ABB SACE Emax E1 Series Fixed-type Air Circuit Breaker, rated current 1600A, equipped with PR121/P microprocessor-based electronic trip unit and three-stage LSI protection function. Model Code Definition Segment Code Description E1N E1N Series identifier for ABB SACE Emax E1 fixed ACB; E1=series code, N=fixed mounting, B=draw-out mounting 16 16 Incoming frame current rating: 1600A frame ...

  • Product Details

ABB SACE Emax E1 Series Fixed-type Air Circuit Breaker, rated current 1600A, equipped with PR121/P microprocessor-based electronic trip unit and three-stage LSI protection function.

  1. Model Code Definition
SegmentCodeDescription
E1NE1NSeries identifier for ABB SACE Emax E1 fixed ACB; E1=series code, N=fixed mounting, B=draw-out mounting
1616Incoming frame current rating: 1600A frame size (8=800A, 10=1000A, 12=1250A, 16=1600A)
R1600R1600Rated current code: In=1600A (R800=800A, R1000=1000A, R1250=1250A, R1600=1600A)
PR121PR121Trip unit model: ABB PR121/P basic microprocessor trip unit supporting LI/LSI protection
LSILSIProtection type for three-stage protection: L=Long time delay (overload), S=Short time delay (short-circuit), I=Instantaneous (short-circuit)

 

  1. Core Technical Specification Table
CategoryDetailed ParametersStandards & Certifications
Basic Ratings• Product Series: SACE Emax E1IEC 60947-2
• Device Type: Air Circuit Breaker (ACB)GB 14048.2
• Mounting: Fixed typeCCC, CE, UL, CSA Approved
• Poles: Optional 3P/4P
• Frame Current (Iu): 1600A
• Rated Current (In): 1600A
• Trip Unit: PR121/P-LSI (3-stage protection)
• Rated Operational Voltage (Ue): 690V AC, 50/60Hz
• Rated Insulation Voltage (Ui): 1000V AC
• Rated Impulse Withstand Voltage (Uimp): 12kV
• Ultimate Short-circuit Breaking Capacity (Icu): 50kA@415V AC, 42kA@690V AC
• Rated Service Short-circuit Breaking Capacity (Ics): 50kA@415V AC (100% of Icu)
Mechanical & Electrical Performance• Mechanical Endurance: 10,000 operationsIEC 60947-1
• Electrical Endurance: 500 operations at rated short-circuit breaking capacity
• Control Supply Voltage: 220V AC/DC (standard), optional 110V/400V
• Operation: Motor spring charging + motor closing/tripping, manual emergency operation available
• Auxiliary Contacts: Standard 2NO+2NC, expandable up to 10NO+10NC
• Wiring Capacity: Copper busbar 10×100mm², cable up to 300mm²
• Tightening Torque for Bolts: 50N·m
Physical Dimension• Mounting: Vertical mounting (standard), optional horizontal mountingIEC 60529
• Overall Size(W×H×D): 296×302×418mm (3P fixed version)
• Weight: Approx.45kg (3P)
• Ingress Protection: IP30 for bare breaker, IP40 with enclosure
Ambient Conditions• Operating Temp: -5°C ~ +40°C (derating required above 40°C)IEC 60068-1
• Storage Temp: -25°C ~ +70°C
• Relative Humidity: 95% @25°C, non-condensing
• Pollution Degree: Class 3
• Altitude: ≤2000m (derating required over 2000m elevation)
Eco & Sustainability• Compliant with EU RoHS DirectiveABB Green Product Certification
• PFOS/PFOA free construction
• Recyclable material ratio ≥90%
• Low power consumption: Control circuit ≤15W
  1. Full Part Number List (E1N Series, 1600A Frame Size)
Part No.DescriptionRated CurrentProtection Type
1SDA055782R1E1N1600 R800 PR121/P-LI800ALI (2-stage: Long Delay + Instantaneous)
1SDA055783R1E1N1600 R1000 PR121/P-LI1000ALI
1SDA055784R1E1N1600 R1600 PR121/P-LI1600ALI
1SDA055785R1E1N1600 R800 PR121/P-LSI800ALSI (3-stage: Long+Short+Instantaneous)
1SDA055786R1E1N1600 R1600 PR121/P-LSI1600ALSI
1SDA055787R1E1N1600 R800 PR123/P-LSIG800ALSIG (4-stage + Earth Fault protection)
1SDA055788R1E1N1600 R1600 PR123/P-LSIG1600ALSIG

Full Series Coverage: Frame ratings 800A/1000A/1250A/1600A; Fixed(N)/Draw-out(B) mounting; LI/LSI/LSIG protection; 3P & 4P configurations available.

  1. Cross-Brand Equivalent & Replacement Options

4.1 In-brand ABB Replacement

Original ModelAlternative ModelSpecification Difference
E1N16-R1600-PR121-LSIE1B16-R1600-PR121-LSIDraw-out type for convenient maintenance, replaceable without power shutdown
E1N16-R1600-PR121-LSIE1N16-R1600-PR123-LSIGUpgraded to 4-stage LSIG with additional earth-fault(G) protection
E1N16-R1600-PR121-LSIE2N16-R1600-PR121-LSIE2 higher-grade series, breaking capacity raised to 65kA@415V AC

4.2 Cross-Brand Comparison Chart

ABBSchneider ElectricSiemensCHINT
E1N16-R1600-PR121-LSIMT16H1600 3P 5.03WL1116-3BB36-4AA0NA1-1600-1600M/3P
Breaking Capacity:50kA@415VBreaking Capacity:50kA@415VBreaking Capacity:50kA@415VBreaking Capacity:50kA@415V
LSI three-stage protectionLSI three-stage protectionLSI three-stage protectionLSI three-stage protection
PR121/P trip unitMicrologic 5.0 trip unit3WL electronic trip unitNA1 electronic trip unit
  1. Application Scope & Practical Cases

5.1 Recommended Application Fields

Industry SectorTypical UsageSelection Advantages
Industrial Power DistributionMain incoming feeder of factory, transformer secondary protection, large MCC50kA high breaking capacity, precise LSI selective coordination for complicated industrial environment
Commercial BuildingsMain distribution panel for shopping mall, hotel & office towerSpace-saving fixed mounting, motorized operation for remote control & easy maintenance
Data CenterUPS output & main power distribution for server roomLow power loss design, high reliability, capable of ATS interlock for redundant power supply
Critical InfrastructureMain protection for airport, metro, hospital vital loadsWide working voltage to resist grid fluctuation, fast fault isolation to minimize blackout range
New Energy IndustryLV side of step-up transformer in PV plant, combiner cabinet for energy storageExcellent harmonic withstand, customizable inverse-time protection curve matching new-energy characteristics

 

5.2 Non-recommended Applications

DC circuits: Select dedicated Emax DC series (e.g.E1N-DC)

Installation above 2000m altitude without current derating

Frequently switching loads: Adopt contactor + thermal overload relay combination instead

Severe environment with Pollution Degree 4: Extra enclosure protection required

5.3 Typical Application Cases

Case1: Main Distribution for Automobile Manufacturing Plant

Application: Secondary-side main protection for 10kV/0.4kV factory transformer (1600A)

Configuration: E1N16-R1600-PR121-LSI 3P fixed type with PR121/P-LSI trip unit

Performance: Realizes long-delay overload, short-delay & instantaneous short-circuit protection; forms selective coordination with downstream MCCB to limit fault outage area and improve power supply reliability.

Case2: UPS Output Distribution in Large-scale Data Center

Application: Main protection for 2000kVA UPS outgoing terminal

Configuration: E1N16-R1600-PR121-LSI 4P fixed type plus communication module for remote monitoring

Advantage: Low power consumption reduces UPS loading; optimized protection curve avoids unintended UPS tripping under short-circuit; communication function enables early fault alert & remote diagnosis.

  1. Common Troubleshooting Guide
Fault PhenomenonRoot CausesRemedial Actions
Failed motor closing1.Abnormal control supply1.Measure input control voltage
2.Uncompleted spring charging2.Await automatic charging or manual charge
3.Interlock not released3.Check rack position & cabinet door interlock
4.Faulty closing coil4.Test coil resistance and replace defective component
Abnormal trip unit display1.Failed internal power module1.Check auxiliary supply for trip unit
2.Broken CT wiring2.Tighten or repair open-circuited CT connections
3.Trip unit program error3.Power cycle trip unit; contact ABB service if fault persists
Unintentional frequent tripping1.Overload or downstream short-circuit1.Measure load current and clear short fault
2.Incorrect protection setting parameters2.Re-calibrate protection setting for selective coordination
3.Excessively high ambient temperature3.Improve cabinet ventilation & ambient cooling
4.Trip unit malfunction4.Verify trip performance or replace trip unit
Stiff manual operation1.Mechanism jamming by foreign matter1.Clean internal mechanism and reassemble
2.Fatigued operation springs2.Inspect charging/closing spring condition
3.Insufficient lubrication3.Apply specified lubricant per service manual

 

  1. Air Shipment Compliance & Certifications

7.1 Air Transport Regulation Compliance

Product Property: No built-in lithium battery/supercapacitor, classified as general electrical equipment

Shipping Classification: Non-dangerous goods compliant with IATA DGR regulations

Packaging: Standard wooden case with inner cushion padding against mechanical damage

Transport Note: Precision device; avoid severe shock & vibration during transit

7.2 Main Certifications List

CertificationCertificate No.Valid Market
CCC2.02101E+15Mainland China
CE0123/CEEU & EEA
ULE250000North America
CSA250000Canada
RoHSComply with Directive 2011/65/EUGlobal environmental restriction of hazardous substances
  1. Quick Selection Rules & Summary Tips

Quick Selection Rules

  1. Frame Current Identification: Digit “16” =1600A frame; 8=800A,10=1000A,12=1250A
  2. Rated Current Lookup: Rxxx = nominal In; R800=800A, R1000=1000A, R1250=1250A, R1600=1600A
  3. Protection Code Definition: LI=2-stage, LSI=3-stage, LSIG=4-stage with earth fault
  4. Mounting Code: N=Fixed type, B=Draw-out type
  5. Breaking Capacity Grade: E1=50kA@415V; E2=65kA@415V