ABB TTH200-Y0 Temperature Transmitter - 접촉기,회로 차단기,감지기,인코더,PLC,변환기

위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

ABB TTH200-Y0 Temperature Transmitter - 접촉기,회로 차단기,감지기,인코더,PLC,변환기

감지기/전기 같은/

ABB TTH200-Y0 Temperature Transmitter

TTH200: ABB TTH200 series DIN-rail mount temperature transmitter (Head Mount / DIN rail dual mounting, HART 프로토콜) Y0: 버전 / 구성 코드, stands for without local display, basic model, HART 4-20mA output, DIN 레일 장착. 시리즈 포지셔닝: The TTH200 is a 2-wire HART temperature transmitter from ABB. It accepts RTD, TC, mV and resistance signals, ...

  • 제품 세부정보

TTH200: 씨줄 TTH200 series DIN-rail mount temperature transmitter (Head Mount / DIN rail dual mounting, HART 프로토콜)

Y0: 버전 / 구성 코드, stands for without local display, basic model, HART 4-20mA output, DIN 레일 장착.

시리즈 포지셔닝: The TTH200 is a 2-wire HART temperature transmitter from ABB. It accepts RTD, TC, mV and resistance signals, and serves as a replacement for the discontinued TTF200.

주요 사양

전원공급장치: 12~42V DC, 2-철사

산출: 4-20mA + 수사슴 5/7

Sensor Inputs:

RTD: Pt100, Pt1000, Cu50, 등. Supports 2/3/4-wire connection

TC: 비,이자형,제이,케이,엘,N,아르 자형,에스,티,U and other thermocouple types

Millivolt mV, resistance signal

정확성: RTD typical ±0.05℃; Thermocouple typical ±0.08℃

설치: DIN 레일 마운트; also can be installed inside sensor connection head (head mount)

주택: 플라스틱 하우징, IP20 (under DIN rail installation)

구성: HART communicator, ABB Device Manager, DTM/FDT software

Suffix code Y0: No local LCD display, basic version without extra hardware options.

비교: Y1 = with LCD display

일반적인 응용 분야

Industrial temperature measurement for HVAC, 화학적인, power and pharmaceutical industries. Used for temperature acquisition on pipelines and tanks, connected to DCS or PLC, paired with Pt100, K-type thermocouples.

모델 선택 & 대사

  1. 같은 시리즈: TTH200-Y1 (디스플레이 포함)
  2. Legacy model replacement: TTF200 → TTH200
  3. 국내 대안: HART DIN rail temperature transmitters (such as Chongqing Chuanyi, Shangrun HART models)

일반적인 문제 해결

  1. 출력 없음: Verify loop voltage ≥12V, check 2-wire wiring for short circuit and polarity
  2. Fixed at 4mA: 센서 개방 회로 / not connected, mismatched configured sensor type (예를 들어. Pt100 configured while K thermocouple wired)
  3. 온도 드리프트: Check RTD wiring (4-wire preferred), cold junction compensation setting for thermocouple
  4. HART 통신 실패: 250Ω resistor inserted into loop, avoid high-power interference, verify HART address

예비 부품 & 구매 참고 사항

Complete order number is not limited to TTH200-Y0; extra codes for sensor type, explosion protection are required

Explosion-proof versions have separate suffixes; TTH200 has intrinsically safe Ex ia variants, confirm explosion-proof requirement before purchase

HS code reference: 90268000 (온도 트랜스미터, industrial measuring instrument)

ABB TTH200 Complete Ordering Selection Table

Order model structure: TTH200 [Explosion-proof code] [Display code] + [Additional options]

예: TTH200-Y0 = Non-explosion proof, without LCD; TTH200-S1-Y0 = NEPSI intrinsically safe, without LCD

  1. 폭발 방지 / Certification Code (1st suffix segment)
암호설명애플리케이션
Y0Non-explosion proof, 표준형 (your current model)Non-hazardous area, control room DIN rail mounting
E1ATEX intrinsically safe Ex ia IIC T6Zone0/1/2, European explosion protection
E2ATEX non-sparking Ex nA / Ex ec IIC T6Zone2 only
H1IECEx intrinsically safe Ex ia IIC T6International explosion-proof certificate, 해외 프로젝트
S1NEPSI intrinsically safe Ex ia IIC T6 GaWidely used in domestic chemical industry with Chinese explosion-proof certificate
L1FM Intrinsically Safe (북아메리카)North America Class I Div.1
L2FM Non-incendive (북아메리카)North America Class I Div.2
R1CSA Intrinsically Safe (캐나다)Canada projects
R2CSA Non-incendive (캐나다)Canada Class I Div.2
P2EAC-Ex + Russian metrology certificationRussian federation explosion-proof projects
G1Russian metrology certification (non-explosion proof)Russian non-hazardous area
G3Kazakhstan metrology certificationKazakhstan non-hazardous area
T2Kazakhstan EAC-Ex + metrology certificationKazakhstan explosion-proof projects
M5Belarus metrology certificationBelarus non-hazardous area
U2Belarus EAC-Ex + metrology certificationBelarus explosion-proof projects
  1. Display Code
암호설명
Y0LCD 디스플레이 없음 (basic model, preferred for DIN rail installation)
Y1With local LCD display, for on-site temperature reading and alarm check

✅ Combination example: TTH200-Y0 (non-explosion proof no display); TTH200-E1-Y1 (ATEX intrinsically safe + LCD)

  1. 주택 / Mounting Accessory Options (added separately, incompatible with some explosion-proof models)
암호Housing DescriptionIP 등급비고
H1Aluminum head housing 80×75×57mm, 2×M16 cable glandsIP65Sensor head mount
H2Polyester housing 75×80×55mm, 2×M16IP65부식 방지
H3Polycarbonate housing 80×82×55mm, 2×M16IP65비용 효율적
H6Aluminum large housing 175×80×57mm, 1×M16+2×M20IP65Large enclosure
H7Polyester large housing with separate terminal blockIP65Split terminal
H8Polyester large housing without separate terminal blockIP65Compact large housing
DIN rail kit3KXT091230L0001 (10 세트) / 3KXT091230L0002 (1 세트)DIN35 rail mounting bracketOptional for Y0/Y1 DIN rail installation

⚠️ Note: Some explosion-proof models cannot be matched with H1/H2/H3 head housing options. Confirm before order.

  1. Functional Additional Options
암호Option Description
CSSIL2 compliance declaration (for safety instrumented SIL2 loop)
  1. Supported Sensor Input Selection (configured in software, stated in order remarks)

RTD Resistance Temperature Detector

Pt100(IEC60751 0.00385)【Default】、Pt100(JIS)、Pt10、Pt50、Pt200、Pt500、Pt1000;Ni50/Ni100/Ni120/Ni1000;Cu10/Cu100;Resistance signal 0~500Ω / 0~5000Ω; support 2/3/4-wire

Thermocouple TC

케이、제이、티、이자형、N、아르 자형、에스、비、엘(DIN43710)、유、기음、디;mV signal: -125~125mV / -125~1100mV

Cold junction compensation: 내장(기본) / external cold junction / no compensation (B-type thermocouple recommended no compensation)

  1. 일반 기술 사양
목매개변수
규약HART5 / 하트7, 2-wire 4-20mA
전원공급장치12~42V DC
정확성RTD typical ±0.05℃; TC typical ±0.08℃
주변 온도Transmitter body: -40~+85℃; Explosion-proof T6 version max 56℃
나무르NE89, NE107 (결함 경보)
안전 수준SIL2 capable (with CS option)
Configuration ToolHART communicator, ABB Device Manager, FDT/DTM
  1. Complete Ordering Examples
  2. TTH200-Y0

Non-explosion proof, no LCD, DIN 레일 장착; configured Pt100, range 0~200℃

  1. TTH200-S1-Y1+CS

NEPSI intrinsically safe, LCD 포함, SIL2 declaration; K-type thermocouple, built-in cold junction compensation

  1. TTH200-E1-Y0+H2

ATEX intrinsically safe, no LCD, polyester IP65 head housing, head mount Pt100

  1. 선택 참고 사항
  2. Y0/Y1 are display codes, NOT explosion-proof codes, a common confusion. For TTH200-Y0, Y0=no display; the preceding Y means non-explosion proof.
  3. DIN rail installation only needs transmitter body + DIN rail clip kit, no H1/H2 head housing. H-series housings are used for sensor head mounting inside temperature probe junction box.
  4. Confirm hazardous area classification (Zone/Div) and temperature class T6 for explosion-proof models; NEPSI S1 version is preferred for domestic hazardous projects.
  5. Measurement range, sensor type and TAG are configuration parameters, submit in order remarks for factory pre-configuration; or configure on-site via HART communicator after delivery.
  6. Cross Series Replacement Reference

TTH200: Single channel, no sensor drift monitoring (이 모델)

TTH300: Dual channel, support sensor redundancy and drift monitoring, 더 높은 성능

Legacy TTF200: 단종, direct replacement by TTH200-Y0/Y1

ABB TTH200 Full Model List (Head Mount / DIN Rail Dual Purpose Temperature Transmitter)

Model structure: TTH200-[Explosion-proof code]-[Display code] [+Additional options]

베이스 시리즈: TTH200 (single channel, HART 4-20mA); TTH300 (dual channel) in same family listed at the end for distinction

  1. TTH200 Base Model List (Combination of Explosion Protection & 표시하다)
전체 모델Explosion Certification표시하다설명
TTH200-Y0Non-explosion proofWithout LCDNon-hazardous area, DIN 레일 / head mount, your target model
TTH200-Y1Non-explosion proofWith LCDNon-hazardous area, local temperature reading
TTH200-S1-Y0NEPSI intrinsically safe Ex ia IIC T6Without LCDDomestic chemical hazardous area, Chinese explosion-proof certificate
TTH200-S1-Y1NEPSI intrinsically safe Ex ia IIC T6With LCDDomestic hazardous area + local display
TTH200-E1-Y0ATEX intrinsically safe Ex ia IIC T6Without LCDEU ATEX intrinsically safe, Zone0/1
TTH200-E1-Y1ATEX intrinsically safe Ex ia IIC T6With LCDATEX intrinsically safe + LCD
TTH200-E2-Y0ATEX Ex nA / Ex ec IIC T6Without LCDATEX non-sparking, Zone2 only
TTH200-E2-Y1ATEX Ex nA / Ex ec IIC T6With LCDZone2 explosion-proof + 표시하다
TTH200-H1-Y0IECEx intrinsically safe Ex ia IIC T6Without LCDInternational IECEx certificate, overseas project
TTH200-H1-Y1IECEx intrinsically safe Ex ia IIC T6With LCDIECEx intrinsically safe + LCD
TTH200-L1-Y0FM intrinsically safe Class I Div.1Without LCDNorth America FM intrinsically safe
TTH200-L1-Y1FM intrinsically safe Class I Div.1With LCDNorth America FM intrinsically safe + 표시하다
TTH200-L2-Y0FM Non-incendive Class I Div.2Without LCDNorth America Div.2
TTH200-L2-Y1FM Non-incendive Class I Div.2With LCDNorth America Div.2 + 표시하다
TTH200-R1-Y0CSA intrinsically safe Class I Div.1Without LCDCanada CSA intrinsically safe
TTH200-R1-Y1CSA intrinsically safe Class I Div.1With LCDCanada CSA intrinsically safe + LCD
TTH200-R2-Y0CSA Non-incendive Class I Div.2Without LCDCanada CSA Div.2
TTH200-R2-Y1CSA Non-incendive Class I Div.2With LCDCanada CSA Div.2 + 표시하다
TTH200-P2-Y0EAC-Ex Russian explosion-proof + metrology certWithout LCDRussian federation explosion-proof project
TTH200-P2-Y1EAC-Ex Russian explosion-proof + metrology certWith LCDRussian explosion-proof + 표시하다
TTH200-G1-Y0Russian metrology cert (non-explosion proof)Without LCDRussian non-hazardous area
TTH200-G1-Y1Russian metrology cert (non-explosion proof)With LCDRussian non-hazardous area + LCD
TTH200-G3-Y0Kazakhstan metrology cert (non-explosion proof)Without LCDKazakhstan non-hazardous project
TTH200-G3-Y1Kazakhstan metrology cert (non-explosion proof)With LCDKazakhstan non-hazardous + LCD
TTH200-T2-Y0Kazakhstan EAC-Ex + metrology certWithout LCDKazakhstan explosion-proof project
TTH200-T2-Y1Kazakhstan EAC-Ex + metrology certWith LCDKazakhstan explosion-proof + LCD
TTH200-M5-Y0Belarus metrology cert (non-explosion proof)Without LCDBelarus non-hazardous area
TTH200-M5-Y1Belarus metrology cert (non-explosion proof)With LCDBelarus non-hazardous + LCD
TTH200-U2-Y0Belarus EAC-Ex + metrology certWithout LCDBelarus explosion-proof project
TTH200-U2-Y1Belarus EAC-Ex + metrology certWith LCDBelarus explosion-proof + LCD
  1. Additional Options (appended after any model with `+`)
접미사 코드설명
+CSSIL2 compliance declaration for SIL2 safety loops
0Aluminum head housing IP65, 2×M16 cable glands
0Polyester head housing IP65, 2×M16 cable glands, 부식 방지
0Polycarbonate housing IP65, 2×M16 cable glands
0Aluminum large housing IP65, 1×M16+2×M20
0Polyester large housing with separate terminal block
0Polyester large housing without separate terminal block

Example complete order number: `TTH200-S1-Y0+CS+H2`

의미: NEPSI intrinsically safe, 디스플레이 없음, SIL2 declaration, polyester IP65 head housing

III. TTH / TTF Family Comparison (Avoid Selection Mistakes)

모델 시리즈채널버스특징
TTH200하나의HART 4-20mAHead / DIN rail dual mount, no sensor drift monitoring, this series
TTH300듀얼수사슴 / Profibus PA / FFDual sensor input, support sensor redundancy & drift monitoring
TTF200하나의수사슴Field mount integral housing transmitter (not head module), legacy discontinued, replaced by TTH200
TTF300듀얼수사슴 / 아빠 / FFField housed dual channel temperature transmitter
TTF300-W듀얼WirelessHARTWirelessHART field temperature transmitter
  1. Common Technical Features of TTH200 Series
  2. Universal input: RTD / TC / 오 / mV, configured in software, not coded in model number, state in order remarks
  3. 2-철사: 12~42VDC, 4-20mA+HART5/HART7
  4. NAMUR NE89, NE107 fault alarm
  5. Two mounting forms: DIN 레일 (transmitter module only); Sensor head mount (transmitter + H-series housing kit)
  6. Purchasing Remarks

Y0/Y1 always as the last segment: Y0 no display, Y1 with LCD; preceding code for explosion-proof / regional certification

H-series housing is additional option, not part of base model; H housing not required for DIN rail installation

실(CS) is compliance declaration without hardware modification; add suffix `+CS` for SIL2 safety loop application

범위, 센서 유형, TAG are configuration parameters, not embedded in model code, add to order remarks for factory pre-configuration

이전:

다음:

답장을 남겨주세요