친트 NM1LE800S-4300-800A MCCB

This is a CHINT NM1LE series 800A moulded case earth leakage circuit breaker with triple protection: 초과 적재, short-circuit and earth leakage. It has S-class breaking capacity (36kA@400V), 4-pole fixed installation, and adjustable rated residual operating current (30–500mA). It is widely used for personal electric shock protection and earth fault protection in industrial power distribution, high-power ...

  • 제품 세부정보

This is a CHINT NM1LE series 800A moulded case earth leakage 회로 차단기 with triple protection: 초과 적재, short-circuit and earth leakage. It has S-class breaking capacity (36kA@400V), 4-pole fixed installation, and adjustable rated residual operating current (30–500mA). It is widely used for personal electric shock protection and earth fault protection in industrial power distribution, high-power motor circuits and building electrical systems.

  1. Full Model Code Breakdown
부분Marking설명Technical Note
1NM1LE제품 시리즈MCCB with earth leakage protection (LE = Leakage) based on CHINT NM1 series
2800프레임 정격 전류Maximum frame current: 800에이
3에스차단 용량 등급S-class standard breaking capacity, 36kA@400V, for general distribution
44300극수 + trip type4 극 (3Ph+N), thermomagnetic trip (300 = no undervoltage release)
5800에이정격전류 (~ 안에)Continuous operating current: 800에이
  1. 주요 기술 매개변수
비고
제품 유형NM1LE series MCCB with earth leakage protectionClassic CHINT series with international advanced technology
정격 절연 전압 (우이)800다섯Maximum continuous voltage for insulation parts
정격 작동 전압 (우에)400뷔와 (50헤르츠)Standard for three-phase four-wire systems
정격 전류 내전압 (음)8kVWithstand capability against transient high voltage
Ultimate breaking capacity (중환자실)36kA@400VS-class, suitable for general industrial & commercial use
Service breaking capacity (IC)50% 중환자실Reusable after fault operation (GB 14048.2 compliant)
정격전류 (~ 안에)800에이Maximum continuous current
Trip characteristic열자기 (inverse time overload + instantaneous short-circuit)초과 적재: 0.8–1.0In adjustable; Instantaneous: 5-10인치
Earth leakage parametersRated residual operating current (IΔn): 30/100/200/300/500mA optionalProvides both personal shock protection and earth fault protection
Residual non-operating current (IΔn0): 0.5IΔn
Operating time: ≤0.3s (≤30mA), ≤0.1s (>30엄마)
폴란드4피 (3Ph+N)N pole for leakage detection only (not for short-circuit breaking except special versions)
장착 유형결정된Standard rail or bolt mounting; withdrawable not supported
Connection type전면 연결 (기준)Rear or plug-in connection optional
보호 정도IP30IEC 60529, protects against finger and solid foreign objects
주변 온도-5℃ ~ +40℃Derate required beyond this range
치수 (mm)H×W×D: 360×240×180Standard industrial size for panel installation
무게대략. 18kgIncludes leakage module; ~3kg heavier than standard NM1
  1. 일반적인 응용 분야
  2. Industrial power distribution systems

Main or sub-switch for three-phase four-wire 800A high-current circuits

Control circuits for large motors (예를 들어, 400kW induction motors) with full protection

Factories, 데이터 센터, mines requiring personal safety protection

  1. Building electrical systems

Main switchboards and emergency power circuits in commercial and high-rise buildings

Public buildings such as hospitals and schools with high safety requirements

Power circuits for HVAC, pump rooms and large equipment to prevent electrical fires

  1. Special safety applications

가혹한 환경: wet, 무미 건조한, corrosive locations (화학적인, textile plants)

Locations requiring high-level fire protection: warehouses, power distribution rooms

Heavy-duty equipment with frequent starts: 크레인, 압축기, to detect insulation failure

  1. 교체 모델

4.1 CHINT Upgrades / 교체품

교체 모델주요 차이점애플리케이션
NM1LE800H-4300-800ABreaking capacity upgraded to H-class (50kA@400V)Systems with high short-circuit current near transformers
NM1LE800S-4308-800AWith motorized operatorRemote control, unattended automation systems
NXMLE800S-4300-800ANew Kunlun Series, 더 작은 크기, improved performanceSystem upgrades, new installations
NM1LE800S-4310-800AWith undervoltage releaseCritical circuits requiring undervoltage protection (예를 들어, fire power)

4.2 Cross‑Brand Equivalents

상표모델주요 일치 매개변수메모
씨줄T6N800 PR221DS-LSI+RCD 800 4피In=800A, Icu=36kA, 4피, earth leakage전자여행 + leakage module, higher precision
슈나이더NSX800F TM800D+Vigi 4PIn=800A, Icu=36kA, 4피, thermomagnetic + 누출Identical breaking capacity, reliable Vigi module
지멘스3VA6880-6EL32-0AA0+3VA9180-0AA00In=800A, Icu=36kA, 3P+N, leakage add-on3VA series with leakage kit, 비슷한 성능
미쓰비시NF800-CW+leakage module 4PIn=800A, Icu=35kA, 4피, thermomagnetic + 누출Japanese brand, suitable for Japanese-equipped systems
  1. 선택 & 애플리케이션 노트
  2. 차단용량 매칭

Ensure short-circuit current ≤ 36kA@400V; otherwise use NM1LE800H (50그만큼).

S-class breaking capacity decreases at higher voltages; recheck for 690V systems.

  1. Earth leakage current selection

Personal protection / wet areas: IΔn = 30mA

장비 & fire protection: IΔn = 100–300mA

모터 & high-power loads: IΔn = 300–500mA to avoid nuisance tripping during startup.

  1. Poles and N‑pole configuration

4-pole for three-phase four-wire systems only; N wire must be connected.

N pole only detects leakage; it does not break short-circuit current (except special versions).

For interruptible N pole, select a special model with “N-pole breaking”.

  1. 설치 & 배선

Fixed mounting; allow ≥180mm depth for heat dissipation.

Use copper busbar/cable rated for 800A: ≥240mm² cable or 40×10mm busbar recommended.

Must be installed vertically, tilt ≤15°.

  1. 유지 & replacement

Test leakage function monthly using the TEST button.

Inspect contacts after short-circuit operation; replace if necessary.

For upgrades, prefer CHINT NXMLE Kunlun Series (호환 가능한 치수, better performance).

Leakage module can be replaced separately.

CHINT NM1LE800S-4300-800A is a reliable 800A earth leakage MCCB with triple protection, standard breaking capacity and 4-pole design, ideal for industrial automation and building electrical systems. Selection should consider short-circuit level, leakage requirements and installation space. For better performance and safety, use higher-breaking versions or the new Kunlun series when applicable.

CHINT NM1LE800S-4300-800A – Key Selection Notes

  1. Breaking Capacity Check

이 모델: S-class = 36kA@400V

If short-circuit current >36그만큼 (near transformer, main incomer), use NM1LE800H (50그만큼).

  1. 현재 등급

프레임 전류 800A, rated current 800A

For continuous loads ≤800A only; do not overload.

  1. 폴란드 & System Type

4300 = 4P (3Ph+N) + thermomagnetic trip

For three-phase four-wire (380V+N) systems only; N wire must be connected.

N pole does not break short-circuit current, only for leakage detection.

  1. Earth Leakage Selection

Available settings: 30/100/200/300/500엄마

Personal safety / wet areas: 30엄마

장비 / fire protection: 100–300mA

Motors / high-power loads: 300–500mA (prevents startup nuisance tripping)

  1. Trip Characteristics

열자기: 초과 적재 + 순간 단락 보호

Instantaneous range: 5-10인치

Set higher for motors to avoid tripping during startup.

  1. 설치 & 환경

Must be vertical, tilt ≤15°

Ambient: -5℃ ~ +40℃; derate at high temperature

IP20 open type; install in enclosure for dusty, wet or oily areas.

  1. 배선 & 열 방출

Use 800A-rated conductors:

≥240mm² copper cable or 40×10mm copper busbar

Terminations must be tightly torqued to avoid overheating.

  1. 유지 & 안전

Press TEST button monthly to verify leakage function.

Leakage module replaceable separately.

Not recommended for three-phase three-wire systems without neutral.

  1. Upgrade Recommendation

New CHINT NXMLE800S series: better performance, 더 작은 크기

Preferred for replacement or upgrade (dimensions nearly compatible).

이전: