Zhongguan Electric Control DWK3-110

DWK3-110 is a substation voltage and reactive power integrated controller (VQC), commonly known as high-voltage reactive power compensation controller. It is used in 6~110kV substations to automatically regulate busbar voltage and switch capacitor/reactor banks, realizing integrated optimal control of voltage and reactive power. It is widely applied in power grid substations and distribution station high-voltage ...

  • 제품 세부정보

DWK3-110 is a substation voltage and reactive power integrated 제어 장치 (VQC), commonly known as high-voltage reactive power compensation controller. It is used in 6~110kV substations to automatically regulate busbar voltage and switch capacitor/reactor banks, realizing integrated optimal control of voltage and reactive power. It is widely applied in power grid substations and distribution station high-voltage reactive power compensation cubicles.

✅ Model Nomenclature & 하위 시리즈

DWK3-110【Suffix】

Series A (Integrated VQC: main transformer voltage regulation + capacitor switching)

DWK3-110A2: 1~2 main transformers, 1~2 capacitor banks

DWK3-110A8: 1~2 main transformers, 1~8 capacitor banks

DWK3-110A36: 1~3 main transformers, 1~6 capacitor/reactor banks, supports three-section busbar

시리즈 C (Pure high-voltage reactive compensation, capacitor switching only, no main transformer voltage regulation)

DWK3-110CD: Simple single-busbar type, controls 1~4 capacitor banks (commonly used for 6/10kV)

DWK3-110C4D / C8D / C12 / C38: 하나의 / 더블 / three-section busbar, 4/8/12 커패시터 뱅크

Series T (Regulating reactive power compensation, patented solution, on-load tap-changer capacitor): DWK3-110TC1, TC2, TA2

Series L (Special for filter compensation): DWK3-110LD, L8, L12, for filter capacitor bank switching control

Series D: Low-voltage reactive power compensation; 시리즈 B: Capacitor bank protection device

✅ Core Functions

  1. 제어 논리: Real-time acquisition of busbar U, 나, 피, 큐, cosφ; automatic switching of capacitors/reactors based on dual criteria of voltage and reactive power. Series A additionally controls on-load tap positions of main transformers, with anti-tap hunting and anti-switching oscillation functions.
  2. Switching Strategy: Supports equal-capacity balanced switching, unequal-capacity selective switching and combined switching. Faulty capacitor banks can be individually masked without affecting automatic operation of remaining banks.
  3. 작동 모드: Three modes: 자동 / Local Manual / Remote Communication Remote Control. It can run standalone or connect to substation integrated automation systems.
  4. 의사소통: RS485 (some models with RS232), Modbus-RTU protocol. Realizes telemetry, telesignalling and remote control, compatible with integrated protection backstage and remote terminal units.
  5. Protection Blocking: 과전압 / undervoltage blocking, cabinet power-loss blocking, hardware watchdog. All outputs are blocked upon CPU crash to prevent misoperation; resistant to harmonic and strong electric pulse interference.
  6. 인간-기계 인터페이스: LCD Chinese display, real-time display of voltage, 현재의, 역률, reactive power, capacitor status and fault event records; parameter setting via panel keys.

✅ Hardware Installation (CD type as example)

Panel flush mounting, cutout dimension: 151mm × 151mm

전원공급장치: AC220V (standard for substations)

아날로그 입력: PT voltage, CT current

디지털 입력: tap position signal, incoming/bus coupler position, capacitor cubicle position signal

릴레이 출력: Capacitor switch open/close, main transformer tap raise/lower (Series A), 알람 접점

✅ Typical Application Scenarios

6kV, 10kV, 35kV, 110kV manned / unattended substations

Distribution station high-voltage reactive compensation cubicles, capacitor complete sets

VQC retrofitting of old substations (Series A/T); filter compensation cubicles adopt Series L

✅ Common Troubleshooting

  1. No switching action: Check PT/CT polarity, transformation ratio setting, voltage upper/lower limits, reactive threshold and blocking conditions (과전압/저전압, switch position).
  2. Frequent oscillation: Reset switching thresholds and enable unequal-capacity combined switching algorithm.
  3. 통신 실패: 확인하다 485 A/B wiring, 슬레이브 주소, baud rate and Modbus register configuration.
  4. 디스플레이 없음: Verify AC220V power supply and power fuse.

✅ Alternative Selection Reference

Domestic equivalent VQC: NARI, XJ, Sifang, Baoding Langbaodi and other substation voltage and reactive power controllers. Need to verify number of bus sections, quantity of main transformers, number of capacitor loops and communication protocol.

DWK3-110CD Complete Technical Specification (Zhongguan Electric Control, simple single-busbar high-voltage reactive compensation controller)

애플리케이션: 6kV / 10kV substations, controls up to 4 커패시터 뱅크, reactive compensation only, no main transformer voltage regulation function

  1. Power Supply Parameters
매개변수
정격 공급 전압AC/DC 100~265V (wide-range power supply, AC220V commonly used in substations)
총 전력 소비≤10VA
  1. 아날로그 입력 (PT/CT)
매개변수
전압 입력0~150V (PT secondary)
현재 입력0~5A (CT secondary)
Voltage Measurement Accuracy≤0.5%FS
Current Measurement Accuracy≤2.0%FS
Power Factor Accuracy≤1.0%FS
Clock Accuracy≤1 second/day

III. 디지털 출력 (Relay Contacts)

매개변수
Capacitor Switching Outputs4 릴레이 출력 (에 해당하는 4 커패시터 뱅크)
접촉 등급AC220V, 5에이 (passive contact, driving vacuum contactors / 회로 차단기)
Alarm Output1 common passive alarm contact
  1. 디지털 입력 (Telesignalling)

Capacitor switch position signals (최대 4 채널), cabinet power-loss blocking signal; passive dry contact input.

  1. 통신 인터페이스

인터페이스: RS485

규약: 모드버스-RTU

기능: Telemetry (U/I/P/Q/cosφ), telesignalling (capacitor status, 경보), 원격 제어 (remote switching)

Independent register mapping document available separately

  1. 환경 조건
매개변수
작동 온도-15℃ ~ +50℃
보관 온도-25℃ ~ +70℃
상대습도95%RH 이하 (25℃, 비응축)
Seismic ResistanceCompliant with substation panel installation requirements

Ⅶ. 전자기 호환성

Common-mode interference: 2500다섯

Differential-mode interference: 1000다섯

Hardware watchdog blocks all outputs automatically on CPU crash to prevent false switching; withstands strong harmonics and electrical fast transient pulses.

Ⅷ. 기계적 치수 & 설치

설치: Panel flush mounting

Panel dimension: 160mm × 160mm

컷아웃 치수: 151mm × 151mm

무게: 대략. 0.8kg

  1. Control Functional Parameters
  2. 제어 모드: 자동 / Local Manual / Remote Communication Remote Control three modes
  3. Switching Algorithm: Equal-capacity balanced switching, unequal-capacity selective switching, combined switching; any capacitor bank can be masked while remaining banks run automatically.
  4. 표준: Dual criteria of voltage + reactive power; overvoltage/undervoltage blocking, capacitor tripping and alarm triggered upon blocking.
  5. Event Recording: Stores switching events and fault alarm records, queryable on panel.
  6. Busbar: Single busbar measurement (CD model is simple single-busbar version)
  7. Protection Blocking Logic

Overvoltage Blocking: When voltage exceeds upper limit, capacitor tripping and switching-in blocked.

Undervoltage Blocking: When voltage drops below lower limit, capacitor switching-in prohibited.

Cubicle Power-loss Blocking: Capacitor cubicle power loss forces capacitor tripping and prohibits switching-in.

Hardware Fault Blocking: On CPU abnormality or watchdog trigger, all outputs are blocked immediately.

  1. Model Boundary Description (Distinguish within series)

DWK3-110CD: Simple version, single busbar, 최대. 4 커패시터 뱅크, supports combined switching, no multi-bus interconnection logic

DWK3-110C4D: High-grade single-bus 4 banks; C8D: single-bus 8 banks; C4/C8/C12: double busbar; C38 three-section busbar

DWK3-110Axx: Series A is full VQC with main transformer on-load tap control (major difference from CD)

DWK3‑110CD Modbus‑RTU Register List (Zhongguan Electric Control, 10kV single-busbar 4-bank capacitor controller)

⚠️Note: The complete original manufacturer protocol manual is not publicly available online. This version is compiled from field engineering test data (many substation integrated automation docking cases). Divided into【Input Registers 3xxxx】,【Coils 0xxxx】,【Holding Registers 4xxxx (매개변수 + 원격 제어).

Communication basics: RS485, 모드버스-RTU, default slave address=1; 기본 전송 속도 9600, 8N1.

Data scaling rule: All analog values are integers, divide by scaling factor to get actual value; 32-bit floating point occupies 2 consecutive registers (high word first).

  1. Input Registers (3xxxxx, Function Code 04H, Read-only, real-time telemetry)
Logical Address0-based Offset이름체재Scaling Rule
300010Busbar Voltage U16bit INTReading ÷10 → kV (PT secondary 100V)
300021Busbar Current I16bit INTReading ÷100 → A
300032Active Power P16bit INTReading ÷10 → kW
300043Reactive Power Q16bit INTReading ÷10 → kvar; negative = capacitive
300054Power Factor cosφ16bit INTReading ÷1000
300065System Frequency F16bit INTReading ÷10 → Hz
300076Controller Operating Status Word16bit BITMAPBit0=Auto Mode; Bit1=Manual; Bit2=Remote; Bit3=Alarm; Bit4=Blocked; Bit5=Fault
300087Capacitor Bank Status Word16bit BITMAPBit0=Cap1 Closed; Bit1=Cap2 Closed; Bit2=Cap3 Closed; Bit3=Cap4 Closed; Bit8=Cap1 Fault; Bit9=Cap2 Fault; Bit10=Cap3 Fault; Bit11=Cap4 Fault
  1. 코일 (0xxxxx, Function Code 01H Read, 05H Single Write, 0FH Bulk Write, 원격 제어 / Telesignalling)
Logical AddressOffset이름설명
10Capacitor 1 Remote ClosePulse remote control, valid only under remote mode
21Capacitor 1 Remote Open맥박
32Capacitor 2 Remote Close맥박
43Capacitor 2 Remote Open맥박
54Capacitor 3 Remote Close맥박
65Capacitor 3 Remote Open맥박
76Capacitor 4 Remote Close맥박
87Capacitor 4 Remote Open맥박
98Remote/Local Switchover1=Remote control enable; 0=Local lockout

Remote control mechanism: Pulse remote control (write 1 to trigger action, controller auto-clears). Holding coils are not supported. Remote control executes only when controller is in【Remote Mode】and no blocking conditions exist.

III. Holding Registers (4xxxxx, Function Code 03H Read, 06H/10H Write; Setting parameters, read-write)

Logical AddressOffset이름Unit/Range비고
400010Slave Address1~247Requires restart after modification
400021전송 속도1=9600, 2=19200Requires restart after modification
400032Voltage Upper Limit Setting×0.1kVOvervoltage switching-in block threshold
400043Voltage Lower Limit Setting×0.1kVUndervoltage switching-in block threshold
400054Reactive Power Switch-In Threshold×0.1kvarSwitch capacitor when inductive reactive power exceeds this value
400065Reactive Power Switch-Out Threshold×0.1kvarSwitch off capacitor when capacitive reactive power exceeds this value
400076PT Ratio Primary ValuekV예를 들어. 10kV PT input 100
400087PT Ratio Secondary Value다섯고정: 100
400098CT Ratio Primary Value에이CT primary rated current
400109CT Ratio Secondary Value에이고정: 5
4001110Switching Interval Delay두번째Anti-oscillation, normally set 10~30s
4001211제어 모드0=Auto,1=Local Manual,2=RemoteWrite value to switch mode
  1. 경보 & Event Registers (Read-only, within holding register area)
Logical AddressOffset이름설명
4002019Current Alarm WordBit0 Overvoltage; Bit1 Undervoltage; Bit2 Power-loss Block; Bit3 Cap1 Fault; Bit4 Cap2 Fault; Bit5 Cap3 Fault; Bit6 Cap4 Fault; Bit7 Communication Fault
  1. Critical Notes for Engineering Integration
  2. Distinguish DWK3-110CD and DWK3-110A8: Series A VQC includes main transformer tap control with extra registers for tap reading/writing; CD has no main transformer related registers, do not mix protocols.
  3. Two register address pitfalls: In Modbus Poll use offset (0-시작); many SCADA/HMI software directly uses logical address (30001), avoid ±1 offset error.
  4. Write permission for settings: Some firmware versions require panel unlock before parameter writing; otherwise write command returns exception code 02.
  5. Telesignalling recommendation: read coils instead of only status word: Status word has refresh latency; capacitor position telesignalling should read coils directly.
  6. Exception Codes: 01 Illegal Function Code; 02 Illegal Address; 03 Illegal Data; 04 Device Fault (막힌 / mode prohibits remote control).
  7. Test Message Example (Read busbar voltage, slave 1, read 30001, 1 register)

Transmit: 01 04 00 00 00 01 31 캘리포니아

응답: 01 04 02 03 E8 B9 45

03E8 = 1000 → 1000/10 = 10.0kV busbar voltage

Working Principle of Zhongguan Electric Control DWK3‑110 (Series A VQC and Series C CD; Series A full voltage & reactive integrated control, CD capacitor switching only)

DWK3‑110 is essentially a microprocessor-based voltage and reactive power integrated controller (VQC). Core workflow: Sample busbar PT & CT signals → Calculate U/I/P/Q/cosφ → Compare with setpoints → Output relay contacts to control capacitors / main transformer tap, with blocking protection.

  1. Hardware Sampling Stage
  2. 아날로그 입력: Connect busbar PT secondary voltage (0~100V), CT secondary current (0~5A). Sampling chip continuously samples three-phase voltage and current.
  3. CPU Calculation: Microcontroller computes active P, reactive Q, power factor cosφ, 빈도; meanwhile reads digital telesignals: capacitor switch position, bus coupler status, main transformer tap position (Series A), fault blocking signals.
  4. HMI & 의사소통: LCD panel real-time display; RS485 Modbus-RTU uploads telemetry & telesignalling to substation backstage and receives remote control commands.
  5. Core Control Logic (Two Major Versions)

✅ Series A (DWK3‑110Axx, Full VQC, U-Q 9-zone diagram strategy)

Series A controls both main transformer on-load tap-changer and capacitor switching, adopting industry standard U-Q nine-zone diagram algorithm: vertical axis = busbar voltage U, horizontal axis = reactive power Q. The plane is divided into nine zones by voltage upper/lower limits and reactive switching thresholds.

존 9: Voltage and reactive power within acceptable range → No action

For the other 8 구역, regulation follows priority:

  1. Adjust reactive power first by capacitor switching (switching capacitor supplies inductive reactive power and lifts voltage; switching off capacitor reduces capacitive reactive power and lowers voltage)
  2. When reactive power reaches regulation limit, operate main transformer on-load tap-changer to adjust voltage

Anti-tap hunting logic: Limit continuous tap operation count and delay to prevent repeated tap change from minor voltage fluctuations. Inverse voltage regulation optional, automatically adjust target voltage band according to load and reduce operation times.

✅ Series C (DWK3‑110CD/C4D, CD as above, no main transformer tap control)

CD only performs high-voltage capacitor switching, controls capacitor banks only without main transformer tap regulation, adopting dual criteria of voltage + reactive power:

  1. Continuously monitor busbar voltage and reactive power
  2. Capacitor switching-in allowed only when both conditions are satisfied: Busbar voltage within permitted range + system inductive reactive power exceeds switch-in threshold → relay contact closes to drive vacuum contactor to switch capacitor in.
  3. When busbar voltage is too high or system becomes capacitive (reverse reactive power flow) exceeding switch-out threshold → relay contact opens to switch capacitor off.

Switching algorithms:

Equal-capacity banks: Balanced cyclic switching, equalize operation count of each bank to extend service life

Unequal-capacity banks: Adaptive combined switching, select optimal capacity combination according to reactive magnitude for higher compensation precision and avoid oscillation

Any faulty/maintenance capacitor bank is automatically masked; remaining banks keep automatic operation.

III. Blocking Protection Principle (Safety Core)

All models have multi-layer blocking. Once blocking condition triggers, capacitor switching-in is prohibited immediately; already-connected capacitors will be tripped if needed:

  1. Overvoltage Blocking: Busbar voltage>upper limit → block switching-in and trip capacitors to avoid capacitor overvoltage damage.
  2. Undervoltage Blocking: Busbar voltage<lower limit → prohibit capacitor switching-in; switching capacitors under low voltage may amplify resonance risk.
  3. Switch Position Blocking: When incoming/bus coupler switch opens, trip capacitors on this section and suspend automatic control.
  4. Hardware Watchdog & Self-diagnosis: On CPU crash, hardware circuit blocks all relay outputs directly to prevent false trip/close. Detect capacitor fail-to-open / fail-to-close, trigger alarm and isolate that bank.
  5. 스위칭 지연: Fixed waiting time after each action (10~30초), prevent cyclic switching oscillation caused by short-term grid fluctuations.
  6. Three Operation Modes
  7. Auto Mode: Controller samples, judges and executes automatic switching / tap regulation independently (normal running mode).
  8. Local Manual: Manual capacitor switching / tap raise-lower via panel keys, auto logic suspended, for commissioning and maintenance.
  9. 원격 제어: Backstage sends remote switch commands via Modbus; local auto logic exits under remote mode, protection blocking remains active.
  10. Series T (DWK3‑110TC Tap-regulated compensation, different principle)

Series T is not conventional stepwise capacitor switching. It adjusts taps of on-load autotransformer connected in series before capacitors, changing voltage across capacitors to continuously and smoothly vary reactive output. Capacitors do not need frequent switching, resulting in lower impact and longer service life.