OMRON MY2N-GS AC220V Intermediate Relay

The OMRON MY2N-GS AC220V is a 2-pole double-throw (DPDT) plug-in miniature intermediate relay from OMRON MY-GS series. It is the official upgraded replacement for the classic legacy model MY2N-J. Standard configurations include an LED operation indicator, mechanical status indicator and manual test locking lever. Adopting silver alloy contacts, it features high reliability, long service life ...

  • Product Details

The OMRON MY2N-GS AC220V is a 2-pole double-throw (DPDT) plug-in miniature intermediate relay from OMRON MY-GS series. It is the official upgraded replacement for the classic legacy model MY2N-J. Standard configurations include an LED operation indicator, mechanical status indicator and manual test locking lever. Adopting silver alloy contacts, it features high reliability, long service life and convenient wiring. Mainly used for PLC output signal amplification, load switching and circuit logic conversion, it is a universal fundamental component for industrial automation control cabinets.

  1. Model Code Breakdown

Full standard model: MY2N-GS AC220/240V

MY: Product series, general-purpose miniature power intermediate relay

2: Number of contact sets, 2 sets of changeover contacts (DPDT, 2 Normally Open + 2 Normally Closed)

N: Standard plug-in terminals with built-in operation indicator

GS: Next-generation series (Generation Standard). It replaces the original MY2N-J series, is equipped with an additional locking lever, and delivers optimized contact durability and electrical performance.

AC220/240V: Rated coil voltage, AC 220~240V, compatible with 50/60Hz power supply.

Supplementary Notes

Most products available on the market are fitted with a locking lever by default (suffix -R), supporting manual testing and contact locking.

Matched standard 8-pin socket: Screw terminal type PYF08A, push-in terminal type PYF08A-PU.

  1. Main Technical Specifications
CategorySpecifications
Contact Configuration2 sets of changeover contacts (DPDT, 2NO+2NC)
Rated Contact Current5A (AC250V resistive load); 5A (DC30V resistive load)
Contact MaterialSilver alloy (AgSnO₂)
Rated Coil VoltageAC 220~240V, 50/60Hz
Coil Power ConsumptionApprox. 1.2~1.5 VA
Operate Time≤ 20 ms
Release Time≤ 20 ms
Mechanical Life≥ 50 million operations
Electrical Life≥ 100,000 operations (under rated resistive load)
Dielectric Withstand Voltage2kV AC / 1min (between coil and contacts)
Status IndicationRed LED indicator (lights up when energized) + Mechanical indicator lever
Mounting TypePlug-in type, used with matched standard socket
Number of Pins8 pins
Operating Ambient Temperature-40℃ ~ +70℃ (No condensation)
Ingress ProtectionIP40 (Relay body)
CertificationsCE, UL, CSA, VDE, CQC
  1. Full Model List of the Same Series

4.1 Classified by Contact Sets

Contact SetsPin CountStandard ModelModel with Locking LeverRated Contact Current
2 changeover contacts (2NO+2NC)8 pinsMY2N-GSMY2N-GS-R5A
4 changeover contacts (4NO+4NC)14 pinsMY4N-GSMY4N-GS-R5A

4.2 Common Coil Voltage Ratings

The entire series supports the following standard voltages, distinguished only by voltage suffix:

DC: DC12V, DC24V, DC48V

AC: AC24V, AC110/120V, AC200/220V, AC220/240V

  1. Pin Assignment & Wiring Instructions

5.1 Pin Definition (Top view from the wiring side of the socket)

Pin No.FunctionDescription
13 (A1)One end of coilConnect to AC220V live wire
14 (A2)The other end of coilConnect to AC220V neutral wire
9Common terminal 1 (COM1)Common pin for the 1st contact set
1Normally Closed 1 (NC1)Conducts with Pin 9 when coil is de-energized
5Normally Open 1 (NO1)Conducts with Pin 9 when coil is energized
12Common terminal 2 (COM2)Common pin for the 2nd contact set
4Normally Closed 2 (NC2)Conducts with Pin 12 when coil is de-energized
8Normally Open 2 (NO2)Conducts with Pin 12 when coil is energized

5.2 Wiring Precautions

  1. The AC coil has no polarity requirement. A1 and A2 can be connected to live wire and neutral wire arbitrarily.
  2. For inductive loads (contactors, solenoid valves), it is recommended to connect a surge suppressor (RC snubber circuit) in parallel to extend contact service life.
  3. Do not operate beyond the rated current. Use contactors for secondary switching of high-power loads.
  4. The locking lever can manually close the contacts, which is applied to power-off commissioning and circuit inspection.
  5. Typical Applications

Amplify PLC output signals to drive loads such as solenoid valves, contactors and indicator lights

Circuit logic conversion, level matching and signal isolation inside control cabinets

Start-stop control, signal relay and circuit expansion for automated equipment

Secondary circuit control and protection signal transmission in power distribution systems

  1. General Troubleshooting Matrix
Fault PhenomenonRoot CauseStep-by-Step Solutions
Relay fails to operate and indicator stays off after power-on1. Abnormal supply voltage / Broken wiring1. Measure voltage between A1 and A2 to confirm normal AC220V supply
2. Burned-out open coil2. Test coil resistance; replace the relay if an open circuit is detected
3. Poor contact with socket3. Re-insert the relay and clean socket pins
Indicator lights up but contacts have no output1. Welded or oxidized contacts with poor conduction1. Test contact continuity; replace the relay if contacts are damaged
2. Broken wiring on load side2. Check wiring and integrity of the load circuit
3. Damaged contacts due to overload3. Verify load current; select a higher-rated model for overload conditions
Contacts fail to release and stick together after power-off1. Contact welding caused by electric arc under heavy current1. Replace the relay and install surge suppression components
2. Mechanical jam or failed return spring2. Inspect internal mechanism; replace the whole relay if mechanical jam occurs
Abnormal buzzing noise during operation1. Incomplete armature attraction due to low voltage1. Adjust supply voltage to the rated range
2. Oil or dust on core surface2. Replace the relay; do not disassemble the core manually
Excessive heating or burnout of coil1. Overvoltage power supply1. Ensure supply voltage complies with rated value; overvoltage operation is prohibited
2. Long-term high-frequency switching2. Reduce switching frequency or adopt solid state relays
  1. Reference of Alternative Models

Original brand legacy replacement: MY2N-J AC220V (Fully pin-compatible, without locking lever)

Domestic alternatives: Chint NJX-13FW/2Z AC220V, Delixi CDZ9-52P AC220V

Imported equivalents: Schneider RXM2LB2P7, ABB CR-MX230AC2L, Phoenix Contact REL-MR-230AC/21

Troubleshooting Matrix for OMRON MY2N-GS AC220V 5A Relay

This model features 2 sets of changeover contacts, 8-pin plug-in structure, LED operation indicator and locking lever. Below is the troubleshooting guide sorted by on-site inspection sequence (from simple to complex), covering faults caused by electrical, mechanical and installation issues.

Fault PhenomenonRoot CauseStep-by-Step Solutions
No operation and red LED indicator off after power-on1. Fault in external power circuit: No voltage, loose wiring, broken live/neutral wire1. Measure AC voltage between socket Pin 13(A1) and Pin 14(A2). Confirm voltage within AC220V±10%. Check upstream switches and terminals if no voltage is detected.
2. Poor socket contact: Oxidized pins or loose connection between relay and socket2. Cut off power, pull out the relay, clean oxide on pins and socket terminals, then reinsert firmly.
3. Burned-out open coil: Overvoltage breakdown, insulation aging or surge impact3. Measure coil resistance. The normal resistance is approx. 12~15kΩ at 25℃. Replace the relay if open circuit or abnormal resistance occurs.
4. Locking lever stuck at release position (for -R version)4. Reset the top locking lever to normal position to eliminate mechanical jam.
LED lights up but contacts have no output1. Wrong wiring for contact circuit: Mixed connection of common, NO and NC terminals1. Verify pin definition: COM terminals are Pin 9 and Pin 12; NO terminals are Pin 5 and Pin 8. Ensure no wrong connection to NC pins.
2. Broken load circuit: No power for load or loose terminals2. Press the locking lever to manually close contacts and test continuity. If still open, inspect power and wiring on load side.
3. Burned or oxidized contacts caused by long-term overload and electric arc3. Replace the relay if contacts remain open due to burnout or oxidation after manual closing.
4. Internal mechanism jam: Coil pulls in normally but linkage fails to drive contacts4. Replace the relay if mechanical jam is found during manual operation.
Contacts stay closed and cannot release after power-off1. Contact welding: Caused by overload, short circuit or electric arc without surge suppression for inductive loads1. Cut off power and confirm no voltage on coil. Reset locking lever and check if contacts open.
2. Failed return spring: Elasticity attenuation due to frequent switching and high temperature2. Replace the relay immediately if contacts are still closed after reset. Welded contacts cannot be repaired for reuse.
3. Foreign matter jam: Dust or iron chips stuck inside armature or contact mechanism3. Ensure load current does not exceed 5A. Install RC surge suppressor for inductive loads.
4. Accidental lock of locking lever after manual test4. Clean surrounding dust and iron chips; replace the relay if mechanical jam cannot be fixed.
Abnormal buzzing noise during operation1. Low supply voltage leads to incomplete core attraction and armature vibration1. Measure coil voltage and keep it within AC220V±10%. Check voltage drop in power circuit if voltage is low.
2. Oil, dust or rust on core surface resulting in excessive magnetic gap2. Reinsert the relay fully and tighten fixing screws of socket and rail.
3. Broken short-circuit ring on core (unique fault of AC coil)3. Replace the relay if noise persists after cleaning core surface (damaged short-circuit ring or worn core).
4. Loose fit between relay, socket and DIN rail causing resonance4. Adjust mounting position to eliminate resonance gap.
Excessive heating or black burnout of coil1. Severe overvoltage exceeding upper limit AC240V leading to coil overload1. Monitor supply voltage strictly; long-term overvoltage operation is forbidden.
2. Excessively high switching frequency causes cumulative overheating beyond Class B insulation limit2. Limit switching frequency ≤ 20 times per minute. Use solid state relay for high-frequency working conditions.
3. Poor heat dissipation under high ambient temperature accelerates insulation aging3. Improve heat dissipation inside cabinet. Keep away from heat-generating components such as inverters and contactors. Ambient temperature shall not exceed 70℃.
4. Insulation breakdown caused by overvoltage and surge4. Connect RC surge suppressor in parallel with coil to suppress transient overvoltage during power-off.
Poor contact, intermittent signal1. Oxidation and dust on contact surface leading to high contact resistance1. Cut off power, pull out the relay, clean oxide on contacts and pins, then insert tightly.
2. Too low load current cannot break through oxide layer (low-level signal circuit)2. Use gold-plated contact relay or properly increase circuit current for low-level signal applications.
3. Fatigue or oxidation of socket pins causing loose connection3. Replace matched PYF08A socket if pins lose elasticity or are severely oxidized.
4. Incomplete insertion of relay leading to mechanical intermittent contact4. Replace with a new relay if intermittent fault occurs frequently to prevent repeated oxidation.
Abnormal brightness or flickering of indicator1. Unstable power supply with large voltage fluctuation1. Measure coil voltage and confirm stable power supply without severe fluctuation.
2. Poor socket contact leading to intermittent coil power supply2. Reinsert the relay and clean pins to eliminate loose contact.
3. Aging and failure of current-limiting resistor for indicator3. Measure coil resistance if indicator malfunctions under stable voltage. Replace the relay immediately if inter-turn short circuit (low resistance) is detected.
4. Coil inter-turn short circuit causing abnormal voltage division4. Temporary use is allowed if only indicator fails while contacts work normally. Batch replacement is recommended.

Supplementary Troubleshooting Notes

  1. Inspection Priority: Follow the sequence: External power supply → Socket contact → Relay body. 80% of faults are caused by wiring and socket problems. Prioritize these checks to avoid unnecessary replacement.
  2. Safety Regulations: Comply with electrical safety standards during live tests. Cut off power before inspecting contacts and coils to prevent electric shock and short circuit.
  3. Service Life Reference: The rated electrical life is 100,000 operations under resistive load. The service life will decrease by more than 50% for inductive loads. Regular replacement is recommended when the service limit is reached.