Danfoss VLT2807 Compact Frequency Converter - 접촉기,회로 차단기,감지기,인코더,PLC,변환기

위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

Danfoss VLT2807 Compact Frequency Converter - 접촉기,회로 차단기,감지기,인코더,PLC,변환기

전기 같은/

Danfoss VLT2807 Compact Frequency Converter

Typical Application Scenarios for Danfoss VLT2807 (0.75 kW) The VLT2807 is a small-size general-purpose open-loop V/F frequency converter. It supports Constant Torque (CT) / 가변 토크 (버몬트) selection, built-in PID and AMA auto-adaptation. Compact side-by-side installation is supported. Mainly used for OEM equipment, HVAC-light-industry and assembly-line drives. Not suitable for high-precision vector control, heavy-shock loads or ...

  • 제품 세부정보

Typical Application Scenarios for 댄포스 VLT2807 (0.75 kW)

The VLT2807 is a small-size general-purpose open-loop V/F frequency converter. It supports Constant Torque (CT) / 가변 토크 (버몬트) selection, built-in PID and AMA auto-adaptation. Compact side-by-side installation is supported. Mainly used for OEM equipment, HVAC-light-industry and assembly-line drives. Not suitable for high-precision vector control, heavy-shock loads or high-inertia lifting applications.

상태: 단종. Legacy compact general-purpose 주파수 변환기, 0.75 kW, widely used for fans, 슬리퍼, assembly lines and small-size drive equipment.

  1. 모델 디코딩 (Full-model example: VLT2807PT4B20SBR1DBF12A00C1)

28: VLT2800 series

07: Power rating 0.75 kW / 1HP

피: Process variant

티: 3상 입력

4: 380-480 VAC

비: Book-style construction, IP20

R1: Built-in Class A1 EMC filter; R0 = No EMC filter

디: No brake chopper; B = Built-in brake chopper

F12: LCP local control panel; F00 = Without panel

Example order number: 134H2368 (with EMC filter and control panel)

  1. 핵심 전기 사양 (380-480 V version)
사양
정격 출력0.75 kW (1HP)
전원공급장치3×380‑480 V ±10 %, 50/60 헤르츠
정격 출력 전류4.2 에이
Apparent power1.7 kVA
보호 등급IP20
스위칭 주파수4‑16 kHz adjustable
열 방출Cabinet mounting; maintain 100 mm clearance top and bottom
순중량대략. 2.1 kg

A single-phase 220 V version VLT2807 (1×220-240 V) is also available, same 0.75 kW power rating, 4.2 A output current.

  1. Hardware Interface Overview

Main-circuit Terminals

입력: L1, L2, L3; Motor output: 유, 다섯, 여; PE 보호 접지; Brake resistor terminals (selected variants only)

Control Terminals (VLT2800 series)

디지털 입력: 18, 19, 27, 29, 33

Analogue inputs: 53 (voltage/current), 60 (현재의)

Analogue output: 42

RS485: 68/69 (Profibus-DP via optional expansion card)

Supported functions: Multi-speed, 시작/중지, PID, analogue reference, pulse reference, precision stop, auto-restart, AC braking.

  1. 주요 특징
  2. Quick Menu: Fast commissioning with 12 key motor-setup parameters; supports AMA motor auto-adaptation (Parameter P107).
  3. V/F 제어; selectable constant-torque / variable-torque mode; built-in PID for constant-pressure water-supply and fan applications.
  4. Supports brake resistor and AC braking; fault auto-reset and auto-restart.
  5. Optional Profibus-DP and DeviceNet fieldbus expansion cards.
  6. LCP panel supports parameter copy for batch-unit commissioning.
  7. Discontinued-product Replacement Solution

공식 직접 교체: VLT Midi Drive FC280, 0.75 kW, 380-480 다섯

Highly compatible mounting dimensions and terminal layout; plug-in terminals are reusable; parameters can be migrated.

Added Safe Torque-Off (STO) safety function with enhanced overall performance.

Alternative reference: FC-051 (경제형, not direct terminal-compatible; requires full rewiring for retrofit).

  1. 일반적인 오류 코드

Err 8: DC-bus under-voltage. 입력전압을 확인하세요, supply voltage drop or momentary power loss.

Err 1: 과전류; Err 4: 지락; Err 14: 접지 결함; Err 16: 단락; Err 29: 과열.

  1. Second-hand Unit Inspection Checklist
  2. Visual check: Swollen electrolytic capacitors, PCB corrosion, fan ageing.
  3. Power-on without motor: Check for alarms; test all panel keys.
  4. Run with small-size motor at no-load; verify three-phase output-voltage balance.
  5. Verify power rating, presence of EMC filter and built-in brake chopper.
  6. Back-up complete parameter set. Electrolytic capacitors are the main failure risk on this legacy series.
  7. Variable-torque loads (팬 & 슬리퍼, VT mode)

Torque decreases with speed; energy-saving operation; built-in PID for pressure/flow closed-loop regulation.

  1. 소형 원심 팬: 작업장 배기팬, 캐비닛 냉각 팬, air-handling-unit fans, small waste-gas-treatment fans.
  2. Water-supply / 순환 펌프: Small-scale constant-pressure water supply, cooling-water circulation pumps, 계량 펌프, process make-up pumps.
  3. HVAC terminal-units and small-building ventilation systems.

✅ 장점: PID sleep-wake-up function; soft-start to minimise water hammer; prominent energy-saving effect.

  1. Constant-torque loads (CT mode, 160 % overload for 1 min)

Torque remains largely independent of speed; sufficient starting-torque required. Mainly for assembly-line and light-industrial machinery.

  1. Conveying equipment: 소형 벨트 컨베이어, 롤러 컨베이어, 체인 컨베이어, sorting-line equipment.
  2. 포장 기계: 소형 포장 기계, sealers, 라벨러; precision-stop function for station positioning.
  3. Mixing-stirring equipment: Small mixing tanks, blenders and agitators.
  4. Light-industry & 직물: Auxiliary drives for small-size unwinding/winding, textile-machinery and cutting equipment.
  5. Extrusion & small-process equipment: Micro-extruders, material feeders.

메모: For long-time operation below 10 Hz, standard-motor cooling deteriorates. Variable-frequency motor with separate cooling fan is recommended.

III. Industry Sectors

  1. 공조: Fans and circulation pumps (most-common application).
  2. 포장 & light-industry OEM: Small-power drive units integrated into machinery.
  3. 수처리: Small-size water-supply and chemical-dosing metering pumps.
  4. 음식 & 음료: Small conveyors and agitators.
  5. General-factory automation: Auxiliary drives for production-lines.
  6. Unsuitable Operating Conditions
  7. High-inertia hoisting / lifting machines (only permitted for light-duty auxiliary mechanisms, not for main lifting drives).
  8. Applications requiring closed-loop vector control or high-dynamic-response servo-level performance.
  9. Continuous heavy-duty operation with frequent shock-loading.
  10. Long-term high-speed spindle operation above 400 Hz.
  11. Configuration Tips for Typical Applications
  12. 팬 / 펌프: Select R1 variant with built-in EMC filter; set P101 to Variable-Torque (버몬트).
  13. 컨베이어 / agitator: Requires high starting-torque; set P101 to Constant-Torque (CT). For frequent braking duty, select variant with built-in brake chopper (suffix-B in model code).
  14. Fieldbus control: Add Profibus-DP option card for PLC interfacing.

Complete Technical Specifications of Danfoss VLT2807 (VLT2800 series)

상태: 단종. 0.75 kW, available in single-phase 220 V and three-phase 380-480 V versions.

  1. Power-stage Electrical Parameters

① Three-phase 3×380-480 V (widely-used VLT2807PT4)

사양
Rated motor power0.75 kW / 1HP
Continuous rated output current Iinv2.1 에이
60‑second overload current3.3 에이 (160 % overload for 1 min)
Apparent power1.7 kVA
Input supply3×380‑480 VAC ±10 %, 50/60 헤르츠
Rated input current1.9 에이
60‑s maximum input current3.0 에이
DC‑bus voltage range540‑800 VDC

② Single-phase 1×220-240 V (VLT2807P1)

사양
Rated motor power0.75 kW / 1HP
Continuous rated output current Iinv4.2 에이
60‑second overload current6.7 에이 (160 % overload for 1 min)
Apparent power1.7 kVA
Input supply1×220‑240 VAC ±10 %, 50/60 헤르츠
Rated input current10.6 에이
60‑s maximum input current16.7 에이
DC‑bus voltage range280‑380 VDC

Overload rating: Constant-Torque (CT): 160 %, 60 s; Variable-Torque (버몬트): 110 % continuous.

  1. 성능 매개변수

Control principle: Open-loop V/F control. User-programmable V/F curve; no closed-loop vector capability.

Output-frequency range: 0-1000 헤르츠; factory default 0-50 Hz.

Carrier switching frequency: 4-16 kHz adjustable, factory default 4 kHz. Current-derating applies at higher switching frequencies.

Motor auto-adaptation AMA: Static AMA supported (P107).

Acceleration / deceleration times: 0.05-3600 s; four independent ramp-time sets selectable.

내장형 PID 컨트롤러: Closed-loop for fans/pumps; sleep-wake-up, 드라이런 보호, no-flow detection.

Braking modes: AC-braking; optional built-in brake chopper (-B model suffix) for external brake-resistor; DC-bus paralleling for load-sharing.

Restart functions: Fault auto-reset & restart, flying-start, power-drop protection.

III. Control-terminal Ratings

디지털 입력 (에서: Terminals 18, 19, 27, 29, 33)

수량: 5 디지털 입력; internal 24 V supply; compatible with NPN / PNP logic.

기능: Start-stop, 정방향/역방향, 다중 속도, fault-reset, pulse reference, output-inhibit.

Analogue Inputs

  1. Terminal 53: 0-10 V voltage / 0-20 엄마 / 4-20 엄마, 구성 가능.
  2. Terminal 60: 4-20 mA current-input only.

Analogue Output (Terminal 42)

1 analogue output: 0-20 엄마 / 4-20 mA programmable. May output frequency, output-current, output-voltage and other process variables.

릴레이 출력

1 릴레이 출력; contact rating AC250 V / 3 에이. Configurable for fault-signal, drive-running, frequency-reached and other status-signals.

통신 인터페이스

  1. 기준: RS485 (Terminals 68/69), supports Modbus-RTU and Metasys-N2 protocols.
  2. Optional expansion cards: 프로피버스-DP, 디바이스넷 (hardware option required).
  3. 기계 & 환경 사양
사양
Enclosure typeBook‑style, IP20; cabinet‑mount only
치수 (H×W×D)200 × 75 × 168 mm
순중량대략. 2.1 kg (without panel); 2.2‑2.6 kg with panel+filter
설치Vertical wall‑mount; side‑by‑side tight‑mount allowed; ≥100 mm vertical clearance top/bottom
Main‑circuit terminal torque0.5‑0.6 Nm; PE‑earth terminal 2‑3 Nm
작동 주변 온도0‑50 °C; derating above 45 °C
보관온도‑20 °C ~ +65 °C
고도No derating ≤1000 m above sea‑level; 디레이팅 필요 >1000 m
보호 등급IP20; not for outdoor installation
  1. Maximum Permissible Motor-cable Length

비차폐 케이블: 200 m (with motor-reactor fitted).

Shielded cable: 100 m (with motor-reactor fitted).

R1 version (built-in A1-EMC filter): 맥스. 50 m shielded cable.

R0 version (no built-in filter): 맥스. 25 m shielded cable.

  1. EMC & Safety Standards

R1 variant: Complies with EN55011 Class A1 (industrial EMC filter). R0: No internal filter.

승인: UL, CE. No built-in Safe-Torque-Off (STO) (STO introduced on successor FC280).

Ⅶ. Model-code Breakdown (VLT2807 full-model string)

VLT2807 P T 4 비 20 S B R1 D B F12 A00 C1

P = Process; T = Three-phase; 4 = 380-480 V; B = Book-style; 20 = IP20

R1 = Built-in A1-EMC filter; R0 = No filter

D = No brake chopper; B = Built-in brake chopper

F12 = With LCP keypad; F00 = Without keypad

Ⅷ. Reference Order Numbers

VLT2807PT4B20SBR1DBF12A00C1 (필터 포함 + 패널): 134H2368

VLT2807PT4B20STR0DBF00A00C1 (no filter, no panel): 195N1013

  1. Replacement-model Parameter Comparison

FC280 Midi Drive 0.75 kW, 380-480 다섯

Identical power rating; high terminal-hardware compatibility; STO safety-function integrated; standard RS485 Modbus. Direct hardware replacement for VLT2807.

Control Modes of Danfoss VLT2807

Parameter P100 (Configuration Mode) defines the high-level drive-operating mode. The underlying motor algorithm is fixed as open-loop V/F. Vector-control and field-oriented control are not supported.

  1. Underlying Motor-control Algorithm
  2. Open-loop V/F (Voltage-to-Frequency) 제어 (only motor-control algorithm)

Selectable Constant-Torque (CT) / Variable-Torque (버몬트) via P101; custom V/F curve available.

Static AMA motor auto-adaptation is supported for motor-stator-voltage-drop compensation.

No encoder-based closed-loop speed-vector control; not for high-precision speed-regulation.

  1. Four Operating-mode Settings of Parameter P100
P100 ValueMode Name설명일반적인 응용
0Open‑loop speed controlV/F open‑loop; speed reference from external source; no feedback팬, 슬리퍼, 컨베이어, general‑purpose speed‑regulation (most‑used setting)
1Closed‑loop speed controlHardware‑encoder interface is not available on VLT2807. This is a residual menu‑option and cannot be used in practical projects.Encoder‑based closed‑loop speed‑control (not implementable on VLT2807)
2예약된Spare setting사용되지 않음
3Process‑PID closed‑loop controlBuilt‑in PID controller, regulates against pressure/flow process‑feedback signalConstant‑pressure water‑supply, constant‑air‑volume fans; pump‑sleep function available

✅ Practical field-usage: P100=0 Open-loop speed control and P100=3 Process-PID closed-loop control.

III. Reference-source & Command-source Options

  1. Local panel control (LCP keypad)

Parameter 002=1 LOCAL

Start-stop, forward/reverse and frequency reference set via keypad buttons.

Used for commissioning and local manual operation of standalone units.

  1. External-terminal remote control (Parameter 002=0 REMOTE)

① Analogue-reference speed setting

Terminal 53: 0-10 다섯 / 0-20 엄마 / 4-20 엄마; potentiometer-speed-setting.

Terminal 60: 4-20 mA current-input only.

Terminal 33 configurable as pulse-frequency reference, max. 67.6 kHz.

② Digital-terminal control

Multi-speed: Combinations of digital-input terminals, 최대 8 preset fixed-speed setpoints.

Start-stop and direction: Terminal 18 for start, Terminal 19 for reverse.

Jog-function, precision-stop, fault-reset, output-inhibit.

  1. Fieldbus communication control
  2. Native RS485 (Terminals 68/69): 모드버스-RTU, Metasys-N2. PLC controls start-stop, speed-reference and parameter-access.
  3. Optional expansion cards: 프로피버스-DP / DeviceNet for bus-based command & reference.
  4. Mixed-source control

Command-source and reference-source may differ. 예: Terminals for start-stop while bus provides frequency-reference; or bus for start-stop with potentiometer-analogue reference.

  1. Braking Modes
  2. AC-braking: Low-frequency AC excitation for fast deceleration; no extra hardware required.
  3. DC-injection braking: DC injection to lock motor-shaft during stop; configurable braking-time and braking-voltage level.
  4. Brake-chopper + brake-resistor (-B model suffix): Energy-dissipation braking for high-inertia regenerative-load applications.
  5. Start-stop Logic Types
  6. Ramp-start-stop: Smooth speed-ramp-up / ramp-down following acceleration-deceleration times.
  7. Flying-start: Detect and synchronise to already-rotating motor speed.
  8. Precision-stop: Counter-based stop for conveyor-station positioning.
  9. Free-coast stop; Fast-stop OFF3.
  10. Unsupported Control Functions

❌ No vector control (no VVC-plus, no flux-vector).

❌ No encoder-based closed-loop speed-control (no hardware encoder-interface).

❌ No positioning or servo-position-control.

❌ No Safe-Torque-Off (STO).

Typical Application-configuration Examples

  1. General fan / conveyor speed-regulation: P100=0 Open-loop speed; terminal-start-stop + potentiometer reference on Terminal 53.
  2. Constant-pressure water-supply pump: P100=3 Process-PID closed-loop; 4-20 mA pressure-transmitter connected to Terminal 60.
  3. PLC fieldbus control: P100=0 Open-loop speed; RS485 Modbus-RTU; start-stop and speed-reference fully via bus.

이전:

다음:

답장을 남겨주세요