PILZ 777301 Safety Relay - Contactor,circuit breaker,sensor,Encoder,PLC,Converter

Wechat: +86-13184948252  WhatsaApp: 0086-13811255435  E-mail:  kent@bestcontactor.com

About    Contact    |    

 PILZ 777301 Safety Relay - Contactor,circuit breaker,sensor,Encoder,PLC,Converter

PLC/

 PILZ 777301 Safety Relay

Order No.: 777301 Product Name: PNOZ X2.8P Supply Voltage: 24 V AC/DC Mounting: DIN rail mounting Housing Width: 22.5 mm Terminals: Plug-in screw terminals Certifications: TÜV, CE, cULus, CCC Safety Specifications Safety Outputs: 3 NO positive-guided safety contacts + 1 NC auxiliary contact Safety Level: PL d / Cat.3 / SIL2 (EN ISO 13849-1) Input: ...

  • Product Details

Order No.: 777301

Product Name: PNOZ X2.8P

Supply Voltage: 24 V AC/DC

Mounting: DIN rail mounting

Housing Width: 22.5 mm

Terminals: Plug-in screw terminals

Certifications: TÜV, CE, cULus, CCC

Safety Specifications

Safety Outputs: 3 NO positive-guided safety contacts + 1 NC auxiliary contact

Safety Level: PL d / Cat.3 / SIL2 (EN ISO 13849-1)

Input: Dual-channel safety input, with short-circuit detection

Start Mode: Automatic start / Monitored manual start (selectable via wiring)

Typical Applications: Emergency stop, safety gate, safety interlock monitoring

Contact Ratings

AC1 240 V: 6 A, 1500 VA

DC1 24 V: 6 A, 150 W

AC15 230 V: 5 A

DC13 24 V: 4 A

Comparison with 777303 (PNOZ X2P)

ModelOrder No.Short-Circuit DetectionTerminal Type
PNOZ X2.8P777301✅ Dual-channel short-circuit detectionPlug-in screw terminals
PNOZ X2P777303✅ Dual-channel short-circuit detectionPlug-in screw terminals

Replacement Models

Direct upgrade replacement: PNOZ S2 (750102) (PNOZsigma series), identical functions, compact size, enhanced diagnostic functions

Spring-cage terminal version: No native spring-cage variant for X series; select PNOZsigma series directly.

Supplementary Notes

The PNOZ X series is a legacy product and gradually phased out. The P-version supports wire short-circuit diagnosis; if two signal wires short out, the relay will detect the fault and refuse to activate, greatly improving safety.

Complete Model List of PILZ PNOZ X Series (Obsolete Legacy Range)

Prefix Coding Rule (Terminal Differentiation)

774xxx: Fixed screw terminals (basic non-P models, no short-circuit detection)

777xxx: Plug-in screw terminals (enhanced P-models, with short-circuit detection)

787xxx: Spring-cage terminals (C-type, corresponding to 777xxx models)

Non-P suffix: No dual-channel short-circuit detection; P suffix: Dual-channel short-circuit detection available

  1. Basic Non-P Range (774xxxx, Fixed Screw Terminals)

1) PNOZ X1 (Single-channel, 3NO+1NC)

774300 PNOZ X1 24 V AC/DC

2) PNOZ X2 (Dual-channel, 2NO, no short-circuit detection)

774301 PNOZ X2 24 V AC/DC

3) PNOZ X3 (Dual-channel, 3NO+1NC + 1 semiconductor output)

774310 24 V AC/DC

774311 42 V AC

774312 48 V AC

774314 110–120 V AC

774315 230–240 V AC

4) PNOZ X4 (3NO+1NC)

774736 110–120 V AC

5) PNOZ X6 (3NO)

774721 42 V AC

774725 110–120 V AC

774726 230–240 V AC

6) PNOZ X7 (Single-channel, 2NO)

774049 48 V AC

7) PNOZ X10 (High-capacity 6NO+4NC)

774700 24 V AC (for vibration-intensive equipment)

  1. Quick Selection Table by Application (High-Frequency Models)
ApplicationRecommended ModelOrder No.Key Features
Dual-channel E-STOP, short-circuit detection, automatic resetPNOZ X2.8P777301Auto start, 3NO+1NC, plug-in terminals
Dual-channel E-STOP, short-circuit detection, mandatory manual resetPNOZ X2.7P777305Monitored start only, prevents unexpected restart
General E-STOP / safety gate, auto/manual start selectablePNOZ X2P7773032NO, wiring-selectable mode, best-selling spare part
PNP safety light curtain (OSSD, curtain with built-in short-circuit diagnosis)PNOZ X2774301No relay short-circuit detection, avoids signal conflict with light curtain
Safety gate with PLC feedback signalPNOZ X3P7773103NO+1NC + 1 PNP semiconductor output
Multiple contactors to be cut off simultaneously, multi-power circuitsPNOZ X107747006NO+4NC high-capacity contacts
Low-risk single-channel protectionPNOZ X7 / X7P774049 / 777059Single-channel 2NO contacts
  1. Critical Selection Restrictions & Common Pitfalls
  2. Do NOT enable short-circuit detection when using PNP OSSD safety light curtains

Light curtains already have built-in pulse diagnosis. Enabling short-circuit detection on X2P/X2.8P will cause pulse conflict and continuous fault alarms. Turn off the relay’s short-circuit monitoring in this case.

  1. Auxiliary NC contact (41-42) cannot be used in safety circuits

Only for PLC fault alarm and indicator feedback.

  1. Contact load limits

AC15 230 V max. 5 A; DC13 24 V max. 4 A. If contactor coil current exceeds the rating, use PZE contact expansion modules. Do not drive heavy loads directly via safety contacts.

  1. No time-delayed safety outputs in X series

For delayed stop applications, select PNOZ XV series instead.

  1. Two-hand control function

Prefer X3P or PNOZ S6; basic X models do not support two-hand logic.

  1. Obsolete Model Replacement Table (Spare Part Replacement & New Projects)
Obsolete PNOZ X ModelRecommended PNOZsigma ReplacementRemarks
PNOZ X2 (774301)PNOZ S2 (750102)Dual-channel, PL d, 2NO contacts
PNOZ X2P (777303)PNOZ S2 (750102)Fully equivalent function; S series includes native short-circuit detection
PNOZ X2.8P (777301)PNOZ S3 (750103)Automatic start, 3NO+1NC
PNOZ X2.7PPNOZ S3 (750103)Change wiring to enable monitored manual reset
PNOZ X3PPNOZ S4 (750104)With semiconductor feedback output
PNOZ X10PNOZ S10 (751104)High-capacity multi-contact version
  1. Pre-Order Selection Checklist

Confirm PL / Cat / SIL requirement: X series max. PL d / Cat.3 / SIL2; not applicable for PL e / Cat.4 / SIL3 applications

Input device type: E-STOP / safety gate → select P-model with short-circuit detection; PNP light curtain → disable short-circuit detection

Reset logic: Automatic start / Monitored manual start

Number of safety NO contacts required; whether semiconductor feedback to PLC is needed

Supply voltage; terminal preference (screw / spring-cage)

Load current; confirm whether PZE contact expansion modules are required

  1. Selection Mnemonic

E-stop & safety gate choose P-version;

Turn off short-circuit detection for light curtains;

Auto reset → X2.8P, mandatory reset → X2.7P;

X2P works for both modes; X3P provides PLC feedback;

X series only for spare parts; new projects use S-series directly.