SEW FSC11B Inverter Special Communication Expansion Module

전체 모델 이름: FSC11B, 재료번호: 18207162 포지셔닝: Special communication expansion module for MOVITRAC® B inverters (SBus/CANopen + RS485). It is mutually exclusive with the FIO11B analog module and cannot be installed on the same inverter at the same time. Interface List X44 (RJ10): RS485 maintenance port Point-to-point commissioning, compatible with MOVITOOLS MotionStudio. Max cable ...

  • 제품 세부정보

전체 모델 이름: FSC11B, 재료번호: 18207162

포지셔닝: Special communication expansion module for MOVITRAC® B 인버터 (SBus/CANopen + RS485). It is mutually exclusive with the FIO11B analog module and cannot be installed on the same inverter at the same time.

Interface List

  1. X44 (RJ10): RS485 maintenance port

Point-to-point commissioning, compatible with MOVITOOLS MotionStudio. Max cable length 3m, for commissioning only.

  1. X45: RS485 terminals (ST11+ / ST12/ GND)

Fixed baud rate 9.6k, 최대 32 역, total bus length ≤200m. Built-in dynamic termination resistor, no external termination resistor allowed.

  1. X46: SBus system bus (CAN 버스, ISO11898 / CAN2.0A/B)

SC11/SC12: SBus channel 1

SC21/SC22: SBus channel 2

핀 7: 24VIO (supplied from the inverter internal 24V)

지원되는 프로토콜: MoviLink, CANopen; 최고 64 노드

On-board DIP switch S1: enable/disable 120Ω termination resistor. Set to ON for the first and last device on the bus, 모든 중간 스테이션에 대해 OFF.

Baud rate vs distance: 125k→320m / 250k→160m / 500k→80m / 1M→40m

적용 가능한 모델

MOVITRAC® B (MC07B series inverters), installed on the front expansion slot of the inverter.

Not compatible with MOVIDRIVE B or other older models; cannot be used for MDX61B, 등.

응용

Multi-inverter SBus (CANopen) networking for synchronization and coordinated motion

PLC control of inverter via CANopen

RS485 network commissioning and parameter read/write

PC 시운전, parameter upload/download and monitoring (RJ10 maintenance port)

Comparison with FIO11B

FSC11B: SBus CANopen + RS485 통신, no analog I/O

FIO11B: Analog input and output (±10V / 4-20엄마), no SBus

Same mounting position; mutually exclusive, cannot be installed together.

주요 사양

Terminal wire gauge: Max 1.5mm² without ferrule; max 1.0mm² with ferrule

Bus cable: 차폐 연선, standard CAN bus cable

프로토콜: MoviLink, CANopen, 꿰매다 proprietary RS485

설치: Front slot of inverter. Must use original fixing screws to ensure EMC grounding.

일반적인 결함

F43: RS485 communication timeout → Check shielding, 종료, 배선, 전송 속도

F36: Missing option / Option mismatch → Confirm it is MC07B, module fully seated

CANopen node cannot go online: Check DIP termination resistor, node address, baud rate P884, P886

교체 노트

FSC11B is the standard option for CANopen communication on MC07B; there is no direct drop-in replacement. For PROFINET, other options such as the DFE series are required.

SEW FSC11B (MC07B) Installation and Commissioning Procedure

전제조건: All operations must be power-off; ESD protection required. FSC11B and FIO11B are mutually exclusive and cannot be fitted together. Only for MOVITRAC B MC07B inverters.

  1. Hardware Installation (전원 끄기)
  2. Cut off power and wait for DC bus discharge (at least 5 분). Open the front cover of the inverter expansion compartment.
  3. 프레임 크기 0 단위: Fit standoffs first. 프레임 크기 1 and above come with standoffs pre-installed. Standoffs ensure high-frequency EMC grounding.
  4. Align FSC11B with the slot and insert straightly. Tighten with the original screws (screws are critical for EMC grounding; do not omit).
  5. Verify the board is fully seated without tilt or poor pin contact. Refit the cover.
  6. DIP switch S1 setting (SBus/CAN bus termination resistor)

First and last inverter on the bus: S1 = ON (120Ω termination enabled)

All intermediate inverters: S1 = OFF (termination disabled)

Only two termination points are allowed on one SBus bus; all other stations must turn termination off, otherwise communication instability and packet loss will occur.

  1. 배선

X44: RJ10 maintenance port, PC commissioning only, cable ≤3m

X45: RS485 (ST11+ / ST12/ GND), SEW proprietary RS485, fixed 9.6k baud

X46: SBus CAN bus (SC11/SC12, SC21/SC22, pin7 24VIO)

Use shielded twisted pair. Shielding should be large-area crimped to inverter shield terminals; shield grounding at both ends of the bus, single-point grounding in the middle is recommended.

SC11/SC12 is one channel; SC21/SC22 is through-wiring for convenient daisy-chain connection.

  1. Recheck wiring for short circuits and misconnection; ensure all node addresses are unique (1~63).
  2. Pre-ower-on Check

Confirm power cable, motor cable and brake resistor wiring are correct

24V control supply healthy, no short circuit on the bus

No FIO11B in the same slot; inverter firmware supports FSC11B

Node ID and baud rate planned and unified for the whole network

  1. Power On and Software Commissioning (MOVITOOLS MotionStudio)
  2. Power on the inverter, connect PC to X44 RJ10 maintenance port (SEW USB-RJ10 commissioning cable)
  3. Launch MOVITOOLS MotionStudio and scan devices. Normally MC07B + FSC11B option will be identified.

If scan fails: Check module seating, 나사, or F36 fault (option detection failure)

  1. Basic motor commissioning (perform motor identification first)

Enter the startup wizard, enter motor nameplate data and run static identification

  1. 매개변수설명
    P884SBus node address (1~63, unique across the network)
    P886SBus baud rate (125k/250k/500k/1M), same for all devices
    P880Control source selection: SBus/CANopen (bus control)
    P881Setpoint source: SBus
    P887SBus communication timeout (triggers F43 on timeout)
  1. PDO Mapping (CANopen)

SEW standard PDO: TPDO (Inverter → PLC: 상태어, actual speed, 현재의, fault code); RPDO (PLC → Inverter: 제어 워드, speed setpoint)

Import the SEW standard EDS file into PLC configuration

  1. Save parameters to the inverter (copy parameters to device). Power cycle once for parameters to take effect.
  2. Bus Network Test
  3. CANopen master scans the bus, all nodes online without heartbeat loss
  4. No-load bus test: PLC sends control word (6 → 0F for enable), inverter ready
  5. Jog test: Speed setpoint sent via bus, motor runs smoothly without oscillation or F43
  6. 다중 모터 동기화: Same sync cycle and baud rate, check timing
  7. Fault simulation: Disconnect bus to verify F43 and safe stop logic trigger at P887 timeout
  8. Common Alarms and Troubleshooting

F36: Missing option / Option recognition error: 모듈이 완전히 장착되지 않음, loose screws, wrong model, 결함이 있는 모듈

F43: SBus/RS485 communication timeout: Wrong termination resistor, 일치하지 않는 전송 속도, duplicate node ID, 열악한 차폐, 버스 단락, 과도한 케이블 길이

Intermittent communication dropouts: Prioritize shielding grounding, DIP termination, separate routing of power and communication cables

  1. Final Handover

Record node ID, baud rate and PDO configuration

Export parameter backup and EDS file for PLC engineer

Label each inverter with node number

SEW Inverter Communication Expansion Module List (Two Main Series: MOVITRAC® B MC07B / MOVIDRIVE® B MDX61B)

메모: MC07B (MOVITRAC B) is general-purpose standard inverter; MDX61B (MOVIDRIVE B) is high-performance inverter. DFE/DFP/DFD/DFI are fieldbus adapters; FSC/FSE are MC07B front-slot expansion boards

  1. MOVITRAC® B (MC07B) Communication Expansion Modules (Front Slot)
모델규약비고
FSC11BSBus / CANopen + RS485The module you are using; CANopen networking, SBus multi-drive linkage, Material No.18207162
FSC12BSBus / CANopen + RS485Upgrade of FSC11B; minor hardware layout and terminal differences, 동일한 기능
FSE24BEtherCATMC07B EtherCAT communication board, front slot mount
DFE24BEtherCATSeparate Ethernet bus adapter (distinguished from FSE24B, often listed together in old docs)
DFE32B프로피넷 IOPROFINET IO adapter, compatible with MC07B/MDX61B
DFE33B이더넷/IP + 모드버스 TCPDual-protocol Ethernet adapter
DFP21BPROFIBUS DPV1PROFIBUS DP adapter
DFD11B디바이스넷DeviceNet adapter, built-in CANopen

Supplementary slot I/O modules (not pure communication but with SBus)

FIO11B: Analog ±10V/4-20mA + RS485, mutually exclusive with FSC11B

FIO21B: 7 digital DI + SBus

  1. MOVIDRIVE® B (MDX61B) Communication Cards
모델규약비고
DFE24BEtherCATMDX61B EtherCAT
DFE32B프로피넷 IO프로피넷 IO
DFE33B이더넷/IP + 모드버스 TCPDual-protocol Ethernet
DFP21BPROFIBUS DPV1프로피버스 DP
DFC11BCANopenMDX61B dedicated CANopen card
DFD11B디바이스넷디바이스넷
DFI11BINTERBUSCopper INTERBUS
DFI21BINTERBUS-LWLFiber INTERBUS
DFS11BPROFIsafe (프로피버스)Safety bus card for PROFIBUS
DFS21BPROFIsafe (프로피넷)Safety bus card for PROFINET
  1. PC Commissioning Adapters (Not Built-in Expansion Boards, 부속품)
모델기능
USB11AUSB to SEW commissioning port, replacement for UWS
UWS21BRS232 commissioning adapter
UWS11ALegacy RS485 commissioning adapter
  1. New Generation MOVITRAC advanced / classic Gateways (New Inverter Platforms, No Longer DFE/FSC)

CFX11A, CFC11A: Modular gateways, support SBus PLUS, EtherCAT, 프로피넷, 이더넷/IP, 모드버스 TCP. Not compatible with MC07B/MDX61B

  1. 빠른 선택 가이드

Multi-drive SBus/CANopen: FSC11B (MC07B first choice)

프로피넷: DFE32B

EtherCAT: FSE24B (MC07B) / DFE24B (MDX61B)

EtherNet/IP+ModbusTCP: DFE33B

프로피버스 DP: DFP21B

디바이스넷: DFD11B

CANopen on MDX61B: DFC11B

  1. 중요 사항
  2. MC07B expansion slot: FSC11B/FSC12B/FSE24B/FIO11B/FIO21B are mutually exclusive; only one board per slot
  3. DFE series are external bus adapters, not front slot boards, different installation method
  4. Older MDX60A, Movidrive A series have legacy DFC/DFP models, 지금은 단종됨

SEW MC07B / MDX61B Inverter Common Fault Code List (Including FSC11B Communication Faults)

Reset methods: 전원 주기, terminal reset, MOVITOOLS software reset. Fault history stored in P080. For all high-voltage inspection, cut off power and wait DC bus discharge ≥5 minutes.

오류 코드Fault Name원인문제 해결 & 솔루션
F01과전류Short circuit in motor cable/motor winding, 기계적 걸림, too short ramp time, damaged IGBT power module1. Disconnect motor cable and power on alone; F01 still present = internal power module damage
2. Measure motor insulation and three-phase resistance; check mechanical jamming
3. Extend acceleration/deceleration ramp; avoid breaking output contactor under load
F03지구 결함Damaged motor cable insulation, motor earth leakage, short circuit at inverter output to groundMegger test motor cable insulation; replace damaged power cable; check inverter output to ground
F04Brake Chopper FaultBrake resistor open circuit, wrong resistance value, brake loop short circuit, damaged brake transistor1. Measure brake resistor value against nameplate
2. Check brake resistor terminals; resistor aging/overheating
3. If resistor is normal but alarm persists: brake unit damaged, return for repair
F06Input Phase Loss입력 단계 누락, loose incoming wiring, blown input fuse, unbalanced grid voltageCheck circuit breaker, 접촉기, terminal voltage; tighten connections; verify three-phase balance
F07DC 버스 과전압빠른 감속, high inertia load, insufficient brake resistor, 높은 그리드 전압1. 감속시간 연장
2. Use higher-power brake resistor / lower resistance value
3. Verify rated input voltage; check brake circuit
F08Speed Monitoring인코더 결함, loose encoder wiring, load slip, 기계적 걸림, incorrect motor identification1. Encoder supply, A/B phase wiring, 차폐
2. Re-run motor identification; check mechanical slip
3. V/F mode: 무거운 짐, current limiting causes speed deviation
F09Start FaultFailed motor identification, 잘못된 모터 매개변수, 일치하지 않는 모터, 기계적 걸림Verify motor nameplate data; run static identification without load; check motor phase sequence
F11과열Clogged heat sink, 고장난 팬, 높은 주변 온도, continuous overloadClean cooling channel; 냉각팬을 확인하세요; 부하를 줄이다; 캐비닛 환기 개선; derate operation
F31TF/TH Motor Thermal ProtectionMotor PTC thermistor open circuit, 모터 과열, broken thermistor wire, wrong parameter settingMeasure motor thermistor; check motor overload; verify P50x thermal parameters; 배선을 확인하세요
F36Missing Option / Option Recognition Error (FSC11B frequent alarm)FSC11B/FIO11B/FSE24B not fully seated, missing fixing screws, 결함이 있는 모듈, wrong model, incompatible firmware1. 전원 끄기, re-seat communication board and tighten screws (critical for EMC)
2. Only one option per MC07B slot; FSC and FIO cannot coexist
3. Test with a spare FSC11B to confirm board failure
F43SBus / CANopen / RS485 Communication Timeout (FSC11B most common)Incorrect termination resistor, 일치하지 않는 전송 속도, duplicate node ID, 버스 단락, 열악한 차폐, 과도한 케이블 길이, offline master1. Termination ON only at first and last station, OFF for intermediate nodes
2. Confirm P884 node address and P886 baud rate consistent across network
3. 차폐 연선, single-point shield grounding; separate power and communication cables
4. 데이지 체인 배선, no star topology; temporarily increase P887 timeout for test
F45Fieldbus Fault (PROFINET/EtherCAT/IP)Loose Ethernet cable, wrong IP/device name, 스위치 결함, offline masterCheck cable and LINK LED; verify PLC device name and IP; switch port; restart bus adapter
F47STO Safety Stop ActiveSafety loop open, broken safety terminal wiring, safety relay trippedCheck STO safety circuit terminals; reset safety loop; inspect safety relay and emergency stop
F80RAM Self-test FaultMainboard hardware damage, firmware error, strong interferenceRestore factory settings; reflash firmware; 결함이 남아 있으면: control board damaged, return for repair
F84모터 보호모터 과부하, long-time over-rated current, improper protection curveMonitor current; 부하를 줄이다; adjust motor protection curve; check motor cooling
F98Flash CRC ErrorParameter area corruption, firmware error, heavy electrical interferenceRestore factory settings, re-download parameters; reflash firmware; check grounding and interference
  1. Common Non-coded Abnormalities (오류 코드 없음, Frequent On-site Issues)
  2. No display after power on, 검은 화면

Missing 24V control supply, blown control fuse, damaged power board

구별하다: Missing 380V main power or missing 24V control supply; MC07B can be powered only by 24V to check display

  1. Display present, no enable, cannot start (digit shows 2)

No terminal enable signal; PLC does not send control word under bus control; P880/P881 source misselected

Local mode: start via panel; bus mode: confirm control source set to SBus/CANopen

  1. Motor oscillation, unstable running, speed drift

Poor SBus/CANopen shielding and messy grounding; reversed encoder A/B phase; incomplete motor identification; load resonance

  1. Intermittent F43 alarms

90% caused by termination resistor, shielding grounding, loose crimps; secondly, power cables routed in parallel with communication cables

  1. Communication established but start/stop control fails

Wrong PDO mapping, control word bit definition error, PLC does not send 0Fh enable, inverter inhibited

  1. Standard On-site Troubleshooting Sequence
  2. Read fault code on display, check historical fault in P080
  3. Classify: Power circuit faults (F01/F03/F06/F07/F11) / Communication option faults (F36/F43/F45) / Safety/motor protection (F31/F47/F84)
  4. Check external wiring, 전압, 격리, mechanics and cooling first; then parameters; finally judge hardware damage
  5. For communication faults (FSC11B): Priority order: DIP termination → Node ID → Baud rate → Shielding grounding → Wiring topology
  6. Reset Priority
  7. Software reset (MOVITOOLS)
  8. Terminal reset
  9. Power off for more than 5 minutes and restart (full DC bus discharge)

Hardware damage faults (F01 module damage, F80, F98) will reoccur after reset

  1. Summary of Key Communication Faults for FSC11B

F36: Inverter cannot recognize FSC11B (설치, 나사, 하드웨어 결함)

F43: SBus/CANopen bus disconnection (배선, 종료, ID, 전송 속도, 차폐)

Bus scanned but frequent packet loss: Check shielding first; use daisy-chain only, avoid star wiring