SIEMENS QAE2112.010 Immersion Temperature Sensor

Passive Insertion/Immersion Water Temperature Sensor of Symaro Series Core element: Pt1000 (Class B per IEC751). Designed for siemes HVAC and Building Management Systems (BMS) to measure liquid temperature in pipelines and water tanks. It does not come with an integrated thermowell and must be installed with a separate thermowell. 전체 주문 코드: BPZ:QAE2112.010 Core Technical ...

  • 제품 세부정보

Passive Insertion/Immersion Water Temperature Sensor of Symaro Series

Core element: Pt1000 (Class B per IEC751). Designed for siemes HVAC and Building Management Systems (BMS) to measure liquid temperature in pipelines and water tanks. It does not come with an integrated thermowell and must be installed with a separate thermowell.

전체 주문 코드: BPZ:QAE2112.010

  1. 핵심 기술 사양
매개변수사양
Sensing ElementPt1000 (Passive Resistance Signal)
측정 범위-30℃ ~ +130℃
Measuring Accuracy±0.95K within -30℃ to 130℃
Immersion Probe Length100mm (Stainless Steel Shaft)
Time Constant8s without thermowell; 30s with thermowell
보호 등급IP42 for sensor body; IP54 after tightening M16 cable gland
전기 연결나사식 터미널 블록, 2-와이어 시스템
케이블 입구M16×1.5 cable gland
Housing DimensionsW80 × H60 × D31 mm
Nominal Pressure RatingPN3 (Must be used with G½ thermowell; Max operating pressure PN10)
재료Probe shaft: 스테인레스 스틸; 주택: Heat-resistant plastic

III. 모델 코드 설명

QAE2112.010

QAE: Series of immersion/insertion temperature sensors

21: Symaro general-purpose water temperature measurement

1: No integrated threaded thermowell; external thermowell fixed by clips

2: Pt1000 sensing element

010: Immersion length 100mm

Comparison of derivative models in the same series:

  1. QAE2112.015: Pt1000, 150mm immersion length
  2. QAE2111.010: Pt100, 100mm immersion length
  3. QAE2120.010: Built-in G½ threaded thermowell, LG-Ni1000
  4. 일반적인 애플리케이션 시나리오
  5. Supply/return water temperature monitoring for heating systems & temperature control of mixing valves
  6. Temperature collection for chilled and hot water pipelines in central air conditioning
  7. Water temperature measurement for domestic hot water tanks and boilers
  8. Over-temperature protection for underfloor heating, heat exchange stations and fan coil units
  9. Matching Siemens DDC controllers (PXC, RWG series, 등.) for building BMS systems
  10. Key Installation Specifications
  11. Thermowell Mandatory: Original ALT-SS100 stainless steel G½ thermowell is recommended. Weld G½ threaded seats on pipelines in advance. A minimum probe insertion depth of 60mm is required to guarantee measuring accuracy.
  12. 장착 위치: Install 1.5~2m downstream of pump outlets or mixing valves with the probe facing the incoming water flow. The cable terminal side must not face upward to prevent water ingress.
  13. Response Optimization: Apply thermal grease between thermowell and probe to reduce thermal resistance.
  14. 배선: Direct 2-wire connection to Pt1000 input terminals of DDC controllers (무극성). Shielded twisted pair cable is recommended to minimize interference.
  15. 배선 & 호환성

산출: Pure passive resistance signal. Only compatible with controllers supporting Pt1000 input.

Compatible Siemens Controllers: RWG16, PXC series, Climatix controllers

Not Directly Replaceable: Pt100 models (QAE2111), 4-20mA active transmitters (QAE2174)

Ⅶ. List of Matching Accessories (Separate Purchase Required)

  1. ALT-SS100: G½ stainless steel protection thermowell (Standard fit for 100mm probes)
  2. Thermal grease: Improves temperature measurement response speed
  3. M16 sealing cable gland (Upgrades protection class to IP54)

Ⅷ. 문제 해결 가이드

결함 증상일반적인 원인솔루션
Constant / Infinite temperature readingBroken probe wire, 느슨한 단자Disassemble housing, fasten screws and measure resistance at both ends of probe shaft
Severe measurement deviation & slow responseMissing thermowell, no thermal grease, insufficient insertion depthInstall thermowell, apply thermal grease and ensure ≥60mm immersion depth
Drifting & fluctuating readingsUnshielded long cables, damp wiring terminalsReplace with shielded cables and tighten cable glands for waterproofing

Complete Technical Datasheet of SIEMENS QAE2112.010 Immersion Temperature Sensor

  1. Basic Model Information

Material Model No.: QAE2112.010

제품 시리즈: Symaro QAE21 Passive Insertion / Immersion Temperature Sensor

제품 유형: Liquid temperature probe for water pipelines and tanks (No integrated thermowell; separate protection thermowell required for installation)

주문 코드: BPZ:QAE2112.010

Segment-by-Segment Model Definition

분절정의
QAESeries of immersion liquid temperature sensors
21Sub-series of general passive HVAC temperature probes
12Sensing element Pt1000 (11=Pt100, 12=Pt1000)
0.01Effective immersion length of probe: 100 mm
  1. Core Sensing & Accuracy Parameters
  2. Temperature Sensing Core

Element: Pt1000, compliant with Class B accuracy per IEC 60751

측정 범위: -30 ℃ ~ +130 ℃

Measuring Error: ±0.95 K (전체 범위)

  1. Response Time Constant

Without protection thermowell: τ₀.₅ ≈ 8 에스

With standard stainless steel thermowell: τ₀.₅ ≈ 30 에스

  1. Passive Signal Characteristics

Pure resistive passive output with no external power supply required. Directly connect to resistance thermometer input modules of Siemens DDCs, thermostats and PLCs.

III. 기계구조 & 치수

  1. Probe Specifications

Effective immersion length: 100 mm

Shaft Material: 스테인레스 스틸

Nominal pressure of matched thermowell: PN3 (Max pressure 3 술집)

  1. Wiring Housing

Housing Size: 80×60×31 mm (L×W×H)

케이블 콘센트: M16 cable gland

배선 방법: Screw-clamp terminals for 0.5~1.5 mm² cables

보호 등급: IP42; IP54 with sealing cable gland accessory

  1. Operating Ambient Conditions

Allowable ambient temperature for housing: -40 ℃ ~ +70 ℃

Compatible Media: Cold water, 뜨거운 물, glycol HVAC circulating water, domestic hot water

  1. Mandatory Installation Accessories (Optional Purchase)

This model does not include G1/2 threaded protection thermowell. Thermowell assemblies must be ordered separately:

  1. Standard protection thermowell: ASZ-100 (G1/2 external thread, fits 100mm probes, PN10 pressure rating)
  2. Locking clip: Secures probe to thermowell to prevent loosening or detachment
  3. 케이블: 3-코어 차폐 케이블 (Standard 3-wire wiring for Pt1000)
  4. Electrical Wiring Rules (3-Wire System)

3-wire Pt1000 connection eliminates measurement error caused by cable resistance:

단말기 1: One end of resistance element

터미널 2 & 3: Two parallel wires from the other resistance end to the controller

Compatible Siemens Controllers: RWD62/RWD68, Synco700, Desigo PXC series, Building DDC

  1. Same-Series Model Differentiation & 교체 옵션

Comparison of Similar Models in Series

모델Sensing CoreImmersion LengthThermowell Configuration
QAE2111.010Pt100100mmProbe only, no thermowell
QAE2112.010Pt1000100mmProbe only, no thermowell (이 모델)
QAE2112.015Pt1000150mmProbe only, no thermowell
QAE2120.010LG-Ni1000100mmIntegrated G1/2 thermowell PN10

Direct Replacement Solutions

  1. Extended Pt1000 version with identical specs: QAE2112.015 (150mm immersion length for thick pipeline walls)
  2. Integrated pre-assembled version without separate thermowell: QAE2120.010 (Nickel resistance; controller must support Ni1000 signal)
  3. Cost-effective Pt100 variant: QAE2111.010 (Only applicable if controller supports Pt100 input)

Ⅶ. 일반적인 애플리케이션 시나리오

공조 & Building Management BMS Systems:

  1. Supply/return water temperature monitoring for chillers
  2. Hot water measurement for boilers and plate heat exchangers
  3. Over-temperature protection for underfloor heating and fan coil units
  4. Constant temperature control for domestic hot water tanks and pipelines
  5. Temperature collection for industrial process cooling water

Ⅷ. Strict Installation Prohibitions

  1. Never immerse the bare probe directly into pipeline fluid without thermowell — risk of corrosion and non-detachable replacement.
  2. Medium pressure shall never exceed PN3. Select QAE2120 series with PN10 integrated thermowell for high-pressure pipelines.
  3. 적어도 90% of the probe shaft must be fully submerged in fluid; incomplete immersion leads to severe temperature deviation.
  4. Do not route sensor cables in the same trunking as power cables. Single-end earthing of shielding layer reduces electromagnetic interference.
  5. Medium temperature shall not exceed 130℃ even temporarily. High-temperature applications require high-temperature resistant thermowells.
  6. Consumable Matching Spare Parts
  7. ASZ-100 Stainless Steel Temperature Thermowell G1/2
  8. M16 Sealing Cable Gland (Upgrade to IP54 protection)
  9. PTFE sealing tape for thermowells, high-temperature gaskets

Shaft Material of SIEMENS QAE2112.010

조사 (Immersion Shaft) 재료: 스테인레스 스틸

보충 노트

  1. All QAE21xx series sensors (QAE2111, QAE2112, QAE2120, 등.) adopt uniform stainless steel immersion shafts, resistant to corrosion from HVAC cold/hot water and glycol circulating water, suitable for medium temperatures ranging from -30℃ to +130℃.
  2. Distinction between two components:

Original thin probe shaft of sensor: 스테인레스 스틸 (Factory-fitted, 100mm length)

External optional protection thermowell ASZ-100: Also stainless steel with G1/2 thread and PN10 pressure rating. Mandatory for pipeline installation; never submerge bare shaft directly in pipeline fluid.

  1. 하우징 재질: ASA engineering plastic (Off-white housing), IP42 protection class.

Application Scenarios of SIEMENS QAE2112.010 (Pt1000 Immersion Water Temperature Sensor)

  1. HVAC Heating Systems (Most Common Use Cases)
  2. Temperature Measurement at Boiler / Heat Source Side

Collect supply and return water temperature of gas/oil hot water boilers to interlock boiler start/stop, proportional regulation and over-temperature protection.

  1. Plate Heat Exchange Stations

Monitor supply & return water of primary municipal heating network and secondary heating loop for automatic temperature control, constant temperature & pressure regulation of heat exchange units.

  1. Underfloor Radiant Heating

Collect supply/return water temperature of manifold assemblies to interlock mixing centers, prevent floor overheating and stabilize supply water temperature.

  1. Radiator Heating Systems

Water temperature monitoring for building risers and branch pipes to support zoned or household independent temperature regulation.

  1. Central Air Conditioning Water Systems
  2. Chilled Water System of Chillers

Acquire chilled supply and return water temperature to calculate temperature difference, control chiller loading/unloading and variable frequency pump speed adjustment.

  1. Cooling Water Systems

Measure cooling supply & return water temperature to interlock cooling tower fan start/stop and variable frequency regulation for unit energy saving.

  1. Fan Coil Units / Air Handling Units

Temperature measurement of chilled/hot water pipelines for air conditioning, cooperating with 2-way & 3-way motorized valves to realize room constant temperature control.

  1. Air Handling Units (AHU)

Monitor inlet & outlet water temperature of heating and cooling coils, automatically adjust valve opening to stabilize supply air temperature.

III. Domestic Hot Water & Swimming Pool Systems

  1. Domestic Hot Water Tanks / Storage Water Heaters

Immersed temperature measurement inside tanks and hot water circulation pipelines to control circulation pump and heating equipment operation for all-day constant hot water supply.

  1. Hot Water Pipe Networks for Hotels & Apartments

Temperature monitoring of main and branch hot water pipes to reduce heat loss and balance hot water temperature across floors.

  1. Constant-Temperature Swimming Pool Systems

Measure pipeline temperature of pool heat exchangers to maintain steady pool water temperature and interlock plate heat exchangers for heating.

 

  1. Industrial Process Water Systems
  2. Process Cooling Water for Workshops

Temperature monitoring of cooling circuits matched with injection molding machines, machine tools and air compressors, triggering over-temperature alarms and equipment interlock shutdown.

  1. Purified Water / Process Hot Water in Cleanrooms

Temperature measurement of cleanroom HVAC hot water and process circulating water to meet constant-temperature process requirements of pharmaceutical and electronic workshops.

  1. Waste Heat Recovery Systems

Temperature detection for waste heat recovery tanks and circulation pipelines to automatically switch recovery/heating modes for energy-efficient operation.

  1. BMS & Energy Metering Applications
  2. Building Energy Consumption Monitoring

Collect temperature difference between supply and return pipes of cooling/heating networks. Calculate cooling & heat energy consumption with flow meters for itemized energy statistics.

  1. Support for Building DDC Automation Systems

Fully compatible with Siemens PXC, RWG and Climatix series controllers as standard water temperature measuring points.

  1. Intelligent Pump Room Monitoring

공급 & return water temperature measurement of primary and secondary pumps for pump variable frequency optimization and pipeline anti-freeze alarming.

  1. Auxiliary Temperature Control & Protection for Supporting Equipment
  2. Solar Hot Water Systems

Measure outlet temperature of solar collectors and storage tanks to control circulation pump operation and realize solar temperature-difference circulation.

  1. Anti-Freezing Monitoring

Detect temperature of buried outdoor heating pipelines and roof chilled water main pipes; automatically activate heat tracing and circulation pumps when temperature drops below setpoint for freeze protection.

  1. Temperature Sensing for Constant-Temperature Mixing Valves

Collect mixed outlet water temperature for closed-loop regulation of cold/hot water inlet ratio to stabilize outlet temperature and prevent scalding.

Restricted & 적용할 수 없는 시나리오

  1. Steam pipelines and high-temperature flue gas (Max measuring range 130℃, not suitable for steam service)
  2. Direct insertion into high-pressure liquid without thermowell (G1/2 thermowell is mandatory)
  3. Liquids with strong acid/alkali corrosion (Standard stainless steel shaft requires anti-corrosion thermowell replacement)
  4. Air duct temperature measurement (Use QAM series duct temperature sensors instead; cross-use prohibited)

이전: