KEYENCE KV-C32XA 입력 확장 모듈

유형: 32-point DC input expansion module (MIL connector type), Discontinued Compatible PLC Series: KV-5000 / KV-7000 / KV-8000 Core Specifications I/O Type: 디지털 입력, 32 points Wiring: MIL standard connector Input Mode (selectable via software): DC24V / DC5V Maximum Input Voltage: DC26.4V DC24V Mode: Rated 24V, 5.3엄마; ON ≥ 19V; OFF ≤ 1.5V DC5V Mode: ...

  • 제품 세부정보

유형: 32-point DC input expansion module (MIL connector type), 단종

호환 가능 PLC 시리즈: KV-5000 / KV-7000 / KV-8000

핵심사양

I/O Type: 디지털 입력, 32 전철기

배선: MIL standard connector

Input Mode (selectable via software): DC24V / DC5V

Maximum Input Voltage: DC26.4V

DC24V Mode: Rated 24V, 5.3엄마; ON ≥ 19V; OFF ≤ 1.5V

DC5V Mode: Rated 5V, 1엄마; ON ≥ 3.5V; OFF ≤ 1.5V

공통 터미널: 1 common group for all 32 전철기 (2 COM terminals)

Input Filter Time: 3 selectable settings (25μs / 1ms / 10ms)

Internal Current Consumption: ≤15mA

인증: UL, CSA

모델 선택 & 교체 참조

Replacement options with MIL connector for 32-point input:

KV-C32XTD (new high-speed input model, supports 5V/24V input)

메모: KV-C32XA is input-only, 출력 없음. Do not confuse it with KV-C32TA (32-point transistor output module).

호환 가능한 액세서리

케이블: OP-series MIL cables, relay terminal blocks

End Cover: OP-84203 (KV bus terminator unit)

보충 노트

  1. 재고만 있음 / used units available after discontinuation; 새로운 프로젝트에는 권장되지 않습니다.
  2. 5V mode is used for encoder and TTL level signal acquisition; 24V mode for conventional NPN sensors.
  3. Single common terminal for all 32 전철기; no isolated grouping support.

Typical Engineering Application Cases of KV-C32XA

Recap of key features: 32-point MIL connector input, dual DC24V / DC5V TTL mode, minimum 25μs high-speed filter, single COM terminal. Compatible with KV-5000/7000/8000. 단종, mainly used for retrofitting old equipment and spare part replacement. 5V mode is its biggest advantage compared with ordinary 32-point input modules.

사례 1: Multi-station Fixture Tooling (24V mode, 가장 일반적인)

장비 유형: Consumer electronics PCB test fixtures, multi-channel pressing fixtures

하드웨어 구성: KV-8000 CPU + KV-C32XA + Solenoid valve output module

Connected Signals: 32-point DC24V NPN sensors

섬유 / diffuse photoelectric sensors: workpiece presence, 위치 확인

Magnetic switches: cylinder home and end-position signals

리미트 스위치, 비상 정지, 안전문, manual pushbuttons

구현: MIL plug directly connected to internal fixture wiring, no heavy terminal blocks required for quick fixture swap and pluggable wiring. 32-point centralized signal acquisition for interlock, mistake-proofing and NG judgment in PLC program.

장점 & 단점: Compact fixture space, concentrated I/O, fast swap; downside: shared COM for all 32 points without isolation. Short circuit on one channel affects the whole module.

사례 2: 인코더 / TTL Pulse Signal Acquisition (5V mode, signature application)

장비 유형: Precision displacement stages, optical inspection platforms, semiconductor dicing machines

하드웨어 구성: KV-7000 + KV-C32XA (set to DC5V mode)

Connected Signals: Single-ended TTL A/B phase, Z zero-index, latch trigger signals converted from differential signals

Multiple incremental encoders (single-ended 5V)

5V trigger, 준비가 된, judgment signals from cameras and laser rangefinders

32-bit parallel status words output from FPGA / motion control boards

이점: 25μs high-speed filter for high-frequency TTL signals. Ordinary 24V input modules cannot accept 5V level directly. This was the main reason for selecting KV-C32XA in the past.

주의: Only supports single-ended TTL; differential signals require prior conversion. Critical to share the same ground between encoders and the PLC controller.

사례 3: Aggregated Judgment Signals for Vision Inspection Stations (24다섯)

장비 유형: Multi-camera vision inspection machines, AOI appearance inspection equipment

하드웨어 구성: KV-5000 + 2 × KV-C32XA

Connected Signals: Judgment output, buffer full, trigger request, 잘못, light ready, scan OK/NG signals from multiple vision controllers (키엔스 IV, XG series), plus material in-position and cylinder magnetic switch signals.

논리: Collect decentralized vision judgment signals into PLC for sorting, 계산, traceability and MES upload.

Engineering Practice: MIL cables routed to relay boards inside the vision cabinet to reduce scattered wiring.

사례 4: 개조 & Spare Parts Replacement for Existing Production Lines (Most common for legacy assets)

대본: Old KV-5000/7000 assembly lines, injection molding robots and packaging lines originally fitted with KV-C32XA. Damaged modules replaced by stock / second-hand units.

Original equipment uses prefabricated MIL harnesses; high modification cost if switching to screw-terminal 32X modules.

Selection reminder: New projects prefer KV-C32XC / KV-C32XTD; KV-C32XA is only used for legacy lines without harness modification.

위험 경고: Stock is scarce after EOL. Verify 5V level threshold and filter parameters after delivery to avoid mismatches with original program logic.

사례 5: Parallel IO Code Disk, Matrix Keypad / Selector Switch Acquisition (5V mode)

장비 유형: Test sorters, programmable test benches, probe stations

용법: Read 32-bit binary status from a board in parallel at 5V level with high-speed latching. Used to read multi-channel relay matrix and channel selection codes.

이점: Read 32 bits in one cycle, faster than RS485 polling. Suitable for test stations requiring synchronous sampling.

사례 6: 위치, Stopper and Material Sensor Acquisition for Conveyor Sorting Lines (24V mode)

장비: Small belt sorters, material box recirculation lines

Connected Signals: Material presence, stopper position, diverter cylinder, grating, overflow alarm, manual reset buttons. 32-point I/O concentrated at the sorting head; MIL plug allows whole sorting head disassembly.

선택 & Commissioning Troubleshooting Summary (Field Experience)

  1. Mode change via software only: DC24V / 5V is set in KV Studio unit parameters, no hardware jumper. Wrong mode setting causes unstable or missing signals.
  2. Single COM limitation: 1 common terminal for all 32 전철기. NPN and PNP cannot be mixed on one module; channel isolation is impossible. Use separate modules if isolation is required.
  3. 5V mode still rated max DC26.4V: Direct 24V wiring under 5V mode burns input channels.
  4. 25μs high-speed filter is sensitive to noise. Use 1ms / 10ms filter for long cables or near large motors.
  5. MIL connectors have limited mechanical life. Frequent fixture plugging causes poor contact from oxidation; most failures are connector issues rather than module damage.

Complete List of KEYENCE KV Series Digital Input Expansion Modules

메모: Only input-only modules (출력 없음). Separated into discontinued XA series, current XC local expansion series, KV-N / NC remote EtherNet/IP I/O input units. 혼합 I/O (XTD/EXT), 고속 카운터, analog and temperature modules excluded. 호환 가능한 CPU: KV-5000/7000/8000

  1. Discontinued XA Series (MIL connector)
모델전철기배선Input Spec비고
KV-C16XA16MIL connectorDC5V / DC24V software selectable단종
KV-C32XA32MIL connectorDC5V / DC24V software selectable단종, 대상 모델
KV-C64XA64Dual MIL connectorDC24V 전용, supports 2-wire sensors단종, 32 points per COM group

XA replacement: XC series of same point count (KV-C32XC replaces KV-C32XA)

  1. Current XC Series (Local backplane expansion, mainstream active models)
모델전철기배선Input Spec
KV-B16XC16Removable screw terminalDC5V / DC24V software selectable
KV-C32XC32MIL connectorDC5V / DC24V software selectable
KV-C64XC64Dual MIL connectorDC24V 전용
  1. KV-N / KV-NC Remote EtherNet/IP Input Units (분산 I/O)
모델전철기배선Input Spec
KV-N8EX8나사식 터미널DC24V
KV-N16EX16나사식 터미널DC5V / DC24V selectable
KV-NC16EX16MIL connectorDC5V / DC24V selectable
KV-NC16EXE16European terminalDC5V / DC24V selectable
KV-NC32EX32MIL connectorDC5V / DC24V selectable
KV-NC32EXE32European terminalDC24V

Confusable Models (NOT input-only modules)

KV-C16XTD / KV-C32XTD: 혼합 I/O (입력 + 산출)

KV-NC16EXT / KV-NC32EXT: Remote mixed I/O

KV-SIR32XT: High-speed synchronous I/O unit (high-speed input + 산출, motion dedicated, not general DI)

KV-SSC02: High-speed counter unit, not general digital input

Quick Replacement Table (XA → XC)

KV-C16XA → KV-B16XC (단말기) / KV-NC16EX (remote connector)

KV-C32XA → KV-C32XC (MIL connector, preferred replacement)

KV-C64XA → KV-C64XC

Installation Guide for KEYENCE KV‑5000/7000/8000 Local Input Expansion Modules (KV‑C32XA / C32XC / B16XC etc.)

Critical Rule: Power off before all installation and removal. Hot-swap is strictly prohibited. Hot-swap triggers bus error and damages backplane connectors.

  1. 설치환경 & DIN 레일 장착
  2. 작동 조건: 0~55℃, humidity 5%~95%RH non-condensing. Keep away from dust, 부식성 가스, strong electromagnetic interference and oil splash. 고도 ≤2000m.
  3. Cooling Clearance: Reserve ≥30mm space top, bottom and side of modules. Install vertically inside cabinet; avoid upside-down or horizontal mounting.
  4. DIN 레일: 표준 35mm DIN 레일. Align the rear latch with rail and press down to lock. Lift the release tab at bottom to detach.
  5. 접지: FG terminals of cabinet, CPU and modules connect to class D ground, 접지 저항 ≤100Ω. Single-ended shield grounding for signal cables.
  6. Backplane Bus Daisy-chain Installation (Local expansion for XA/XC)

순서: CPU → chained expansion modules → Termination cover OP‑84203 must be fitted on the last module

  1. Remove the protective cover on CPU right-side expansion port (keep the cover for future disassembly).
  2. Each module has expansion bus connectors on both sides: Left connector mates with previous unit, right connector mates with next unit.
  3. Align modules, insert vertically and fully engage bus connectors. Do not force at an angle, which may bend pins.
  4. Module arrangement: 입력, output and special modules after CPU. Total expansion count cannot exceed the CPU maximum supported unit limit.
  5. Bus termination: Fit OP‑84203 termination cover on the right port of the last module in the chain. Missing termination causes unstable bus, intermittent module dropout and unit error alarms.

메모: XA/XC are local backplane I/O. KV‑NC series are EtherNet/IP remote I/O and do NOT use this backplane daisy-chain method.

  1. External I/O Wiring (KV‑C32XA as MIL example)
  2. Confirm mode first: DC24V / DC5V TTL configured via KV Studio, no hardware DIP switch. Define before power-on. 24V applied under 5V mode burns channels.
  3. COM Common: C32XA uses one COM group for all 32 전철기. NPN 센서: COM to 0V; PNP 센서: COM to 24V+. NPN and PNP cannot mix on one module.
  4. MIL Plug: Use OP-series MIL cables. Insert straight into module MIL socket and lock the latch. Do not pull cables to bear mechanical load.
  5. Cable Separation: Separate high-power cables (솔레노이드, power wiring) and MIL signal cables by ≥100mm. Use shielded cable for long-distance or high-speed 5V TTL signals to reduce interference.
  6. 전원공급장치: Module is powered by PLC backplane bus, no separate power supply required for the module. Sensor power (24V/5V) comes from external independent power supply, common ground with PLC power supply.
  7. 소프트웨어 구성 (KV Studio)
  8. Complete hardware installation and wiring, double-check before power-up.
  9. Open KV Studio, enter Unit Editor.
  10. Add CPU and expansion modules (예를 들어. KV‑C32XA) in exactly the same physical order as installed.
  11. Select the input module, open unit parameters: set input mode (24다섯 / 5다섯), 필터 시간 (25μs / 1ms / 10ms).
  12. Download project to PLC, restart PLC. Enter monitor mode to confirm module LED status, no ERR alarm, and DI points can monitor signals normally.
  13. Supplementary Installation for Remote Input Modules (KV‑NC16EX / NC32EX etc.)

These are EtherNet/IP remote I/O and do not connect to CPU backplane bus:

  1. DIN 레일 장착, power off for wiring.
  2. Remote module powered independently by DC24V.
  3. Ethernet cable to EtherNet/IP bus, follow EtherNet/IP bus termination rules.
  4. Import EDS file and configure I/O mapping in KV Studio EtherNet/IP setup.
  5. 제거 절차
  6. Power off the whole PLC system.
  7. Disconnect external MIL / terminal signal wires first.
  8. Start from the last module: remove termination cover, then disconnect bus connectors between modules sequentially.
  9. Lift DIN rail latch and remove module from rail.
  10. Refit protective covers on unused bus ports.
  11. Common Installation Faults
  12. Missing termination cover → random unit error, modules detected intermittently.
  13. Mismatch between physical module order and software configuration → unit mismatch error.
  14. 24V wired under 5V mode → channel burnout.
  15. Forced angled insertion of bus connector → bent pins and poor contact.
  16. No common ground for 5V TTL signals → signal jitter and false triggering.
  17. Signal cables run together with power cables → noise and erratic signal at 25μs high-speed filter setting.

이전:

답장을 남겨주세요