for communication modules | Mandatory for all Ethernet modules | PSU-1 |
| Relay Module | RU-1 | Signal amplification & contact expansion (AC250V/10A, DC28V/10A) | High-power load control | RU-1 |
| Under-voltage Delay Controller | UVTZ-1 | Delayed trip during temporary low voltage | Voltage-sensitive equipment | UVTZ-1 |
- Auxiliary Contact System (상태 표시 & 제어)
NA1-3200X standard configuration: 4 sets of transfer contacts (4NO+4NC), 확장 가능.
| 유형 | 모델 | 연락처 구성 | 평가 | 애플리케이션 | Selection Code |
| 3 sets Transfer | NA1-AX-3Z | 3아니요+3NC | AC230V/5A | Basic control | AX-3Z |
| 4 sets Transfer (Default) | NA1-AX-4Z | 4NO+4NC | AC230V/5A | 표준 구성 | AX-4Z |
| 5 sets Transfer | NA1-AX-5Z | 5NO+5NC | AC230V/5A | Extended control | AX-5Z |
| 3아니요+3NC | NA1-AX-33 | 3아니요+3NC | AC230V/5A | Custom control logic | AX-33 |
| 4NO+4NC | NA1-AX-44 | 4NO+4NC | AC230V/5A | 표준 구성 | AX-44 |
| 5NO+5NC | NA1-AX-55 | 5NO+5NC | AC230V/5A | Complex control | AX-55 |
| 6NO+6NC | NA1-AX-66 | 6NO+6NC | AC230V/5A | Only for Type M controller, cannot match suction undervoltage delay | AX-66 |
- Mechanical Interlock & Safety Accessories
4.1 Mechanical Interlock (Misoperation Prevention)
| 유형 | 모델 | 기능 | 애플리케이션 | Selection Code |
| Connecting Rod Interlock | NA1-LK-LG | Mutual interlock for two breakers to prevent simultaneous closing | Bus tie & ATS system | LK-LG |
| Cable Interlock | NA1-LK-GL | Remote mechanical interlock, standard cable length: 2중 | ATS system with large cabinet spacing | LK-GL |
| Key Lock | NA1-KEY | Multiple configurations: 1-lock-1-key, 2-lock-1-key | Unauthorized operation prevention | KEY-1-1 |
| KEY-2-1 | ||||
| Button Lock | NA1-BL | Lock closing/tripping buttons | Accidental touch prevention | BL |
4.2 Door Interlock
| 유형 | 모델 | 기능 | 애플리케이션 | Selection Code |
| Position Door Interlock | NA1-DL-WZ | Cabinet door locked at test/connected position | Draw-out breaker, electric shock prevention | DL-WZ |
| Status Door Interlock | NA1-DL-ZT | Cabinet door locked when breaker closed | Live operation prevention for all types | DL-ZT |
4.3 Other Safety Accessories
| 이름 | 모델 | 기능 | 애플리케이션 | Selection Code |
| Transparent Protective Cover | NA1-TP | IP54 protection for operating mechanism | Dust environments & safety enhancement | TP |
| Counter | NA1-CT | Mechanical operation counting | Frequent circuits & predictive maintenance | CT |
| Position Indicator | NA1-PS | Draw-out position indication (Disconnect/Test/Connected) | Draw-out breaker status monitoring | PS |
| Phase Barrier | NA1-PSB | Isolate three-phase busbars to prevent phase short circuit | Insulation improvement | PSB |
- 설치 & Connection Accessories
5.1 Main Circuit Accessories
| 이름 | 모델 | 평가 | 애플리케이션 | Selection Code |
| Horizontal Busbar | NA1-BUS-H | 3200에이 | Standard horizontal wiring | BUS-H |
| Vertical L-type Busbar | NA1-BUS-V | 3200에이 | 수직 설치 & space saving | BUS-V |
| Rotatable Busbar | NA1-BUS-R | 3200에이 | Flexible wiring for draw-out breakers | BUS-R |
5.2 Secondary Circuit Accessories
| 이름 | 모델 | 기능 | 애플리케이션 | Selection Code |
| Secondary Connector | NA1-SP | Secondary circuit connection for draw-out breakers | Quick plug & unplug | SP |
| Control Fuse | NA1-FU | 6에이, control circuit protection | Mandatory for all control loops | FU-6A |
- Complete Configuration Example
예:
NA1-3200X-3200M/3P, motorized draw-out type, AC220V, with shunt trip / undervoltage trip / closing solenoid + 5 sets transfer contacts + Profinet communication + connecting rod interlock
Complete Order Model:
NA1-3200X-3200M/3P Motorized Draw-out AC220 F-AC220 Q-AC230 X-AC220 AX-5Z COM-PN+PSU-1 LK-LG
- Accessory Application Notes
- Unified control voltage: Use identical voltage for shunt trip, undervoltage trip, closing solenoid and motor charging mechanism to simplify wiring.
- Communication matching: PSU-1 power module required for Profinet/EtherNet/IP; ST-DP module required for Profibus-DP.
- Auxiliary contact capacity: 5A@AC230V; use RU-1 relay module for high-power load control.
- Undervoltage trip requirement: Undervoltage trip coil must be powered on before breaker closing.
- Shunt trip specification: Single energization time ≤ 2s, frequency ≤ 5 times/min to avoid overheating damage.
접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지