6ES7-235-0KD22-0XA0 Siemens

Detailed Explanation of EM 235 Analog I/O Module Model Code Breakdown Model Segment Description 6ES7 Prefix for Siemens SIMATIC automation product series 235 Module type identifier: EM 235 analog input/output module 0KD Specification code: 4 entradas analógicas (IA), 1 saída analógica (AO), ±10V DC signal range 22 Hardware version number 0XA0 Standard version identifier (0XA8 ...

  • Detalhes do produto

Detailed Explanation of EM 235 Analog I/O Module

  1. Detalhamento do código do modelo
Segmento de modeloDescrição
6ES7Prefix for Siemens SIMATIC automation product série
235Module type identifier: EM 235 analog input/output module
0KDSpecification code: 4 entradas analógicas (IA), 1 saída analógica (AO), ±10V DC signal range
22Hardware version number
0XA0Standard version identifier (0XA8 is the China region version EM 235 CN)
  1. Especificações Técnicas Principais

Posicionamento do produto: Expansion module for SIMATIC S7-200 series, only compatible with S7-22X CPUs (not compatible with S7-21X), peça de reposição

Configuração de E/S: 4 entradas analógicas (IA) + 1 saída analógica (AO)

Características de entrada:

Tipo de sinal: Differential input, ±10V DC (other ranges selectable via DIP switches)

Resolução: 12 pedaços (incluindo bit de sinal)

Impedância de entrada: ≥10MΩ (voltage input)

Proteção contra sobretensão: Up to 30V DC

Características de saída:

Tipo de sinal: ±10V DC (tensão) / 0–20mA (atual, opcional)

Resolução: 12 bits for voltage output, 11 bits for current output

Output impedance: ≤0.5Ω (voltage output)

Capacidade de carga: Max 5mA for voltage output, max 20mA for current output

Requisitos de energia:

External supply: 24Em DC, max 60mA

Backplane bus: 5Em DC, max 30mA

Power dissipation: Typical 2W

Conversion Performance:

Input conversion time: <250μs por canal

Output response time: 1.5ms to 95% steady-state value

  1. Ambiente Operacional
  2. Temperatura operacional: 0–60°C (montagem horizontal), 0–40ºC (montagem vertical)
  3. Temperatura de armazenamento: -40–+85°C
  4. Umidade relativa: 5–95% (sem condensação)
  5. Classe de proteção: IP20 (compatível com IEC 61131-2)
  6. Montagem: Montagem em trilho DIN (compatível com EN 50022)
  7. Application scenarios:

Analog signal acquisition and control for small automation systems

Monitoring and regulation of process variables such as temperature, pressão, and flow

Simple control loops requiring simultaneous analog input and output

  1. Substituição & Modelos compatíveis
ModeloCompatibilidadeNotas
6ES7 235-0KD22-0XA8Totalmente compatívelChina version (EM 235 CN), same functions and parameters
6ES7 231-0HC22-0XA0Input replacementEM 231 4-channel analog input module (sem saída)
6ES7 232-0HD22-0XA0Output replacementEM 232 2-channel analog output module (no input)
S7-200 SMART EM AE04Upgrade replacementFor S7-200 SMART CPU, 4 entradas analógicas; similar functions but not compatible with S7-22X
  1. Informações oficiais sobre pedidos

Standard order number: 6ES7 235-0KD22-0XA0 (global version)

China order number: 6ES7 235-0KD22-0XA8 (EM 235 CN)

Product status: Currently a spare part for S7-200 system maintenance and replacement

  1. Key Usage Notes
  2. DIP switch settings: DIP switches on the side select input signal range; only one range can be set for the entire module
  3. Programação:

Use Scale_I_to_R and Scale_R_to_I instructions in S7-200 software for analog/digital conversion

Analog input addresses: AIW0–AIW6 (2 bytes per channel)

Analog output address: AQW0 (2 bytes)

  1. Wiring rules:

Use shielded twisted-pair cable for analog signals, keep at least 10cm away from power cables

Unused channels should be shorted to avoid interference

  1. Precauções:

Both external 24V DC and backplane 5V DC power must be connected

Hot swapping not supported; install/remove only with power off

  1. Comparison with S7-200 SMART Modules
Item6ES7 235-0KD22-0XA0S7-200 SMART EM AE04
CPU compatívelS7-22X seriesS7-200 SMART series
E/S4AI/1AO4IA
Signal range±10V / 0–20mAMultiple options (including thermocouple/RTD)
ComunicaçãoPPI protocolPROFINET / Ethernet
Fonte de energiaExternal 24V + backplane 5VExternal 24V only

Complete Model List of Siemens EM 235 Analog I/O Modules

  1. Core EM 235 Série de modelos (by hardware version)
ModeloHW VersionRegiãoDescriçãoStatus
6ES7 235-0KD00-0XA00GlobalEM 235 analog combo module, 3AI/1AO, 12-pedaçoDescontinuado, early version
6ES7 235-0KD10-0XA010GlobalEM 235 analog combo module, 4AI/1AO, 12-pedaçoDescontinuado, transitional
6ES7 235-0KD20-0XA020GlobalEM 235 analog combo module, 4AI/1AO, 12-pedaçoDescontinuado, legado
6ES7 235-0KD22-0XA022GlobalEM 235 analog combo module, 4AI/1AO, 12-pedaço, S7-22X onlySpare, available
6ES7 235-0KD22-0XA822CN (China)EM 235 CN analog combo module, 4AI/1AO, 12-pedaço, S7-22X onlySpare, China-only
  1. Detailed Model Differences

2.1 Common Features of All EM 235 Modelos

E/S: 4IA + 1AO (3IA + 1AO for 00 versão)

Entrada: ±10V DC (other ranges via DIP switches: 0–20mA, 4–20mA, mV)

Saída: ±10V / 0–20mA (4–20mA via wiring)

Resolução: 12-bit input (with sign), 12-bit voltage output, 11-bit current output

Compatibilidade: Only for S7-22X CPUs (not S7-21X)

2.2 Principais diferenças

Item6ES7 235-0KD00-0XA06ES7 235-0KD22-0XA0/0XA8
Entradas analógicas3 canais4 canais
DIP switchesBasic settingsAprimorado, supports more ranges
PrecisãoBásicoImproved, better anti-interference
PoderExternal 24V + backplane 5VMesmo, optimized to 2W dissipation

2.3 Global vs. China (CN) Versão

6ES7 235-0KD22-0XA0: Global version, worldwide except China

6ES7 235-0KD22-0XA8: China-specific version; same functions and parameters, different certification and distribution

  1. Pedido & Substituição

3.1 Current Valid Part Numbers

Global: 6ES7 235-0KD22-0XA0 (poupar)

China: 6ES7 235-0KD22-0XA8 (EM 235 CN, poupar)

3.2 Upgrade Path to S7-200 SMART

S7-200 ModuleS7-200 SMART ReplacementDiferença
EM 235 (4AI/1AO)6ES7 288-3AM03-0AA0 (2AI/1AO)Fewer channels, funções aprimoradas, PROFINET/Ethernet
EM 235 (4AI/1AO)6ES7 288-3AM06-0AA0 (4AI/2AO)More outputs, full feature upgrade
  1. Important Operational Notes
  2. DIP switches: Set uniform measurement range for all AI channels
  3. Addressing:

Entradas analógicas: AIW0–AIW6 (2 bytes each)

Saída analógica: AQW0 (2 bytes)

  1. Fiação:

Shielded twisted-pair required; separate from power cables by ≥10cm

Short unused channels to reduce noise

  1. Poder: Both 24V DC external and 5V DC backplane required; no hot-swapping

Os principais modelos do Siemens EM 235 módulo de E/S analógica são 6ES7 235-0KD22-0XA0 (global) e 6ES7 235-0KD22-0XA8 (China NC), ambas as versões de hardware 22 peças sobressalentes para manutenção de CPU S7-22X. Earlier versions (00/10/20) are discontinued. For system upgrades, use corresponding S7-200 SMART modules.

Siemens EM 235 (4 entradas analógicas + 1 saída analógica)

is the most widely used analog mixed module for the S7-200 micro PLC.

Its core purpose: acquire multiple analog sensor signals and output one analog for closed-loop control.

It is designed for small-to-medium equipment, standalone automation, and local control systems, not large DCS systems.

Below is a complete list of applications by industry + typical control scenarios.

  1. General Closed-Loop Control Applications
  2. Constant Pressure Control

IA: Pressure transmitter (4–20mA)

AO: Inverter for pump/fan (0–10V ou 0–20mA)

Uses: Abastecimento de água com pressão constante, compressed air regulation, pipeline pressure stabilization

  1. Constant Temperature Control

IA: Temperature transmitter, thermocouple/RTD

AO: Electric control valve, aquecedor, electronic expansion valve

Uses: Water tank temperature control, small oven, HVAC unit, heat exchanger station

  1. Constant Level Control

IA: Level transmitter (hydrostatic/ultrasonic)

AO: Inlet control valve, variable-speed drainage pump

Uses: Water tank, reservoir, water tower, small storage tank level maintenance

  1. Flow & Metering Control

IA: Electromagnetic flowmeter, turbine flowmeter

AO: Control valve, metering pump, proportional valve

Uses: Sistemas de lote, dosing, fluid proportioning

  1. Tension & Position Control

IA: Tension sensor, displacement transducer

AO: Inversor, proportional hydraulic valve

Uses: Constant tension in textile, impressão, film, cable machinery

  1. Industry-Specific Applications

2.1 Water Supply & Wastewater Treatment

Small constant-pressure water supply systems

Sewage lift pumps, integrated wastewater treatment

Water tank level monitoring and auto refill

Pipeline pressure/flow monitoring and inverter control

2.2 AVAC & Refrigeration

Chillers, air-cooled units

Fan coil units, air handling units

Heat exchanger station: primary/secondary water temp/pressure + valve control

Cooling tower fan speed control

2.3 Indústria Leve & Automation Machinery

Embalagem, filling, sealing machines (level/weight control)

Pequenas máquinas-ferramentas, sistemas hidráulicos (pressão + proportional valve control)

Conveyor speed adjustment, material height detection

Food machinery: misturadores, blenders, oven temperature control

2.4 Small Chemical & Batching Systems

Temperature and pressure monitoring for small reactors

Liquid batching and proportional mixing

Dosing systems: metering pump flow control

Tank level and temperature remote monitoring

2.5 Environmental Equipment

Bag filter differential pressure + fan control

Small desulfurization and denitrification regulation

Exhaust fan and spray pump control

2.6 Automação Predial & Small Facilities

Building AHU and fresh air units

Ventilation pressure control in underground garages

Small heating and heat exchanger stations

2.7 Small Boilers & Heating Systems

Hot water boiler temperature, pressão, level monitoring

Circulation pump variable-speed control

Analog control of burner damper/fuel valve

2.8 Hidráulico & Pneumatic Equipment

Hydraulic power unit pressure monitoring

Proportional pressure/flow valve control

Precision position control of pneumatic actuators

  1. Ideal Project Characteristics for EM 235

Small system: 1 CPU + few expansion modules

Requires 2–4 analog inputs and 1 analog control output

Espaço compacto, sensível ao custo

Standard industrial signals: 0–10V / 0–20mA / 4–20mA

Single closed-loop control (temperatura, pressão, nível, tension)

  1. Summary of Typical Applications

The EM 235 is widely used in small automation machines, pump stations, HVAC units, constant-pressure water supply, and temperature control systems

where multi-channel analog acquisition plus single-channel analog closed-loop control is required.