QUINT-ORING/24DC/2X40/1X80
제품개요
Active DC redundancy module (Oring module), DIN 레일 마운트. Designed for parallel redundant 전원 공급 장치 of two 24VDC power supplies. Adopts MOSFET active current balancing ACB technology to resolve the drawbacks of diode redundancy, such as large voltage drop and unbalanced current sharing. Widely used in industrial control cabinets, DCS and PLC critical power supply circuits. It enables seamless switching when one power supply fails to guarantee continuous power to loads.
주요 사양
| 목 | 매개변수 |
| 주문 번호. | 2902879 |
| 입력 | 2 channels of 24VDC, 최대. 40채널당 A; operating voltage range 18–29.5VDC |
| 산출 | Single-channel 24VDC, total rated 80A |
| 토폴로지 | Active Oring, MOSFET, efficiency up to 98% |
| 기능 | ACB automatic current balancing, preventive monitoring for input/output/decoupling circuit, overvoltage clamping to 32V |
| 터미널 | 나사 터미널 |
| 설치 | Built-in UTA107/30 DIN rail adapter |
| 보호 등급 | IP20 |
| 작동 온도 | -25℃ ~ +60℃ |
| 인증 | CE, cULus, RoHS 규제 |
| HS코드 | 85371091 |
작동 원리
Two 24V power supplies connect to the two input channels respectively. The module automatically balances load current. If either power supply fails or loses power, the internal MOSFET isolates the faulty branch rapidly, and the healthy power supply continues to power the load. Monitoring contacts can send fault signals to upper-level PLC.
일반적인 애플리케이션 시나리오
Redundant power supply for DCS and safety instrumented systems in petrochemical, power generation and railway industries
Large-scale automated production lines and warehouse logistics control systems
Server rooms and security monitoring DC redundant power supply
대체 선택 참조
- Lower-current model of the same series: 2902878 QUINT-ORING/24DC/2X20/1X40 (2×20A input, 40출력)
- 대체 솔루션: 다이오드형 이중화 모듈 (저렴한 비용, but with voltage drop, not suitable for high-current precision power supply)
문제 해결 지침
- Red LED alarm: Check single-channel input undervoltage, power supply failure or module overheating
- Output voltage drop: Verify input wire gauge, tightening torque of terminals under high-current conditions; check heat dissipation clearance of the module
- Current imbalance: The output voltages of the two power supplies must be calibrated consistently for normal ACB current sharing
Active MOSFET Oring Redundancy Module vs. Conventional Diode Redundancy Module
Conventional redundancy modules refer to diode-type passive redundancy modules, 즉 피닉스 QUINT-DIODE series. 그만큼 2902879 QUINT-ORING is an active MOSFET Oring module. The core differences are listed below:
- 핵심 구성 요소 & 전압 강하 (Most Critical Difference)
Active Oring (MOSFET)
Internally uses controlled MOSFET switches; conduction drop at tens of millivolts, nearly negligible, efficiency up to 98%.
Low heat generation under high-current operation. No need to deliberately raise power supply output voltage to compensate for voltage drop.
Conventional Diode Redundancy (Passive)
Relies on Schottky diodes for unidirectional conduction; voltage drop of 0.3~0.4V.
High power dissipation and heat generation at 80A. Engineers must increase the power supply output by ~0.4V for compensation, otherwise load-side voltage will be insufficient.
- Load Current Sharing (ACB Automatic Current Balance)
Active Oring (예를 들어. 2902879)
Equipped with ACB automatic current balance technology. Two power supplies share the load current equally. Both power supplies carry load continuously, 서비스 수명 연장. Not a setup where one unit runs at full load while the other stands by.
Diode Redundancy
No active current sharing. The power supply with slightly higher output voltage takes most of the load, while the other remains almost unloaded. One unit ages faster in long-term operation; it is a hot standby scheme without load sharing.
- 모니터링, 경보 & 진단
Active Oring
Continuously monitors two input voltages and MOSFET decoupling circuit status. Relay alarm contacts are available to report faults: loss of single power supply, module overheating, decoupling circuit failure, OVP overvoltage clamping (limits maximum output voltage to protect PLC/DCS cards). It provides early warning of lost redundancy for maintenance replacement before dual faults cause shutdown.
Diode Redundancy
Pure passive hardware with no monitoring or alarm signals. If one power supply fails, the system remains powered, but the loss of redundancy cannot be detected until the second power supply also fails and causes outage.
- Fault Isolation Speed
Active Oring: MOSFET turns off in microseconds. Reverse current is detected and the faulty branch is cut off immediately to prevent the failed power supply from pulling down the output bus.
Diode Redundancy: Passive blocking via inherent diode unidirectional characteristic; response depends on diode properties.
- 비용, 신뢰할 수 있음 & 적용범위
Active Oring (2902879 유형)
✅ 장점: Low voltage drop, 낮은 발열, automatic current sharing, 결함 모니터링, 과전압 보호, high availability
❌ Disadvantages: More complex circuit, 더 높은 가격, built-in control circuit
👉 Applications: DCS, SIS safety instrumented systems, power/petrochemical/railway industries, high-value production lines, critical high-current 24V power circuits where unexpected shutdown is prohibited.
Conventional Diode Redundancy Module
✅ 장점: 간단한 구조, few components, stable reliability, 저렴한 비용, no control circuit, suitable for explosion-proof environments
❌ Disadvantages: Large voltage drop, severe heat at high current, no current sharing, no fault alarm, heavy heat dissipation burden under high current
👉 Applications: Ordinary control cabinets, low/medium-current auxiliary circuits, projects with limited budget that only require basic anti-parallel reverse protection.
비교표
| 비교항목 | Active Oring Redundancy Module (2902879) | Conventional Diode Redundancy Module |
| 핵심 구성 요소 | Controlled MOSFET + 제어 회로 | Schottky diode |
| Conduction Drop | <50mV | 0.3~0.4V |
| Current Sharing | ACB automatic load sharing | No current sharing; higher-voltage supply bears most load |
| 모니터링 & 경보 | Input/circuit monitoring, relay fault output, OVP overvoltage clamping | No monitoring or alarm |
| 능률 | ~98% | 낮추다, severe heat generation at high current |
| 비용 | 더 높은 | 낮은 |
| 일반적인 시나리오 | SIS, DCS, critical high-current industrial power supply | Ordinary control cabinets, low/medium-current auxiliary circuits |
선택 추천
If current ≥40A, high shutdown loss is expected and remote redundancy status monitoring is required → Select active Oring such as 2902879
For low-current auxiliary circuits with limited budget, only basic anti-reverse parallel protection needed → Diode redundancy module is sufficient
Phoenix QUINT-ORING Active Redundancy Module Full Series List (ACB Auto Current Balancing MOSFET Oring, 일련의 2902879)
-메모: Distinguish QUINT-ORING (original standard version) / QUINT4-ORING (4th generation new version); `/CO` denotes conformal coated version (anti-corrosion for chemical plants and high-humidity environments)
- QUINT-ORING (Original Series, fixed 24DC input, your model belongs here)
| 주문 번호. | 전체 모델 | 사양 | 비고 |
| 2902877 | QUINT-ORING/24DC/2X10/1X20 | 2×10A input, 20출력 | 기준, non-coated |
| 2902878 | QUINT-ORING/24DC/2X20/1X40 | 2×20A input, 40출력 | 기준, non-coated |
| 2902879 | QUINT-ORING/24DC/2X40/1X80 | 2×40A input, 80출력 | 귀하의 모델 |
| 2320173 | QUINT-ORING/24DC/2X10/1X20/CO | 2×10A input, 20출력 | Conformal coated /CO |
| 2320186 | QUINT-ORING/24DC/2X20/1X40/CO | 2×20A input, 40출력 | Conformal coated /CO |
| 2320199 | QUINT-ORING/24DC/2X40/1X80/CO | 2×40A input, 80출력 | Conformal coated /CO |
- QUINT4-ORING (4th generation upgraded model, 12~24VDC wide input, new replacement)
| 주문 번호. | 전체 모델 | 사양 | 비고 |
| 1088206 | QUINT4-ORING/12-24DC/2X10/2X10 | 2 independent outputs, 10A each | 12~24V wide DC input |
| 2905488 | QUINT4-ORING/12-24DC/2X20/1X40 | 2×20A input, 40출력 | 12~24V wide DC input |
| 2905489 | QUINT4-S-ORING/12-24DC/1X40 | Single channel 40A, single-channel Oring (anti-reverse / isolation for single power supply) | Single-channel version |
- Passive Diode Redundancy of the same platform (QUINT-DIODE, not part of ORING active series, 참고용으로만)
-Passive diode redundancy, no ACB current sharing, no active MOSFET, do not confuse with ORING
2907719 QUINT4-다이오드/12-24DC/2X20/1X40
2320157 5중 다이오드/12-24DC/2X20/1X40
Series Selection Summary
- QUINT-ORING (2902877/2902878/2902879): Fixed 24VDC input, ACB active current balancing, standard for industrial cabinets; `/CO` coated variant for chemical, offshore and highly corrosive environments.
- QUINT4-ORING: 12~24VDC wide DC input, new generation hardware with optimized dimension and monitoring logic. Preferred for new projects.
- Current ratings: 20A /40A /80A. Match rating according to rated current of the two power supplies.
Model Naming Breakdown (QUINT-ORING/24DC/2X40/1X80)
QUINT-ORING: QUINT series active redundancy Oring module
24DC: Rated input 24V DC
2X40: Two input channels, 최대. 40채널당 A
1X80: Combined single output channel, 최대. 80에이
/콜로라도: 컨포멀 코팅, anti-corrosion protective coating