Schneider GV3P50 Motor Circuit Breaker

The Schneider GV3P50 motor circuit breaker is an ideal choice for protecting 22kW three-phase motors. Featuring thermal-magnetic tripping, an adjustable current range of 37–50A, a breaking capacity of 100kA and IP20 ingress protection rating, it is widely deployed in industrial automation, fluid conveyance, building facilities and other sectors. Key points: match breaker rating to motor ...

  • Product Details

The Schneider GV3P50 motor circuit breaker is an ideal choice for protecting 22kW three-phase motors. Featuring thermal-magnetic tripping, an adjustable current range of 37–50A, a breaking capacity of 100kA and IP20 ingress protection rating, it is widely deployed in industrial automation, fluid conveyance, building facilities and other sectors. Key points: match breaker rating to motor power and operating conditions; avoid non-recommended applications including DC circuits, high-frequency starting and high-altitude environments. Combined with contactors and auxiliary contacts, it forms a complete motor protection and control system.

Code SegmentDefinitionDetailed Description
GV3Product SeriesTeSys GV3 range motor circuit breakers for three-phase motor protection
PProduct TypeStandard thermal-magnetic trip unit with rotary knob operation
50Rated CurrentMax adjustable trip current 50A; thermal trip setting range: 37–50A
Full ModelGV3P503-pole thermal-magnetic motor breaker, 37–50A, EverLink BTR screw terminals, IP20
Order CodeFD6887Schneider official standard part number
  1. Core Technical Specification Table
Parameter CategoryTechnical DataRemarks
Basic Parameters
Pole Configuration3P (3-pole)For three-phase AC circuits
Trip TypeThermal-MagneticCombines thermal overload protection & magnetic short-circuit protection
Operation ModeRotary Knob ControlManual switching with ON/OFF marking
TerminationEverLink BTR screw-clamp terminalsFast wiring to reduce loose connection risks
Electrical Parameters
Thermal Trip Adjustment37–50ACompatible with motors of different rated powers
Rated Operational Voltage (Ui)690V AC50/60Hz
Rated Insulation Voltage (Ue)690V ACCompliant with IEC 60947-2
Rated Operational Current (Ie)50AMaximum continuous operating current
Magnetic Trip Current700AShort-circuit instantaneous tripping value
Ultimate Breaking Capacity (Icu)100kAAt 400V
Matched Motor Rating22kW @ 400VFor three-phase asynchronous motors
Mechanical & Ambient Parameters
Ingress ProtectionIP20Finger-touch safe against live components
MountingDIN rail mountingStandard 35mm top-hat rail
WeightApprox. 0.45kgEasy installation & transportation
Operating Temperature-25°C ~ +60°CSuitable for most industrial environments
Storage Temperature-40°C ~ +85°CWide storage temperature range
Certifications
Main ApprovalsCE, UL, CSA, CCC, EACGlobally certified per international standards
Eco CertificationsRoHS, REACHEU-compliant environmentally friendly design

III. Full GV3P Series Model List

ModelThermal Trip RangeMatched Motor Power @400VMagnetic Trip CurrentOrder Code
GV3P4025–40A18.5kW600AFD6886
GV3P5037–50A22kW700AFD6887
GV3P6548–65A30kW800AFD6888
GV3ME5037–50A22kW700AFD6890
GV3ME6548–65A30kW800AFD6891
GV3ME8056–80A37kW1000AFD6892
GV3ME10070–100A45kW1200AFD6893
  1. Alternative Cross Reference (Replacement Models)
  2. In-house Schneider Replacement
Original ModelReplacementDescription
GV3P50GV3ME50Identical performance; ME is enhanced version with better accessory compatibility
GV3P50New production GV3P50No functional change, only production batch update
  1. Cross-Brand Equivalents
BrandEquivalent ModelMatching GradeAdvantages
ABBMS132-50★★★★★Same current rating, interchangeable mounting dimension
Siemens3RV2031-4KA10★★★★☆Thermal-magnetic trip, fits 22kW motors
EatonPKZM0-50★★★★☆3-pole design, 100kA breaking capacity
ChintNDM2-63M/3300★★★☆☆Cost-effective for bulk replacement
DelixiCDM1-63M/3300★★★☆☆Well-known domestic brand with high cost-performance
  1. Application Environments & Field Cases
  2. Recommended Applications

Industrial Automation: Overload & short-circuit protection for 3-phase asynchronous pumps, fans and compressors

Manufacturing: Production line motor control & machine tool protection

Building Electrical: Central air-conditioning & fire-fighting pump control

Energy Sector: Front-end protection for small generator sets and inverters

Infrastructure: Wastewater treatment equipment & bulk material conveying systems

  1. Non-Recommended Applications

DC Circuits: Designed exclusively for AC; abnormal tripping characteristics under DC supply

Ultra-Frequent Cycling: Not applicable for >30 starts per hour (accelerates trip unit aging)

High Altitude: Derating mandatory above 2000m elevation

Corrosive Atmosphere: No anti-corrosion coating; unsuitable for strong acid/alkali surroundings

  1. Typical Application Cases

Case 1: Fan System Protection for Food Processing Plant

Equipment: 3×22kW centrifugal fans, 380V/50Hz

Solution: GV3P50 + LC1D65 contactor combination

Outcome: Triple protection against overload, short-circuit & phase loss; equipment failure rate reduced by 40%

Case 2: Submersible Sewage Pump Control at Wastewater Plant

Equipment: 4×22kW submersible sewage pumps, 380V/50Hz

Solution: GV3P50 + auxiliary contacts + PLC interlock control

Outcome: Full motor protection plus remote monitoring, lower maintenance expense

  1. Air Shipment Compliance & CE Certification
  2. Air Freight Compliance

UN38.3: Not required; no built-in lithium battery or supercapacitor inside

Shipping Class: General commodity without special transport restriction

Packing: Standard industrial carton to avoid transit damage

Shipping Document: Copy of CE certificate + RoHS compliance declaration available

  1. CE Certification Details

Applicable Standards: IEC 60947-2 (LV switchgear) & IEC 60947-4-1 (motor control equipment)

Valid Region: European Economic Area (EEA) & global territories accepting CE marking

Validity: Permanently valid complying with current normative requirements

Inquiry: Check Schneider official website product page or certification database

VII. Common Fault Troubleshooting

Fault SymptomProbable CausesRemedial Actions
Frequent thermal tripping1. Motor overload1. Inspect motor load
2. Underset trip current2. Adjust rotary knob to correct setting
3. Excess ambient temperature3. Improve ventilation or derate operating current
Unable to close1. Tripping latch not reset1. Toggle knob OFF then ON to reset
2. Short circuit in wiring2. Troubleshoot short-circuit faults
3. Mechanical jamming3. Clean or replace breaker
No protection upon phase loss1. Wrong wiring1. Recheck three-phase cabling
2. Damaged trip unit2. Replace trip component
3. Severe 3-phase unbalance3. Balance connected loads
Overheated terminals1. Loose terminals1. Retighten terminal screws
2. Undersized cable2. Upgrade to proper wire gauge
3. Terminal oxidation3. Clean terminals or replace unit

VIII. Sizing Guidelines & Quick Selection Rules

Quick Selection Formula Summary

> GV3P series 3-pole thermal-magnetic breakers;

> Suffix number denotes upper current limit;

> 40 = 25–40A, 50 =37–50A, 65 max at 65A;

> Power matching rule: 40 for 18.5kW, 50 for 22kW, 65 for 30kW.

Quick Rules

  1. Current Matching: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
  2. Power Reference: At 400V, GV3P50 matches 22kW motor (~44A nominal)
  3. Accessory Option: Auxiliary contact: GV3AE11 (1NO+1NC) / GV3AE20 (2NO)
  4. Mounting Spacing: DIN rail install; ≥10mm clearance for heat dissipation, away from heat-generating devices
  5. Installation & Wiring Instruction
  6. Installation Steps

Confirm standard 35mm DIN rail

Snap breaker firmly onto rail

Incoming power: top-feed or bottom-feed acceptable

Motor cable connection: terminal tightening torque 2.5Nm recommended

  1. Wiring Specification

Wire cross-section range: 1.5mm² min ~35mm² max

Terminal: EverLink BTR screw terminal compatible with copper/aluminum conductors

Phase marking: R/S/T corresponds to L1/L2/L3; no neutral connection (3P without N pole)

  1. EMC Protection

Maintain ≥50mm clearance between breaker and contactors

Separate control wiring from power cables to avoid cross-interference

Install EMC filter if needed for EMI suppression

Full Application Overview for Schneider GV3P50 Motor Circuit Breaker

  1. Core Application Summary

Schneider GV3P50 is a 3-pole thermal-magnetic motor circuit breaker with adjustable trip 37–50A, rated for 22kW three-phase asynchronous motors @400V. Its core functions: motor overload, short-circuit & phase-loss protection plus manual switching, widely used in below industries:

  1. Detailed Application Classification
  2. Industrial Automation & Manufacturing
ApplicationEquipmentProtection RequirementApplication Benefit
Production Line ControlConveyors, sorters, packaging machinesContinuous running protection against overload shutdownImprove line stability & reduce breakdown loss
Machine ToolsMilling, lathe & grinder spindle motorsProtection for frequent start-stop & instant short-circuit breakingProtect costly equipment and extend service life
Bulk HandlingBucket elevators, screw conveyorsStall & phase-loss protectionPrevent burnout & cut maintenance cost
General MachineryPrinting, textile & plastic processing machinesOverload protection + emergency manual cut-offSimplify control circuit & enhance operational safety
  1. Fluid Conveyance Systems
ApplicationEquipmentProtection FeatureTypical Parameter
Pump SetIndustrial pump, fire pump, sewage pumpDual overload + phase-loss protection, moisture-resistant22kW/380V,50Hz, setting 37–50A
Fan UnitCentrifugal/axial/induced draft fansLight-load startup protection against impeller jammingAdapt to current fluctuation from variable duct resistance
CompressorAir & refrigeration compressorsHeavy-start & overheat protectionTolerate frequent loading/unloading cycles
Vacuum PumpIndustrial & water-ring vacuum pumpsLow-current idle-running damage preventionAdjustable setting for light-load operation
  1. Building & Municipal Infrastructure
SectorSystemKey DemandMounting Method
HVACCentral air-con, air handler, cooling towerStable continuous-duty protectionDIN rail mounted with contactor interlock
Building AutomationFire control, security & elevator room equipmentEmergency cut-off safetyRemote monitoring via PLC
WastewaterAerator & sludge processing unitsDust & moisture resistanceCabinet installation with IP20 protection
New EnergySmall gen-set & PV inverterOvercurrent & grid-fault isolationRated up to 690V high-voltage system
  1. Other Industrial Sectors
IndustryEquipmentSpecial RequirementMatching Advantage
AgricultureIrrigation pump & feed processorOutdoor installation against grid voltage swingWide operating temp: -25°C~+60°C
MiningSmall conveyor & mine ventilation fanHeavy startup + high short-circuit withstand100kA high breaking capacity
Food & BeverageMixer & sterilization equipmentSanitary & easy-clean layoutNo exposed live parts for hygiene compliance
PharmaPharmaceutical & cleanroom machineryPrecise control & low failure rateHigh accuracy thermal-magnetic trip characteristic

III. Non-Recommended Applications (Avoidance Guide)

Unsuitable ConditionReasonAlternative Solution
DC CircuitAbnormal tripping characteristic under DC (rated only AC 50/60Hz)Dedicated DC-rated Schneider circuit breakers
>30 Starts/HourAccelerated trip unit ageing & shortened service lifeGV3ME enhanced series or match with soft starter
Altitude>2000mPerformance derating requiredHigh-altitude specified breaker or add upstream protection
Strong Corrosive AtmosphereUncoated terminals prone to oxidationAnti-corrosion coated model or protective enclosure
Explosion Hazard ZonesStandard version without ATEX certificationATEX certified explosion-proof breakers
Single-Phase Motors3-pole structure cannot provide single-phase protectionGV2 single-phase motor breaker series
  1. Detailed Field Application Cases

Case1: 22kW Fan Protection in Food Factory

Setup: 3×22kW centrifugal fans 380V/50Hz, independent control per unit

Scheme: GV3P50 + LC1D65 contactor + GV3AE11 auxiliary contact

Logic: Manual/Auto switch; auto stop & alarm upon overload

Result: Triple protection realized; failure rate -40%, maintenance cost -30%

Case2: Submersible Sewage Pump Control at WWTP

Setup: 4×22kW submersible sewage pumps 380V/50Hz, alternating operation

Scheme: GV3P50 + PLC interlock + level transducer

Condition: Humid environment, 10~15 starts/hour frequent cycling

Result: Anti-stall burnout + remote auto-switching, improved system reliability

Case3: Central Air-conditioning for Shopping Mall

Setup: 3×22kW chilled water pumps with VFD control 380V/50Hz

Scheme: GV3P50 + inverter + temperature sensor

Feature: Speed auto-adjust by return water temp; coordinated protection by inverter + breaker under overload

Result: ≥30% energy saving, service life doubled, superior system stability

  1. Recommended Matching Components & Selection Tips
  2. Recommended Matching List
AccessoryPart No.FunctionValue
AC ContactorLC1D65Remote control for frequent start-stopEnable automatic control & reduce manual operation
Auxiliary ContactGV3AE111NO+1NC signal outputAlarm feedback or PLC interlock
Thermal Overload RelayLRD4363Optional secondary overload protectionDouble motor protection for enhanced safety
Control PushbuttonXB4 SeriesManual start/stopHMI & emergency shutdown function
  1. Sizing Rules
  2. Power Match: 22kW (~44A @400V) optimally paired with GV3P50 (37–50A)
  3. Trip Setting: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
  4. Mount Clearance: ≥50mm gap to adjacent contactors; ≥10mm free space for heat dissipation
  5. Wiring Torque: Cable terminal tightening torque fixed at 2.5Nm
  6. Ambient Derate: Derate 1% rated current per every 1°C rise above +40°C ambient temperature