NV = Earth Leakage Circuit Breaker (ELCB); NF = standard MCCB without earth leakage protection; 125 = Frame size AF125A; SV = Standard S model; 3P = 3-pole; 63A = rated operational current In=63A
✅ Core Electrical Specifications
| 목 | 매개변수 |
| 전체 모델 번호. | NV125‑SV 3P 63A with adjustable earth leakage 100/200/500mA |
| Rated Voltage Ue | AC100~440V, suitable for 3-phase 3-wire / single-phase 2-wire circuits |
| 정격 전류 입력 | 63에이 |
| 폴란드 | 3피 (3 단계, neutral not switched) |
| Short-circuit Breaking Capacity Icu/Ics@AC400V | 30그만큼 / 30그만큼 |
| Earth Leakage Sensitivity | 3-레벨 조절 가능: 100엄마 / 200엄마 / 500엄마 |
| 누설 유형 | 교류형, surge resistant, anti-harmonic, suppresses nuisance tripping |
| 작동 시간 | 맥스. 0.04에스 |
| 전반적인 차원 (폭×높이×깊이) | 90mm × 130mm × 90mm |
| 무게 | 대략. 1.1kg |
📌 Model Code Breakdown
- NV: Earth Leakage Circuit Breaker (ELCB, moulded case type with leakage protection)
- 125: Frame rating 125A (프레임 크기, this unit rated 63A)
- SV: 표준 S형 (New WS-V generation); CV = Economy type, HV = High breaking capacity type
- 3피: 3-폴, protects 3 live phases, neutral line does not pass through breaker
- 63에이: Continuous rated circuit current 63A
Common suffix: 1.2.500MA = 100/200/500mA adjustable earth leakage
🛠️ Application Scenarios
Industrial control panels, 물 펌프, 팬, small 3-phase power circuits
Integrated protection for equipment: 누전, 초과 적재 & 단락 보호
Suitable for harmonic-rich environments (VFD, 서보 드라이브), less prone to nuisance tripping than older generations
패널 장착, standard screw terminals; 옵션 액세서리: Alarm switch AL, Auxiliary switch AX, 션트 트립 / Under-voltage coil
⚠️ Selection & 교체 노트
- Distinguish NV (ELCB with leakage) vs NF (standard MCCB without leakage). Similar appearance, 직접 교환할 수 없음.
- 3P version does NOT disconnect neutral conductor. Select 4P model NV125-SV 4P if neutral switching is required.
- Earth leakage threshold is preset at factory and adjustable via rotary knob on site; 100개인 보호를 위한 mA, 200/500mA for equipment fire protection.
- Domestic alternatives reference: CHNT NM1LE-125S/3P 63A, Delixi CDM1LE-125/3P 63A; verify breaking capacity and adjustable leakage range.
- Within the same frame size, current rating can be changed directly (63/75/80/100/125에이), mounting dimensions remain unchanged.
🧰 Troubleshooting Quick Reference
Trips immediately upon closing: Priority check for earth leakage or damaged load insulation; try higher leakage threshold.
과부하 트리핑: Continuous load current >63에이; inspect motor / cable loading.
단락 트리핑: Severe short circuit; power off and inspect for phase-to-phase short circuit.
Leakage protection fails to operate: Press red TEST button periodically; verify leakage function monthly.
미쓰비시 NV125-SV (WS-V Series) Built-in Accessory List (도끼 / 알 / SHT / UVT)
All accessories are clip-on built-in modules, field mountable; compatible for NV125-SV / NF125-SV same frame; accessories installed in the right-side compartment of breaker.
- AX Auxiliary Switch
모델: 도끼-03SVU
기능: Reports ON/OFF status of main contacts, cannot distinguish manual opening or fault tripping
접점등급: 1a1b (1NO +1NC)
애플리케이션: Send breaker position signal to PLC / indicator lamps
배선: Lead wire type; SLT version available with terminal block
- AL Alarm Switch
모델: 알-03SVU
기능: Activates ONLY when tripped by fault (초과 적재, 단락, 누전); no action during manual opening
접점등급: 1a1b
애플리케이션: Fault trip alarm, SCADA signal upload, 들리는 & 시각적 경보
Combined module: ALAX-03SVU = integrated AX+AL module (provides both position feedback and fault trip signal, 가장 널리 사용되는)
- SHT Shunt Trip
Voltage variants:
SHTA240-03SVU: AC100~240V AC shunt trip
SHTA440-03SVU: AC200~440V AC shunt trip
SHTD100-03SVU: DC24V DC shunt trip
접미사 U: built-in module; L = extended lead; S = special spec
기능: Remote electrical trip via control signal; used for emergency stop, fire linkage circuit cut-off
Important note: Short-time energized type, continuous power supply is prohibited.
- UVT Under Voltage Trip
Two types:
UVTN-03SVU Non-synchronous UVT: Instant trip upon voltage drop
UVTS-03SVU Synchronous UVT: Trip at voltage zero-crossing during voltage drop, for large inductive loads to reduce breaking surge
Voltage ratings: AC100/200/240/400V optional
기능: Automatic trip when main circuit voltage drops or power loss; will NOT auto-reclose after voltage recovery, manual closing required on site.
External Accessories for NV125-SV
| 액세서리 모델 | 이름 | 설명 |
| TC‑1SV | 단자 커버 | Insulation protection for exposed terminals |
| LC‑1SV | Padlock device | Handle lockout, prevent accidental closing |
| MI‑05SV3 | 기계적 인터록 | Mechanical interlock for 2 회로 차단기 (dual power switching) |
| HLF‑1SV | External rotary handle | Panel mounted operating handle, with door interlock |
⚠️ Selection & 설치 제한 (비판적인)
- One NV125-SV breaker can be fitted with max. one built-in accessory module only. SHT + ALAX cannot be installed together.
Option A: ALAX (위치 + fault signal)
Option B: SHT (원격 트리핑)
Option C: UVT (under-voltage protection)
- Built-in accessories occupy space on the right side of breaker. Do not mount breakers side-by-side with zero clearance when fitted with internal accessories (UVT needs extra space).
- Two ordering options:
Breaker pre-fitted with accessories at factory (complete unit order)
Purchase accessory modules separately and assemble on site
- ELCB NV125-SV supports SHT/UVT installation for fire linkage and loss-of-voltage protection; accessories are interchangeable with NF125-SV standard MCCB.
Ordering Examples
NV125-SV 3P 63A + ALAX-03SVU (with switch position & fault alarm contacts)
NV125-SV 3P 63A + SHTA240-03SVU (AC220V remote shunt trip)
Full Model List of Mitsubishi NV125-SV (WS-V ELCB)
Frame AF125, Icu=30kA / Ics=30kA @AC400V; Standard AC type leakage 100/200/500mA adjustable; 3P /4P; 열 자기 여행; dimension W90×H130×D90mm
Naming format: NV125-SV [3P/4P] [Rated Current A]
✅ Rated Current Range (~ 안에)
16에이, 20에이, 25에이, 32에이, 40에이, 50에이, 63에이, 75에이, 80에이, 100에이, 125에이
✅ Full Model Matrix
3피 (3-단계, neutral not switched)
NV125-SV 3P 16A
NV125-SV 3P 20A
NV125-SV 3P 25A
NV125-SV 3P 32A
NV125-SV 3P 40A
NV125-SV 3P 50A
NV125-SV 3P 63A (target model)
NV125-SV 3P 75A
NV125-SV 3P 80A
NV125-SV 3P 100A
NV125-SV 3P 125A
4피 (3-단계 + 중성극, neutral can be disconnected)
NV125-SV 4P 16A
NV125-SV 4P 20A
NV125-SV 4P 25A
NV125-SV 4P 32A
NV125-SV 4P 40A
NV125-SV 4P 50A
NV125-SV 4P 63A
NV125-SV 4P 75A
NV125-SV 4P 80A
NV125-SV 4P 100A
NV125-SV 4P 125A
Derived variants on same WS-V platform
NV125-CV: 경제 버전, Icu=10kA @AC400V
NV125-HV: 높은 차단 용량, Icu=50kA @AC400V
NV125-SEV/HEV: Electronic trip ELCB (electronic protection, long/short time delay available)
Suffix explanation: 1.2.500MA = 100/200/500mA adjustable leakage (standard for China market); 30mA high-speed leakage variant available for personal protection.
Cross-brand Equivalent Reference (Reference target: NV125-SV 3P 63A, AC400V, Icu≥30kA, adjustable leakage 100/200/500mA, 열 자기)
⚠️ 중요 사항: Physical size and accessories are NOT interchangeable; only electrical equivalent. Verify cabinet cutout, wiring and accessory interface for site retrofit. Table based on 63A/3P.
| 상표 | 동등한 모델 | 주요 매개변수 | 비고 |
| Mitsubishi Original | NV125-SV 3P 63A | 3P 63A, Icu=30kA@400V, AC leakage 100/200/500mA adjustable, 열 자기 여행 | Reference unit, WS-V series |
| 슈나이더 | EZD125E 3P 63A Vigi (leakage module) | 3P 63A, Icu=30kA, adjustable residual current | EZD125E + separate Vigi module; split type leakage, not integrated ELCB; 다른 차원 |
| 슈나이더 | NSX100N 3P 63A Vigi | Icu=36kA, 조정 가능한 누출 | NSX higher performance, 더 높은 가격, modular leakage |
| 씨줄 | T2N160 3P 63A RCD | Icu=36kA, adjustable AC residual current | MCCB body + external RCD module, integrated solution Tmax T2N |
| 지멘스 | 3VT8106-1AA03-0AA0 + leakage trip module | 3P 63A, Icu=25kA, optional leakage module | Breaking capacity slightly lower than Mitsubishi; check short-circuit capacity |
| CHNT | NM1LE-125S/3P 63A | 3P 63A, Icu=35kA, leakage 100/200/500mA adjustable | Main domestic alternative, integrated ELCB, 열 자기, similar mounting size |
| 맛있는 | CDM1LE-125/3P 63A | 3P 63A, Icu=35kA, multi-level adjustable leakage | 국내 대안, 125AF frame, 통합 누출 |
| 사람들 전기 | RMM1LE-125/3P 63A | 3P 63A, Icu=35kA, 조정 가능한 누출 | 경제적인 국내 대안 |
Key Differences for Replacement Engineering
- Leakage construction: Mitsubishi NV125-SV is integrated built-in leakage. Schneider NSX/EZD and ABB Tmax mostly adopt separate external leakage modules, more failure points.
- 차단 용량: NV125-SV Icu=30kA; Icu cannot be downgraded during replacement, risk of breaker failure under bus short-circuit.
- 액세서리 호환성: Mitsubishi AX/AL/SHT/UVT are right-side clip-on modules; Schneider/ABB accessories are independent modules. Mitsubishi old accessories cannot be reused, new accessories must be purchased for retrofit.
- 극 선택: 3P only switches 3 live conductors, neutral passes through. Select 4P if neutral protection is required.
- 누설 유형: Above are all AC type, suitable for standard power frequency loads. For VFD-heavy systems, A/F type leakage is recommended.
Mitsubishi Legacy to WS-V Upgrade
Old NV125-SW / NV125-SVL (old WS series) → NV125-SV (WS-V)
Same outer dimension, mounting hole compatible
Higher short-circuit breaking capacity (old 25kA upgraded to 30kA)
Updated accessory model: old SW accessories incompatible with SV; must use -03SVU series (도끼-03SVU / 알-03SVU)
Recommended Replacement Priority
- Cabinet space & accessory reuse preferred: Original Mitsubishi NV125-SV
- Import equivalent upgrade: ABB T2N160 / Schneider NSX100N Vigi
- Cost-effective domestic engineering replacement: CHNT NM1LE-125S / Delixi CDM1LE-125
NV125-SV 3P 63A Replacement Retrofit Risk Checklist
범위: Replace Mitsubishi NV125-SV 3P 63A (ELCB, AC400V, Icu=30kA, 100/200/500mA adjustable leakage) with identical model, imported equivalent (ABB/Schneider/Siemens) or domestic alternative (CHNT/Delixi/People). Used for ECN, technical briefing, incoming inspection and pre-commissioning check. ✅=Pass; ❌=Fail; ⚠️=Requires confirmation/rectification
- Electrical Parameter Verification (Highest Priority, No Icu Downgrade)
| 아니요. | 항목 확인 | 요구 사항 / 표준 |
| 1 | 정격 전류 입력 | New device ≥ 63A and matches circuit design; continuous load ≤0.8×In |
| 2 | Pole Consistency | Original 3P must use 3P; if changing to 4P for neutral switching, rework wiring & cabinet cutout |
| 3 | Rated Voltage Ue | New device rated voltage ≥ AC400V, compatible with system voltage |
| 4 | Short-circuit Breaking Icu@AC400V | New Icu ≥ 30kA (must not be lower than original NV125-SV 30kA), risk of breaker damage under bus short-circuit |
| 5 | IC (서비스 차단 용량) | ≥30kA, same as Icu, allows reclose after short-circuit event |
| 6 | Earth Leakage Protection Type | 교류형 (or A/F type); adjustable leakage range 100/200/500mA must be retained |
| 7 | 누설 작동 시간 | 0.04초 이하 (고속); separately verify for 30mA personal protection version |
| 8 | Thermal-Magnetic Trip Characteristic | 초과 적재 / short-circuit trip curve must match original coordination; electronic trip requires setting verification |
| 9 | Short-circuit Selectivity | Recheck selectivity coordination with upstream and downstream protective devices |
⚠️ Red Line Rule①: Do NOT energize any replacement unit with Icu <30그만큼. Leave panel de-energized rather than downgrade breaking capacity.
- 기계적인 설치 & Dimension Check
| 아니요. | 항목 확인 | 요구 사항 / 표준 |
| 1 | 장착 컷아웃 | Compare original NV125-SV (W90×H130×D90mm) with cabinet cutout; re-cut or use adapter plate if dimension mismatch |
| 2 | 장착 유형 | TH35 DIN rail or panel bolt mounting compatible with original bracket |
| 3 | 배선 공간 | In/out terminal clearance sufficient for cable stripping and crimping (meet minimum cable bending radius) |
| 4 | Phase Clearance | Creepage & air clearance between phase terminals comply with new device specification |
| 5 | 열 방출 | Panel spacing meets thermal requirement; no tight side-by-side mounting with internal accessories fitted (UVT especially) |
| 6 | Handle / Door Cutout | Door opening and handle projection match new device; confirm if external rotary handle needs replacement |
| 7 | Torque for Terminals | Tightening torque follows manufacturer manual; conductor cross-section adequate, crimping secure |
⚠️ Red Line Rule②: Do not force oversized cutout or suspend breaker without proper support. Use manufacturer drawing or adapter plate.
- Accessory Compatibility Check (High Risk, Frequently Missed)
| 아니요. | 항목 확인 | 요구 사항 / 표준 |
| 1 | Accessory Interface | Original AX-03SVU / 알-03SVU / SHTA/D / UVTN/S cannot be fitted to other brands; purchase new accessories matching new breaker brand |
| 2 | 경보 / Position Signal | Re-select equivalent ALAX accessory for new breaker and rewire secondary circuit |
| 3 | Shunt Trip SHT | Reconfigure remote trip, verify AC/DC voltage rating |
| 4 | Under Voltage Trip UVT | Reconfigure UVT; verify trip characteristic (동기식 / non-synchronous) against load type |
| 5 | Mechanical Interlock MI | Dual power interlock must be matched accessory from new brand; interlocks from different brands are incompatible |
| 6 | 단자 커버 / Lockout | Fit TC/LC protective accessories as per new device spec |
| 7 | External Leakage Module (Import Split Type) | Schneider NSX/EZD, ABB T2N use separate leakage module; confirm module installed and wired correctly |
⚠️ Red Line Rule③: Do NOT reuse old Mitsubishi accessories on new breakers. Mismatched assembly causes poor contact, loss of alarm or protection function.
- 기본 & Secondary Wiring Check
| 아니요. | 항목 확인 | 요구 사항 / 표준 |
| 1 | 주회로 배선 | Phase sequence matches busbar, terminals fully tightened |
| 2 | Neutral Handling | 3P version neutral passes through unswitched; rewire neutral if replaced with 4P |
| 3 | Zero-sequence CT / Leakage Transformer | Integrated ELCB has built-in CT, no external CT needed; check CT cable passing direction for split leakage module |
| 4 | Secondary Control Wires | AX/AL contacts to PLC / indicator circuit; verify contact type (1a1b) and voltage rating |
| 5 | Shunt / UVT Coil Wiring | SHT is short-time energized, continuous power forbidden; UVT coil voltage matches supply |
| 6 | Wiring Marking | Phase labels and accessory terminal numbers clear and consistent with drawing |
| 7 | 터미널 토크 | Follow manufacturer torque specification to avoid overheating / 느슨한 연결 |
⚠️ Red Line Rule④: SHT coil is short-time energized, continuous supply burns coil. UVT will not auto-close after voltage recovery; manual closing required in commissioning procedure.
- Pre-commissioning Test & 수락
| 아니요. | 항목 확인 | 요구 사항 / 표준 |
| 1 | 절연 테스트 | Phase-to-phase / phase-earth insulation resistance meets requirement; disconnect secondary / electronic accessories before test |
| 2 | 누설 테스트 (TEST Button) | Press red TEST button; breaker must trip reliably to validate leakage protection |
| 3 | Leakage Threshold Verification | Test tripping at 100/200/500mA if site conditions permit |
| 4 | 초과 적재 / Short-circuit Simulation | Verify thermal-magnetic trip if test available; otherwise confirm factory trip characteristic |
| 5 | Accessory Function Test | Test ALAX alarm contact, SHT remote trip, UVT under-voltage trip one by one |
| 6 | Mechanical Operation | 수동 ON/OFF 원활, no jamming, no missing phase |
| 7 | 무부하 & Load Trial Run | Close breaker under no-load first; then energize load, monitor temperature and nuisance tripping |
| 8 | Earthing Continuity | Equipment and cabinet protective earth secure |
| 9 | Setting Record Filing | Document new breaker rating, leakage setting and accessory configuration |
⚠️ Red Line Rule⑤: Do NOT put into formal operation before passing TEST button leakage verification. ELCB without working leakage protection functions only as ordinary MCCB, no personnel protection.
- Inapplicable Conditions & Forbidden Operations
| 대본 / 작업 | Judgement |
| Frequent ON/OFF cycling | ⚠️ Thermal-magnetic trip not suitable for high cycle rate; use motor protector or add contactor |
| Heavy corrosion, 먼지, 응축 | ❌ Standard model not suitable; IP rated enclosure + anti-condensation heater required |
| VFD & servo heavy harmonic environment | ⚠️ AC type may nuisance trip; upgrade to A/F type leakage or surge-resistant model |
| Replace breaker with upstream live | ❌ Live working prohibited. 전원 끄기, test dead, lockout-tagout (마음) 필수의 |
| Reset immediately after leakage trip without investigation | ❌ Do not repeatedly reclose; troubleshoot insulation/earth fault first |
| Replace ELCB with standard MCCB (NF) | ❌ Loss of earth leakage protection, strictly prohibited |
| Replace with lower Icu rating | ❌ Not allowed |
접촉기,회로 차단기,감지기,인코더,PLC,변환기





















NH42-63-318x560.png)



