슈나이더 SXWASPSBX10002 BMS 네트워크 컨트롤러

EcoStruxure Building (SpaceLogic AS-P-NLS) Building Automation Server (BMS Network Controller) with Secure Boot. Designed for HVAC, 조명, 냉각수 & heat source control, alarm management, trend logging and protocol gateway applications. ✅ Model Code Definition AS-P: SpaceLogic Automation Server Premium (high-end automation server) NLS: N = No LON bus; L = Zigbee wireless support; 에스 ...

  • 제품 세부정보

EcoStruxure Building (SpaceLogic AS-P-NLS) 건물 오토메이션 섬기는 사람 (BMS Network 제어 장치) with Secure Boot. Designed for HVAC, 조명, 냉각수 & heat source control, alarm management, trend logging and protocol gateway applications.

✅ Model Code Definition

AS-P: SpaceLogic Automation Server Premium (high-end automation server)

NLS: N = No LON bus; L = Zigbee wireless support; S = Secure Boot firmware verification

비교: AS-P-NL (SXWASPXXX10002) without Secure Boot; AS-P-NLS equipped with anti-tampering firmware authentication.

📌 Hardware Ports

2 × RJ45 10/100 Mbps Ethernet (LAN1/LAN2, dual-port network isolation supported)

2 × RS485 field buses (M-Bus, Modbus RTU compatible)

1 × I/O Bus for SpaceLogic I/O expansion modules

1 × USB Device (프로그램 다운로드 & 시운전)

1 × USB 호스트 (USB storage, Zigbee wireless adapter)

📋 핵심 기술 사양

전원공급장치: 24 VDC

Max power consumption: 10 여

메모리: 512 MB RAM / 4 GB 플래시

인클로저 등급: IP20, DIN 레일 장착

치수: 90(여) × 114(시간) × 64(디) mm

순중량: 0.321 kg

작동 온도: 0 ~ +50 ℃; 보관온도: -20 ~ +70 ℃

습기: ≤95% RH, 비응축

🧩 Protocols & 핵심 기능

BACnet IP, BACnet/SC (Secure Connect), Modbus TCP/RTU

Zigbee wireless device integration

Control logic execution, trend logging, alarm management, user access control

Standalone operation or zone controller under upper-level servers; acts as multi-protocol gateway

Secure Boot: prevents firmware tampering, ideal for high-security projects (병원, 데이터 센터)

⚠️ Product Lifecycle (Critical Information)

End of Order (EOO): 31 Dec 2026

End of Service (EOS): 31 Dec 2029

권장 교체 모델: SXWASP3XX10001 (AS-P-3 V3 New Generation)

Upgrade highlights for AS-P-3: Gigabit Ethernet port, 3 RS485 ports, dual USB Host ports, 더 높은 성능, fully compatible with EcoStruxure toolchain.

📎 Matching Accessories

TB-ASP-W1: Terminal base

PS-24V: 24 VDC 전원 공급 장치

Zigbee USB adapter, SXW series I/O expansion modules

📝 Quick Selection Comparison Table

부품 번호Short NameSecure BootLON BusZigbee
SXWASPSBX10002AS-P-NLS예아니요예
SXWASPXXX10002AS-P-NL아니요아니요예
SXWASPSBX10001AS-P-S예예아니요

Migration Guidelines: AS-P-NLS (SXWASPSBX10002) → AS-P-3 (SXWASP3XX10001)

Core Tool: Device Administrator – Convert backup set server type (do NOT restore backup directly). Minimum EBO version requirement: EBO 7.0 또는 나중에. Older EBO versions cannot recognize AS-P-3.

전제조건: Offline full backup, field trial first, scheduled downtime, rollback plan prepared.

  1. 프로그램 마이그레이션 (EBO Project, 제어 논리, Scripts, Licenses)
  2. Backup & Conversion Workflow (Most Critical Step)
  3. Perform a full online backup of the legacy AS-P-NLS (including control programs, trends, 경보, permissions, gateway settings, TGML graphics). Never restore this backup directly onto AS-P-3.
  4. Open the backup set in Device Administrator, run the Convert backup set server type function to change the target device type from AS-P to AS-P-3. Only converted backups can be downloaded to the new controller.
  5. Most control logic, FBD, ST programs, schedules, alarm strategies and trend configurations remain fully compatible after conversion, no program rewriting required.
  6. Always open the converted project in WorkStation and run a full compile check to eliminate errors and warnings.
  7. Key Compatibility Checks

✅ Standard HVAC, BACnet and Modbus function blocks are fully compatible.

⚠️ Custom third-party drivers, user-defined C-scripts and special driver packages must be validated for AS-P-3 compatibility; older drivers may not work.

Zigbee Compatibility: The original Zigbee USB adapter works on AS-P-3, but the USB port path changes (유산: 1 USB 호스트; 새로운: 2 USB Host ports). Update the USB device path inside the project.

Secure Boot: Certificates and BACnet/SC credentials are retained after conversion; re-export and validate certificates after migration.

❌ Incompatibility Risks:

  1. Legacy AS-P exclusive system variables and status objects
  2. Hardcoded USB/COM port numbers in TGML graphics
  3. TLS version mismatch: AS-P-NLS uses TLS 1.0 while AS-P-3 defaults to TLS 1.3. Email alerts and web access will fail due to handshake errors; adjust mail server TLS settings accordingly.

✅ License Note: The original AS-P software license cannot be migrated directly. Apply for license re-binding with the new AS-P-3 serial number in advance via 슈나이더 license transfer process.

  1. Post-Migration Testing Items
  2. Full project compilation, resolve all errors & 경고
  3. Offline simulation of control sequences, PID loops and interlocks
  4. Verify alarm forwarding, trend recording and event logging
  5. Test TGML graphic access and point read/write permissions
  6. I/O Bus & I/O Mapping (Top Risk Area – Hardware Topology Changed)

Legacy AS-P uses TB-ASP-W1 terminal base with different I/O Bus addressing and power budget. AS-P-3 is an integrated unit without a separate base.

  1. I/O Bus Address Rule Change (Most Common Failure)

Legacy AS-P: Server occupies I/O Bus address 1

AS-P-3: Server is fixed at I/O Bus address 2. I/O modules start from address 3, 최고 32 노드 (최대 31 I/O devices).

Direct migration will cause I/O address offset, module offline and wrong point readings.

Two solutions:

  1. Rearrange the physical I/O Bus topology, reassign addresses following AS-P-3 rules, then cross-check I/O mapping table in the project (추천).
  2. Modify each I/O module’s bus address inside the project to match physical wiring.

Wiring rule: Install AS-P-3 on the far left of the DIN rail; I/O modules extend rightwards. 위치 1 is reserved and unavailable.

  1. I/O Bus Power Budget

Legacy AS-P base has limited power output; AS-P-3 built-in I/O Bus power: 맥스 20 여. Add an external 30 W I/O bus power supply if the total power consumption exceeds the limit, otherwise modules will drop offline randomly.

Calculate total module power consumption before migration.

  1. I/O Mapping Validation

DI/DO/AI/AO channel definitions remain unchanged; only the I/O Bus address is updated.

Verify every item after download: module number, bus address, channel number, forced values, channel inversion and filter parameters.

SXW series I/O modules are fully interchangeable between legacy AS-P and AS-P-3; no hardware replacement needed.

III. 네트워크 구성 (Ethernet Ports, RS485, 백넷, 게이트웨이)

  1. Ethernet Port Comparison

Legacy AS-P-NLS: 2 × 10/100 Mbps LAN (LAN1/LAN2)

AS-P-3: 포트1 (10/100/1000 기가비트), Port2 & Port3 (10/100 Mbps). 3 ports total, supports RSTP and isolated private subnets.

Major Pitfall: Port numbering and subnet roles have changed.

  1. IP Planning: Keep the same Device Name and BACnet Device ID to avoid reconfiguration on upper BMS and third-party integration systems.
  2. Port Role Reassignment:

Port1 = Main WAN (BMS backbone network)

Port2 / Port3 = WAN or Private Network (구성 가능)

All static routes, BACnet IP interfaces and gateway bindings previously assigned to LAN1/LAN2 must be re-bound to the new AS-P-3 port numbers, otherwise BACnet IP communication and cross-subnet routing will break.

  1. BACnet Settings

BACnet IP and BACnet/SC protocols are compatible. Certificates are preserved after backup conversion, but TLS 1.3 is enabled on AS-P-3; BACnet/SC clients must support TLS 1.3.

Re-scan BACnet routers, BBMD and external device subscriptions after migration.

  1. RS485 Serial Ports (COM Ports)

Legacy AS-P: COM A, COM B (2 RS485 ports)

AS-P-3: COM A, COM B, COM C (3 RS485 ports)

모드버스 RTU / MS/TP programs referencing COM A/B do not require editing; only re-terminate field wiring to the new terminal block.

Bus biasing and termination resistors: AS-P-3 has different built-in biasing characteristics. Retest bus waveform and adjust termination resistors on long-distance MS/TP buses to eliminate intermittent communication loss.

  1. Additional Network Services

Recheck NTP, DNS, static routes, VPN and SNMP settings; re-bind all network objects to the correct physical ports.

  1. 하드웨어, 배선 & Installation Differences (Field Implementation)
  2. 전원공급장치: Legacy AS-P requires separate PS-24V power module; AS-P-3 has integrated power supply, directly powered by 24 VAC / 24~30 VDC. The external PS-24V can be removed from the cabinet.
  3. Mechanical Size: Legacy AS-P + 베이스 + 전원 공급 장치; AS-P-3 integrated body matches the overall size of legacy AS-P plus PS-24V. DIN rail mounting position is interchangeable, but terminal layout differs – do not reuse existing pre-wired terminal plugs; re-crimp all field wires.
  4. USB 인터페이스: 유산: 1 Mini-B debug + 1 USB-A Host; 새로운: 1 USB-C debug + 2 USB-A Host. After plugging the Zigbee adapter into the new USB Host, update the USB instance path inside the project.
  5. 열 방출: AS-P-3 has higher power consumption. Install horizontally on DIN rail with sufficient top & bottom ventilation; avoid dense stacking.
  6. Step-by-Step Migration Procedure (Minimize Downtime Risk)
  7. Before shutdown: Create full project backup, export I/O mapping table, network parameters, BACnet device list, Modbus point list and Zigbee device inventory; keep hard copies.
  8. Upgrade EBO WorkStation to V7.0+, and install the matching Device Administrator version.
  9. Convert the backup to AS-P-3 format, compile the project and complete offline simulation testing.
  10. Replace the controller hardware inside the cabinet, rewire I/O Bus, 24V power, RS485 buses, Ethernet and Zigbee adapter.
  11. Flash the latest firmware to AS-P-3, import the converted backup and activate the software license.
  12. Power up step by step: First I/O Bus, then RS485 field buses, finally the backbone Ethernet network.
  13. Full point verification: I/O channels, field bus communication, 백넷, 모드버스, 경보, trends, graphics and Zigbee sub-devices.
  14. 24-hour continuous trial run. Keep the original AS-P-NLS as rollback spare hardware; do not remove it immediately.
  15. Common Post-Migration Troubleshooting
  16. I/O modules offline: Wrong I/O Bus address (server address changed from 1 에게 2), incorrect physical topology, or total bus power exceeds 20 W limit.
  17. Intermittent Modbus/MS/TP communication: Improper bus biasing or termination resistors, or COM port binding mismatch.
  18. Upper BMS cannot read BACnet points: WAN/Private subnet misconfiguration, BBMD error or duplicate BACnet Device ID.
  19. Zigbee devices offline: USB Host instance path not updated in the project.
  20. Email notification failure: TLS version incompatibility (mail server does not support TLS 1.3).
  21. Backup restore error: Direct restore without running the Convert backup set server type tool.

Full Model List of the Series

1st Generation AS-P (단종, with TB-ASP-W1 Base)

Standard HVAC Models

Short Model부품 번호LON BusZigbeeSecure Boot비고
AS-PSXWASPXXX10001예아니요아니요Basic model with LON
AS-P-SSXWASPSBX10001예아니요예Secure Boot + LON
AS-P-NLSXWASPXXX10002아니요예아니요No LON, Zigbee wireless
AS-P-NLSSXWASPSBX10002아니요예예No LON + Zigbee + Secure Boot
AS-P-SBASXWASPSBX10A01예아니요예BAA Buy American Act compliant

UL864 Smoke Control (SMK) Fire Models

Short Model부품 번호LONZigbeeSecure Boot
AS-P-SMKSXWASPXXX1S001예아니요아니요Smoke control firmware
AS-P-NLS-SMKSXWASPSBX1S002아니요예예Smoke control + Zigbee + Secure Boot

Terminal Bases (필수 액세서리)

  1. TB-ASP-W1: SXWTBASW110002 (Standard projects)
  2. TB-ASP-W1-BAA: SXWTBASW110A02 (BAA-compliant projects)

2nd Generation AS-P-3 V3 (New Replacement, Integrated Unit, No Base Required)

All models include Secure Boot; EBO V7.0+ required.

Short Model부품 번호LON BusRS485 PortsEthernet Ports레거시 교체
AS-P-3SXWASP3XX10001아니요31 기가비트 + 2 패스트 이더넷AS-P-NL / AS-P-NLS (SXWASPSBX10002)
AS-P-L-3SXWASPL3X10001예21 기가비트 + 2 패스트 이더넷AS-P / AS-P-S (LON retained)

주요 차이점: AS-P-3 has one extra RS485 port; AS-P-L-3 keeps LON bus with one fewer RS485 port.

모델 코딩 분석 (SXWASPSBX10002)

  1. SXWASP = SpaceLogic AS-P Automation Server
  2. 6번째 문자: S = Secure Boot enabled; X = No Secure Boot
  3. 7번째 문자: B = No LON bus; L = LON bus enabled
  4. 8번째 문자: X = No Zigbee; L = Zigbee enabled
  5. 접미사 10001/10002 = Version & compliance variant; S = SMK smoke control firmware

End-of-Life Replacement Mapping Table

  1. SXWASPSBX10002 (AS-P-NLS) → SXWASP3XX10001 (AS-P-3)
  2. SXWASPXXX10002 (AS-P-NL) → SXWASP3XX10001
  3. SXWASPSBX10001 (AS-P-S) → SXWASPL3X10001 (AS-P-L-3, LON retained)
  4. SXWASPXXX10001 (AS-P) → SXWASPL3X10001

Compatible I/O Modules (SXW Series, Interchangeable Between Old & New Servers)

UI-8/AO-V-4, UI-16, DI-16, DO-FC-8, AO-8, RTD-DI-16, 등. No hardware replacement needed; only update I/O Bus address settings.