Independent Thermal-Magnetic Trip Unit (Overcurrent Release) for SENTRON 3VL Series MCCB에스
Compatible Circuit Breaker Frame: VL400 frame size (3VL4xxx 400A frame moulded case switches)
극수: 3-폴, LI thermal-magnetic trip for power distribution protection (초과 적재 + 순간 단락)
- Breakdown of Order Code 3VL9431-7DC30
- 3VL: Main series of SENTRON moulded case circuit breakers
- 9: 접미사 9 = Internal Accessory / Independent Trip Unit (Not a complete circuit breaker body)
- 4: Compatible frame size VL400 (400프레임)
- 31: Trip current specification code
- 7: LI thermal-magnetic trip (Distribution protection, non-time-delayed short-circuit)
- 디: Connection type – Screw terminal connection
- 기음: 표준 버전, universal for AC applications
- 30: 3-폴, no additional auxiliary contacts, standard delivery configuration
III. Core Setting Parameters (Key Protection Values)
| Protection Item | 조정 가능한 범위 | Operation Description |
| Long-time Overload Trip Ir | 250 ~ 315A adjustable | Thermal trip for cable/busbar overload protection |
| Instantaneous Short-circuit Trip Ii | 1575 ~ 3150A adjustable | Magnetic instantaneous trip for immediate short-circuit breaking |
| 여행 유형 | 리 (열자기) | Standard protection for distribution lines, no short-time delay |
| Rated Compatible Frame Current | In=400A (VL400 body) | Maximum matching frame size: 400에이 |
- 전기 같은 & 기계적 매개변수
- 적용 전압
교류: 50/60헤르츠, 최대. 690다섯
DC: 최대. 440다섯
- 장착 방법: Direct replacement and installation onto the base of 3VL4xxx VL400 circuit breakers; no cabinet modification required
- 순중량: 대략. 1.42~1.46kg, individually packed per unit
- Connection Terminals: Screw compression terminals, compatible with copper busbars and cable lugs
- 표준 인증: CE, CCC, IEC 60947-2 standard for moulded case circuit breakers
- 응용 시나리오
- Replacement of trip units for VL400 MCCBs in low-voltage complete switchgear and power cabinets
- Protection of incoming and outgoing distribution circuits (케이블, busbars) in factories and buildings
- General load protection (Not dedicated for motors; motor loads require motor-specific trip units)
- Project retrofits: Spare replacement part for failed trip units of existing 3VL400 circuit breakers
- Examples of Matching Circuit Breaker Bodies
Directly mountable on the following 400A frame circuit breakers:
3VL4731-1DC36-0AA0
3VL4740-1AA36-0AA0
All standard 3-pole VL400 frame moulded case switches in the 3VL4xx range
Ⅶ. Differentiation of Equivalent Series Replacements (Selection Pitfall Avoidance)
3VL9431-6DC30: Thermal-magnetic trip for motor protection with different Ii setting range; non-interchangeable
3VL9431-7SP30: Plug-in terminals; screw type D model cannot directly replace plug-in SP model
3VL96xx: Compatible with VL630 frame; larger frame dimension, cannot be fitted to VL400 bodies
Ⅷ. 설치시 주의사항
- Disconnect upstream power supply and perform full power cut-off before replacing the trip unit
- After adjusting the Ir (초과 적재) and Ii (단락) 손잡이, fasten anti-loosening screws to prevent setting drift during operation
- Only compatible with 3-pole VL400 circuit breakers; 4-pole VL400 breakers require 4-pole trip units from the 3VL944x series
- No derating required for long-term operation at ambient temperature ≤50°C; reduce Ir setting current if temperature exceeds 50°C
Full List of Applicable Industries for 지멘스 3VL9431-7DC30 (315A LI Thermal-Magnetic Trip Unit for VL400 Distribution Frame)
This model is a distribution-specialized thermal-magnetic trip unit (not for motor use), compatible with 3VL4xxx 400A frame MCCBs, with adjustable Ir=250~315A. It provides overload and instantaneous short-circuit protection for busbars, 케이블, transformers and general power feeders. It is not suitable for main circuits of high-power three-phase motors (3VL9431-6DC30 shall be selected for motor applications).
- General Manufacturing Industry (Most Widely Used)
- 가공 & Equipment Manufacturing
Protection for branch feeders and busbar outlets in machine tool plants, 자동화된 생산 라인, stamping/forging workshop MCC (모터 제어 센터) and workshop power distribution cabinets; 315A circuits suit centralized power supply loops for large gantry milling machines and CNC production lines.
- Complete Vehicle & Auto Component Plants
Low-voltage power cabinets in stamping, welding and coating workshops, general feed switches for workshop zoning, spare trip units for 400A MCCBs in factory substations and retrofit replacements.
- 고무 & 플라스틱, 직물, 종이 & Printing Industries
Incoming and outgoing circuits of distribution cabinets for extruders, setting machines and paper main drives; protection of factory cable trunk lines, suitable for ordinary dusty industrial environments.
- 야금, Steel Structure & 금속 가공
Auxiliary power distribution for steel rolling, power circuits in steel cutting workshops, auxiliary power feeders for medium-frequency furnaces; withstand short-circuit protection under impulse loads.
- Municipal Water, 폐수 & 환경 보호 산업
- Sewage Treatment Plants, Water Purification Plants & Pump Stations
Main distribution cabinets in pump houses, busbar feeders for large water pumps, distribution circuits for blowers and sludge dewatering equipment; spare replacement of 400A MCCBs in plant substations.
- Waste Incineration & Kitchen Waste Treatment Plants
Auxiliary power supply for incinerators, distribution cabinets in leachate treatment workshops, centralized power circuits for fans and air compressors.
- Municipal Heating & Heat Stations
Low-voltage power distribution in heat exchange stations, trunk line protection for circulating pumps, branch switches of boiler room power cabinets.
III. 건설 & 상업용 건물
- Large Commercial Complexes, 쇼핑몰 & Hotels
Zonal main switches in underground power distribution rooms, feeders for central air conditioning main units, power busbar protection for underground parking garages; 315A rating matches power supply circuits for large chillers.
- Grade-A Office Buildings & Standard Industrial Parks
Floor main distribution cabinets, power incoming feeders for equipment rooms, spare trip units for VL400 breakers in park power houses.
- 병원 & Healthcare Facilities
Main medical power distribution, standby power feeders for operating rooms, high-reliability distribution protection to meet continuous power supply requirements for medical loads.
- 학교, Stadiums & Exhibition Centers
Power distribution cabinets for venues, centralized distribution trunk lines for central air conditioning and stage equipment.
- 교통 인프라
- 철도 운송 (지하철, High-Speed Railway Stations, Intercity Rail)
Station power distribution rooms, feeders for ventilation and water supply & drainage equipment, low-voltage power distribution in depot maintenance workshops; suitable for maintenance replacement of 400A MCCBs inside stations.
- 공항, 포트 & Logistics Warehousing Parks
Main power distribution for terminal buildings, distribution cabinets for dock handling equipment, trunk line protection for large cold storage warehouses.
- Tunnels & Highway Service Areas
Power distribution rooms for tunnel fans, main distribution switches for service area comprehensive buildings.
- 에너지신산업
- Ground-Mounted PV Power Stations & 광고 & Industrial Distributed PV Systems
Distribution cabinets on the AC side of inverters, low-voltage feeders of step-up stations, power busbar protection in PV plants (supports AC 690V / DC 440V).
- 풍력 발전 단지 & Energy Storage Power Stations
Low-voltage outgoing circuits of box transformers, auxiliary power loops of energy storage containers, spare VL400 breakers for station power distribution rooms.
- Centralized EV Charging Stations
Main distribution cabinets for large charging yards, protection of 315A power supply circuits for multi-charger clusters.
- 데이터 센터 & Precision Equipment Rooms
Low-voltage power cabinets in IDC rooms, cloud computing centers and server rooms, UPS input & output feeders. Protects server room busbars, precision air conditioners and uninterruptible power loads; accurate overload isolation reduces the risk of full-site power outages.
Ⅶ. 화학적인, Grain, 기름 & 식품 가공
- Fine Chemical & Daily Chemical Plants
Main distribution cabinets outside explosion-proof zones of production workshops, power trunk lines for circulating pumps and agitators (non-explosion-proof body only for non-hazardous zones).
- Grain, 음료 & Food Processing Plants
Power circuits for filling and fermentation workshops, centralized power busbar protection for cold storage facilities.
Ⅷ. Other Supporting Industries
- Complete Electrical Equipment Manufacturers (Core OEM Customers)
Original matching spare trip units for low-voltage switchgear, power cabinets and MCC cabinets, mass-fitted to 3VL400 circuit breakers before factory delivery.
- 산업용 & Mining Retrofit, Electromechanical Maintenance Projects
Power distribution renovation of aging factories, spare replacement for damaged trip units of existing VL400 circuit breakers.
- Cold Chain Warehousing & Cold Storage Industrial Parks
Centralized power supply circuits for large cold storage compressors, main feeder protection for refrigeration equipment rooms.
Industry Selection Restrictions (Unapplicable Scenarios)
- Main protection circuits for high-power three-phase motors (Instantaneous Ii setting range cannot match motor starting inrush; 3VL9431-6DC30 motor-specialized model must be selected)
- High-risk flammable and explosive areas of Zone 1 / 존 2 explosion-proof divisions (Explosion-proof cabinets are required as accessories; the trip unit itself carries no explosion-proof certification)
- Vessels and offshore platforms (Special trip unit models with marine certification are required; standard 3VL94 series fails marine classification standards)
- VL630 frame 630A circuit breakers (Only compatible with 400A VL400 frame; frame dimensions are non-interchangeable)
접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지