Mini-MW W2YV Compact Dual-Output Isolator
M-SYSTEM (Japan), DIN rail mount, 4-way galvanic isolation (Input / Output1 / Output2 / Power supply). Designed for 4~20mA industrial signal isolation, ground loop interference suppression and 1-input 2-output signal distribution.
✅ Model Decoding W2YV-AAA-M
W2YV ①②③ ④
- ① A: Input signal = DC 4~20mA (Input resistance: 250Ω)
- ② A: Output 1 = DC 4~20mA (Max load ≤750Ω)
- ③ A: Output 2 = DC 4~20mA (Max load ≤350Ω)
- ④ M: Power supply = AC 85~264V wide-range AC (47~66Hz)
Full definition: 4~20mA input, two independent isolated 4~20mA outputs, AC85-264V powered signal distribution isolator
📋 Core Technical Specifications
| Item | Specifications |
| Isolation Structure | Galvanic isolation between Input / OUT1 / OUT2 / Power supply |
| Accuracy | ±0.1% FS |
| Temperature Drift | ±0.015% /℃ |
| Response Time | ≤0.5s (0~90%) |
| Withstand Voltage | 2000V AC, 1 minute (between each isolation barrier) |
| Insulation Resistance | ≥100MΩ @500VDC |
| Zero / Span Adjustment | Front panel independent trimming; separate ZERO/SPAN adjustment for two outputs |
| Mounting | DIN rail, dense side-by-side installation for high-density cabinet layout |
| Overall Dimensions | W29.5 × H88.5 × D124 mm |
| Terminals | M3 screw, tightening torque 0.8 N·m |
| Operating Environment | -5 ~ +55℃, 30~90%RH (non-condensing) |
| Power Consumption | Approx. 4VA @AC100V; Approx. 6VA @AC240V |
| Weight | Approx. 200g |
🎯 Typical Applications
- Eliminate ground loop interference between PLC and transmitters
- Distribute one 4~20mA measurement signal to PLC + recorder / indicator (1-input 2-output signal splitting)
- Provide galvanic isolation between field transmitters and control room systems to protect AI modules
- Impedance conversion for parallel acquisition by multiple receiving instruments
⚙️ Selection & Replacement Information
Same series DC powered variant: W2YV-AAA-R2 (DC11~27V supply)
Domestic alternatives: Yutong, Chenzhu, Wanxun and other 1-in-2-out 4-20mA isolators (compare isolation rating, accuracy and temperature drift)
Note: The two current outputs have different maximum load limits. OUT2 max load is only 350Ω. Use OUT1 for high-load applications.
📌 Troubleshooting Guide
- Inaccurate output: Recalibrate ZERO/SPAN on front panel; check 250Ω matching resistor on input loop
- No output signal: Verify AC supply 85~264V; check tightness of M3 terminal screws
- Signal drift: Check earthing; ensure input side ground is separated from PLC ground. The isolator is used to break common ground.
- Excessive voltage drop under load: Connect the load to OUT1 channel (OUT1 has higher load capacity)
W2YV (Mini-MW Dual-Output Signal Conditioner) Complete Model Code + Common Model List
W2YV = W2YV-①②③-④⑤
①: Input signal; ②: OUT1 output; ③: OUT2 output; ④: Power supply; ⑤: Optional suffix
Code Definition
① Input Code
A: DC 4~20mA, input resistance 250Ω
6: DC 1~5V, input impedance ≥1MΩ
② OUT1 (Channel 1, higher load capacity: Max 750Ω)
A: DC 4~20mA
6: DC 1~5V
③ OUT2 (Channel 2; Max 350Ω for current output; ≥5kΩ for voltage output)
A: DC 4~20mA
6: DC 1~5V
Y: No output (single-output mode)
④ Power Code
M: AC85~264V (Wide AC)
R2: DC11~27V (24V DC supply)
⑤ Options (Suffix /Q, multiple options can be combined)
C01: Silicone coating (moisture & dust protection)
C02: Polyurethane coating
C03: Rubber coating
V01: Multi-turn trim potentiometer
S01: Stainless steel terminal screws
✅ Common Available Models of W2YV Series
- W2YV-AAA-M: 4~20mA input, dual 4~20mA outputs, AC85~264V (your target model)
- W2YV-AAA-R2: 4~20mA input, dual 4~20mA outputs, DC11~27V
- W2YV-6AA-M: 1~5V input, dual 4~20mA outputs, AC supply
- W2YV-6AA-R2: 1~5V input, dual 4~20mA outputs, DC supply
- W2YV-A6A-M: 4~20mA input, OUT1=1~5V, OUT2=4~20mA, AC supply
- W2YV-AA6-M: 4~20mA input, OUT1=4~20mA, OUT2=1~5V, AC supply
- W2YV-6A6-M: 1~5V input, OUT1=4~20mA, OUT2=1~5V, AC supply
- W2YV-A66-R2: 4~20mA input, dual 1~5V voltage outputs, DC supply
- W2YV-AAY-M: 4~20mA input, OUT1=4~20mA only, OUT2 no output (single output)
- W2YV-666-R2: 1~5V input, dual 1~5V voltage outputs, DC supply
📌 Other W2 Family Models (Same DIN rail housing as W2 series)
W2XF: Arithmetic signal conditioner (addition / subtraction calculation)
W2VABS: Absolute value signal converter
W2RS: RTD resistance temperature detector isolator
W2YV is only for DC mA/V signal 1-in-2-out isolation and distribution. For temperature measurement or arithmetic functions, select other W2 series models above.
⚠️ Important Selection Notes
- Mixed output (one current + one voltage): Place current signal on OUT1. OUT1 has higher load capacity (750Ω vs 350Ω of OUT2)
- Coated versions C01 are recommended for high-humidity and chemical cabinet environments
- Side-by-side dense DIN installation; no heat dissipation gap required, which is the key advantage of this series
W2YV‑AAA‑M (M-SYSTEM) Overall Dimensions
Width(W) × Height(H) × Depth(D) = 29.5 mm × 88.5 mm × 124 mm
Inch: 1.16″ × 3.48″ × 4.88″
Supplementary Dimension Information
- DIN rail mounting: 35mm standard DIN rail. Modules can be closely mounted side by side, no heat dissipation gap required between modules, ideal for high-density cabinet arrangement
- Weight: Approx. 200g
- Mounting method: DIN rail clip mounting, or base plate screw fixing (2×Φ4.2 mounting holes)
- Terminals: M3 screw terminals. The terminal block protrudes forward; above dimensions refer to maximum overall outline of the unit.
W2YV‑AAA‑M Input Signal Description
For model W2YV-AAA-M specifically: Input is fixed as DC 4~20mA (1st character A), input resistance 250Ω
All Optional Input Types of W2YV Series (1st character in model code)
- A: DC 4~20mA (Current Input)
Input resistance: 250Ω
This is the input specification of your W2YV-AAA-M
- 6: DC 1~5V (Voltage Input)
Input impedance ≥1MΩ, high-impedance voltage acquisition
⚠️ Important: W2YV series only has these two factory fixed input ranges. It is NOT programmable. It cannot be modified on-site for 0-10V, 0-20mA, thermocouple or RTD signals. If temperature measurement or multi-range programmable function is required, select other W2 series models such as W2XF.
Brief Comparison
| Code | Signal Type | Input Impedance |
| A | DC 4~20mA | 250Ω |
| 6 | DC 1~5V | ≥1MΩ |
Supplement
The input range of W2YV is locked at factory by model coding. It cannot be changed by hardware jumpers on site. Only A (4~20mA) or 6 (1~5V) can be selected during ordering.
Contactor,circuit breaker,sensor,Encoder,PLC,Converter