ULP system gateway server. Distinguished from the single-circuit-breaker interface LV434001; capable of stacking multiple IFM modules (LV434000). One server connects multiple IMU intelligent units, built-in RTC real-time clock, successor to the obsolete LV434011.
✅ Compatible circuit breaker ranges
ComPacT NSX 100~630
ComPacT NS630b~NS3200
MasterPact MTZ / NT / NW
PowerPact H/J/L/P/R frame breakers
Prerequisite: Circuit breaker equipped with MicroLogic trip unit + BSCM / BCM ULP communication module
✅ Communication interfaces
ETH: 2×RJ45, 10/100Mbps, Modbus TCP, daisy-chain support; built-in web server for web configuration, monitoring and remote control
ULP: 2×RJ45 ULP internal bus (ULP cable, max. 20 m), supports stacking IFM modules
Modbus-SL (RS485 serial Modbus, 9.6~38.4 kbps): manages up to 20 Modbus-SL slaves, supports up to 11 stacked IFMs
Protocols: Modbus TCP, HTTP, FTP, SMTP email alarm, NTP, SNMP
✅ Electrical & mechanical specifications
Power supply: DC24V (19.2~26.4 V), typical 120 mA; powers itself and stacked IFMs, IFMs require no separate power supply
Mounting: DIN rail snap-on mounting
Dimensions: 72 × 105 × 71 mm
Weight: 187 g
Protection: Front panel IP4x, terminals IP2x
Operating temperature: -25℃ ~ +70℃; storage temperature: -40℃ ~ +85℃
Certifications: CE, cULus, FCC, EAC
✅ Core functions
- Collect current, voltage, power, energy, protection alarms, status (closed/open, fault trip)
- Remote closing / opening (local lock switch on front panel can disable remote control authority)
- Email alarm, event logging with RTC timestamp
- Built-in web page for configuration, data viewing and debugging; EcoStruxure Power Commission (Ecoreach) for firmware upgrade and commissioning
- Test button and reset button (hold for 5s to restore DHCP factory default)
⚠️ The embedded switch does not support ring topology and STP, redundant ring network is not allowed
✅ Cross-series model comparison
| Model | Name | Features |
| LV434002 | IFE Switchboard Server | Supports IFM stacking, multiple IMUs, Modbus-SL gateway, RTC |
| LV434001 | IFE Single-breaker Ethernet Interface | Connects only one IMU, no IFM stacking |
| LV434000 | IFM Modbus-SL Interface | Single-breaker Modbus-RTU slave, must be connected to LV434002 |
✅ Common matching cables & spares
S434204 / S434303 / S434305: Insulated ULP cables for systems >480 VAC
S434201 / S434202: Standard ULP cables, for ≤480 V only
- Complete commissioning steps with EcoStruxure Power Commission (Ecoreach)
Preparations
- Wiring: 24 VDC power supply; ULP cable connected to BSCM/BCM; Ethernet cable directly to PC or switch; unused ULP ports must be fitted with terminator plugs
- Software: Free Schneider Ecoreach (EPC), version ≥2.14 recommended; PC IP in the same subnet as LV434002; firewall and proxy disabled
- Factory setting: DHCP; IP can be scanned by software after power-on; hold reset button for 5s to restore DHCP factory setting
Step 1: Discover LV434002 gateway
- Open Ecoreach → Create new project, select [Switchboard]
- Click [Launch Device Discovery], select Ethernet/IP as communication method
- Scan the subnet, identify LV434002 (IFE Server) and add it to the project
- Access IFE web page (browser input IP directly): configure static IP, NTP, SMTP alarm, Modbus-SL serial parameters (baud rate, parity, slave quantity)
Step 2: Scan ULP-connected IFMs and breaker IMUs
- On the IFE gateway topology page, run [Scan ULP Bus]
- Automatically identify all LV434000 IFMs and NSX/MTZ breakers behind BSCM modules
- Verify Modbus slave ID of each IFM; address conflict will be reported directly
- Configure each IFM: modify Modbus-SL parameters, rename, enable/disable auto link
Step 3: Verify breaker parameters and communication
- Open any breaker IMU: read real-time electrical values, status and alarms
- Remote control test: confirm remote lock on breaker panel is unlocked → send open/close command via software; priority check lock position and ULP link light if failed
- Event logging: RTC synchronization (NTP server or manual time setting on web page) to ensure accurate timestamps
- Firmware upgrade: select IFE / IFM / Micrologic trip unit for online upgrade (DO NOT power off during upgrade)
Step 4: Modbus-SL (RS485) configuration (optional)
- Configure Modbus-SL on IFE web page or Ecoreach: 9600~38400 bps, parity, stop bits
- Max. 20 Modbus-SL slaves, independent address space, separate from ULP IFM address planning
- Termination resistor required at the end of Modbus-SL bus
Step 5: Export commissioning report
After telemetry, remote signalling and remote control pass, export switchboard communication test report from Ecoreach for BMS / SCADA integrators
III. Standalone WEB commissioning (on-site quick test without Ecoreach)
- Enter IFE IP on browser within the same subnet to log into built-in Web Server
- Menu: Network (IP, DHCP), ULP Bus, Modbus SL, Time (NTP), Alert (SMTP email alarm), Diagnostic (link diagnosis, event log)
- Diagnosis page displays ULP port signal quality, IFM online status and packet counters for fast fault location
- HS Code & Declaration Notes
LV434002: Schneider Enerlin’X IFE Switchboard Server (Modbus TCP gateway, low-voltage power distribution intelligent communication module)
Recommended HS code: 85176290 (Other communication gateway equipment, industrial Modbus TCP gateway)
Alternative code adopted by some customs brokers: 90308990 (Electrical measuring accessory)
✅ Reminder: HS code subject to final confirmation by customs broker and local customs. I can check customs code for Uzbekistan separately. Declaration elements: Brand: Schneider, Model: LV434002, Application: Communication acquisition gateway for low voltage circuit breakers, Power supply: DC24V, Protocol: Modbus TCP
- Alternative options
- Original direct predecessor: LV434011 (Old IFE switchboard server, obsolete, no RTC, not recommended for new projects, same hardware topology)
- Series selection guide
LV434002: IFE Server ✅ Supports multiple IFMs, Modbus-SL gateway, RTC (this model)
LV434001: IFE Single-breaker Ethernet Interface ❌ No IFM stacking, only one IMU
LV434000: IFM Modbus-SL Interface ❌ Must be connected to LV434002, cannot connect to Ethernet independently
- Domestic alternatives (same function note): ULP is proprietary Schneider bus, domestic gateways cannot interface BSCM directly. Domestic solution requires abandoning ULP and adopting breakers with native Modbus-RTU modules
- Common troubleshooting
- ULP LED yellow flashing: Degraded ULP link, excessive cable length, oxidized connector, missing terminator plug
- Ecoreach cannot find IFE: Mismatched subnet, DHCP IP failure, crossover cable (auto-adaptive port, incompatible with old switches), excessive 24 V voltage drop
- Modbus read successful but remote control invalid: Local lock activated, trip latch, protection interlock, outdated firmware
- Modbus-SL communication failure: Missing termination resistor, A/B reversed, duplicate address, mismatched baud rate
LV434002 core positioning: One gateway aggregates multiple NSX/MTZ breakers inside one switchboard cabinet via ULP + stacked IFMs, with integrated Modbus-SL gateway. Clearly differentiated from LV434001 which serves only one breaker. Below are industry scenarios and architecture scenarios.
- Typical industry application scenarios
- Data Center / IDC low-voltage distribution (high frequency)
Incoming cabinet, bus tie cabinet, UPS output cabinet, precision power distribution cabinet, centralized monitoring of MTZ frame and NSX moulded case breakers
Telemetry electrical parameters, remote signalling for open/close and trip, remote opening; SMTP email / SNMP alarm push for operation & maintenance; RTC ensures accurate event timestamp
Connect to BMS, environmental monitoring and power SCADA for PUE energy statistics, fault tracing and power outage logging
- Industrial plants, production lines, power rooms, chemical / pharmaceutical / semiconductor factories
Main distribution panel and MCC motor control centre with multiple NSX breakers in one cabinet, aggregated by one LV434002 + multiple LV434000 IFMs
Connect to factory SCADA and PLC: overload pre-alarm, harmonic monitoring, load balancing, emergency remote opening; unified maintenance on EcoStruxure Power platform
Predictive maintenance: collect breaker trip history, temperature rise and load trend for scheduled maintenance
- Commercial buildings, office towers, hospitals, rail transit, airports
BMS integration for intelligent LV/MV distribution, sub-metering for lighting, power and air conditioning
Critical load such as hospital: alarm and SOE sequence of event recording for power continuity; local web view, event cache when network offline
Standard configuration for Schneider BlokSeT prefabricated intelligent switchboard with factory-integrated Enerlin’X ULP bus
- PV, energy storage and EV charging distribution & grid-tie cabinet
Monitoring of NSX/MTZ grid-tie breaker: power, energy, trip status, remote opening protection; internal power panel inside energy storage container
Connect to EMS energy management system to collect branch loads for power scheduling
- Retrofit & renovation projects (very common)
Existing NSX/MTZ already fitted with BSCM/BCM ULP modules. Replace multiple LV434001 one-to-one IFEs with one LV434002 aggregator to save IP addresses and switch ports
Compact DIN rail module with DC24V supply, limited cabinet space; no modification to main circuit, only communication wiring added
- Architecture selection guide
✅ Suitable for LV434002 (IFE Server)
- ≥2 intelligent breakers in one cabinet: 1×LV434002 + up to 11×LV434000 IFMs, ULP daisy chain, single Modbus TCP IP for upper system, core advantage over LV434001 one-to-one scheme with higher cost for multi-breaker cabinets
- Cabinet with ULP breakers plus other RS485 Modbus-SL meters: Integrated Modbus-SL gateway supports up to 20 485 slaves (power meters, temperature & humidity sensors, etc.) to convert both ULP breaker data and RS485 data to Modbus TCP, saves extra Modbus gateway
- Local web page, email alarm, independent RTC and offline event log required
- Batch commissioning via Ecoreach: ULP topology scan, batch firmware upgrade for breakers and communication modules
❌ Not suitable, select LV434001 instead
Only one breaker inside cabinet, no IFM stacking and no external Modbus-SL instruments needed
III. Upper system integration
- Host SCADA: KingView, ForceControl, Intouch, Schneider EcoStruxure Power, third-party power monitoring platform, PLC (Siemens / Mitsubishi etc.)
- Local O&M: Direct browser access for data, alarm and manual remote control; Ecoreach for commissioning, verification and report output
- Alarm delivery: Email alarm, SNMP Trap to network management platform
- Limitations & design pitfalls
- ULP is Schneider proprietary bus, only compatible with NSX, MTZ and PowerPact fitted with BSCM/BCM, incompatible with other brands of breakers
- Dual Ethernet ports support daisy chain only, STP ring redundancy not supported. Redundant network for critical IDC requires additional industrial switch
- Remote control requires breaker fitted with motor operator and unlocked local remote lock; the module itself only provides communication channel
Schneider Enerlin’X ULP Series LV4340 Main Line Complete Order List
Main line: IFE / IFM communication modules (LV434002 belongs to this group). Classified as Active New / Obsolete Replacement / Breaker-side ULP Module / ULP Cable & Accessories
- Core IFE / IFM communication modules (LV4340xx)
| Order No. | Name | Description | Status |
| LV434002 | IFE Switchboard Server | Multi-breaker aggregation gateway, up to 11 stacked IFMs, integrated Modbus-SL gateway, RTC, dual-port Modbus TCP | ✅ Active (Main), replaces LV434011 |
| LV434001 | IFE Single-breaker Ethernet Interface | One-to-one, connects only one breaker, no IFM stacking, Modbus TCP | ✅ Active, replaces LV434010 |
| LV434000 | IFM Modbus‑SL ULP Interface | Single-breaker Modbus-RTU slave, must connect to LV434002, cannot connect to Ethernet independently | ✅ Active |
| LV434011 | Legacy IFE Switchboard Server | Old multi-breaker IFE, no RTC | ❌ Obsolete, replaced by LV434002 |
| LV434010 | Legacy IFE Single-breaker Ethernet Interface | Old one-to-one IFE | ❌ Obsolete, replaced by LV434001 |
- MT withdrawable embedded IFE (EIFE, separate series)
| Order No. | Name | Description | Status |
| LV851001 | EIFE Embedded Ethernet Interface for MTZ | Built-in IFE inside MTZ withdrawable unit | ✅ Active |
| LV851100SP | EIFE Spare Kit MTZ1 | Repair kit for MTZ1 withdrawable EIFE | ✅ Spare part |
| LV851200SP | EIFE Spare Kit MTZ2/MTZ3 | Repair kit for MTZ2/3 withdrawable EIFE | ✅ Spare part |
III. Breaker ULP communication modules (BSCM / BCM, front end for IFM/IFE)
| Order No. | Name | Applicable breaker | Status |
| LV434220 | BSCM Modbus‑SL/ULP | New generation NSX (NSX100~630), ULP + Modbus SL | ✅ Active |
| S434205 | BSCM Standard ULP Module | NSX / PowerPact H/J/L, basic ULP status acquisition | ✅ Active |
| 33106 | BCM ULP Module | MasterPact NT/NW, PowerPact P/R frame breakers | ✅ Active |
- ULP dedicated cables (RJ45 proprietary ULP cable, ⚠️ Ordinary Ethernet cable NOT allowed)
| Order No. | Specification | Remarks |
| LV434200 | ULP cable 0.35 m, ≤480 VAC | Standard NSX ULP cable |
| LV434201 | ULP cable 1.3 m, ≤480 VAC | Most popular |
| LV434202 | ULP cable 3 m, ≤480 VAC | |
| LV434204 | Insulated ULP cable 1.3 m, >480 VAC | Mandatory for voltage >480 V |
| LV434195 | BCM cable 0.35 m | For NT/NW frame BCM |
| LV434196 | BCM cable 1.3 m | For NT/NW frame BCM |
| LV434197 | BCM cable 3 m | For NT/NW frame BCM |
| LV434198 | BCM cable 5 m | For NT/NW frame BCM |
- ULP mandatory accessories
| Order No. | Name | Description |
| TRV00880 | ULP terminator plug (10 pcs/pack) | Unused ULP port must be terminated, common omission causing link failure |
- Quick selection guide for proposal
- ≥2 NSX/MTZ breakers in one cabinet, aggregated to Ethernet: LV434002 + multiple LV434000 IFMs
- Only one breaker in cabinet, direct Ethernet connection: LV434001
- Breaker only requires Modbus-RTU without Ethernet: LV434000 IFM (connect to third-party Modbus master)
- Integrated solution for MTZ withdrawable cabinet: Prefer LV851001 EIFE