ACS580-01-246A-4
- ACS580: ABB new generation general wall-mounted VFD série
- 01: Standard integrated wall-mounted unit (non-cabinet modular type 04)
- 246UM: Corrente de saída nominal 246 UM
- 4: 3-phase input voltage class 380~480 V AC
Optional protection suffixes:
No suffix = IP21 standard version; +B056 = IP55 high-protection dustproof and waterproof version
Tamanho do quadro: R8
Order material numbers: 3AUA0000080507 (IP21), 3AUA0000083582 (IP55)
- Potência nominal / Current Ratings (400 V Grid)
| Tipo de carga | Corrente de saída | Potência do motor correspondente | Overload Specification |
| Padrão / Light Load (Fãs & Bombas) ILd | 234 UM | 132 kW | 110% para 1 min a cada 10 min |
| Rated Nominal Current In | 246 UM | 132 kW | Continuous rated operation |
| Heavy Load (Transportadores / Extruders) IHd | 206 UM | 110 kW | 150% para 1 min a cada 10 min |
Apparent output capacity: 170 kVA; Overall efficiency ≥ 98%
III. Parâmetros elétricos principais
- Input Power Supply
Phases: 3-fase (3Ph)
Tensão: AC 380~480 V ±10%
Mains frequency: 47.5~63 Hz
Power factor correction: Built-in DC choke (standard for R8 frame)
- Output Drive
Tensão de saída: 0~Uin (0~480 V)
Frequência de saída: 0~500 Hz
Control algorithms: Scalar V/F + Controle vetorial de fluxo sem sensor
Torque performance: 100% rated torque available at 0.5 Hz; Torque response <10 ms
- Standard Built-in I/O Terminals (Onboard Control Board)
| Tipo | Quantidade | Specification Description |
| Analog Input AI | 2 canais | Switchable 0~10 V / 4~20 mA |
| Analog Output AO | 2 canais | 0~10 V / 4~20 mA |
| Digital Input DI | 6 canais | 24 VDC NPN/PNP compatible |
| Digital Output DO | 3 canais | Relay dry contacts (250 VAC / 2 UM) |
| Porta de comunicação | 1 × RS485 | Modbus RTU standard; expandable to Profinet/Profibus/EtherNet/IP |
| USB Port | 1 canal | PC commissioning, parameter upload & download |
- Full Standard Protection Functions
Sobrecorrente, sobretensão, subtensão, sobrecarga, IGBT overtemperature, motor stall, falha de terra, perda de fase, proteção contra travamento, cooling fan fault, proteção contra curto-circuito, parameter loss alarm.
- Dimensões Mecânicas & Peso
IP21 Standard Wall-mounted (ACS580-01-246A-4)
Overall size: H 615 × W 270 × D 250 milímetros
Peso líquido: 21 kg
IP55 High-protection Model (ACS580-01-246A-4+B056)
Overall size: H 965 × W 300 × D 452 milímetros
Peso líquido: 77 kg
Montagem: Vertical wall mounting; leave ≥200 mm ventilation space top and bottom for heat dissipation
- Environmental Operation Specifications
- Temperatura operacional: -15℃ ~ +50℃ (derate output by 5% at 50℃)
- Armazenar / temperatura de transporte: -40℃ ~ +70℃
- Classe de proteção: Base IP21; upgrade to IP55 with +B056 option
- Altitude: Full power up to 1000 eu; desclassificar 1% per additional 100 m above 1000 eu
- Umidade: 5~95% RH, sem condensação, sem gás corrosivo
- Padrão Integrado & Acessórios opcionais
Factory Standard Built-in Components
Detachable Chinese assistant control panel
Integrated DC choke
Basic I/O control board, Modbus RTU
Bottom cooling fan
Optional Expansion Parts
- Resistor de frenagem / braking unit: Mandatory for high-inertia start-stop and overhauling loads
- Communication adapters: Profibus DP, Profinet IO, Ethernet/IP
- EMC filters: Classe A / Classe B, compatível com padrões industriais de EMC
- Externo 24 V power supply module, remote panel extension cable
- Complete IP55 cabinet kit (model suffix +B056)
VII. Cenários típicos de aplicação
- AVAC & Tratamento de Água (Light Load 132 kW)
Cooling fans, tunnel exhaust fans, constant-pressure water supply main pumps, sewage agitators, torres de resfriamento; variable-torque energy-saving operation.
- Manuseio de materiais & Materiais de Construção (Heavy Load 110 kW Class)
Transportadores de correia, elevadores de caçamba, cement mixers, extrusoras, centrífugas; frequent start-stop and shock loads.
- General Machinery
Compressores grandes, wire drawing machines, mixing mills, paper production lines; precise speed regulation + multi-speed logic.
- Mineração & Ports
Belt transfer equipment, dust removal fans; ideal IP55 model for wide voltage tolerance and strong dust resistance.
VIII. Adjacent Power Model Comparison within the Same Series
| Modelo | Corrente nominal | Standard Power | Heavy Load Power |
| ACS580-01-206A-4 | 206 UM | 110 kW | 90 kW |
| ACS580-01-246A-4 | 246 UM | 132 kW | 110 kW |
| ACS580-01-293A-4 | 293 UM | 160 kW | 132 kW |
- Principais vantagens do produto
- Fully integrated functions: Built-in choke, Modbus, multi-channel I/O; ready for complete set without extra options
- Chinese assistant panel: Guided commissioning wizard, one-click motor identification
- Wide grid compatibility: Universal 380~480 V, compatible with domestic 380 V and overseas 400/440 V grids
- Dual control modes: Simple V/F control + vetor sem sensor, suitable for both fan and heavy-duty equipment
- Optional IP55 high protection; direct wall mounting outdoors or in humid workshops without separate control cabinet
- Comprehensive energy-saving algorithms: Sleep mode, flow optimization, soft start-stop, cutting fan and pump energy consumption by over 30%
- Compatible with mainstream industrial buses, seamlessly connected to PLC systems such as Siemens, Mitsubishi, Inovação
- Instalação de chave & Especificações de fiação
- Fiação do Circuito Principal
Entrada: L1/L2/L3 connected to 3-phase 380 V; Output U/V/W connected to 3-phase asynchronous motor; PE earth terminal reliably connected to cabinet ground.
- Control Cable Requirements
Route shielded analog signal cables separately with a minimum spacing of 30 cm from power cables; single-end shielding grounding for digital twisted-pair cables.
- Mandatory Heat Dissipation Rules
Vertical mounting for R8 frame; top ventilation gap ≥200 mm, side gaps ≥50 mm; blow filter screens monthly in dusty environments.
- Braking Selection Reminder
Braking resistors must be fitted for high inertia shutdown and overhauling loads, otherwise frequent DC overvoltage faults will occur.
- Quick Troubleshooting Checklist
- Overcurrent OL: Parada do motor, output short circuit, cable earth breakdown, insufficient derating for heavy loads
- Overvoltage OV: No braking resistor fitted for inertial loads, transient grid high voltage
- Overtemperature OT: Blocked air ducts, ambient temperature over 50℃, faulty cooling fan
- Output Phase Loss: Loose motor wiring, broken wire on U/V/W one phase
- Communication Loss: Poor shield grounding, missing bus terminating resistor
All Control Modes of ABB ACS580-01-246A-4
All ACS580 drives share one unified control core with no functional cuts for the 246 UM (R8 frame) modelo. Three major control categories are supported: Scalar V/F, Sensorless Vector, Vector with Encoder, subdivided into 5 operation modes to cover fans/pumps, general heavy loads and high-precision positioning applications.
- Scalar V/F Control (Parâmetro 99.04 = SCALAR)
- Linear V/F (Default for Light Load Fans & Bombas)
Voltage rises linearly with frequency with uniform voltage boost from 0~50 Hz. Suitable for fans, blowers, pumps and general centrifugal loads.
Características: Estrutura simples, multi-motor parallel drive (one VFD driving multiple asynchronous motors); weak low-speed torque, zero torque at 0 Hz.
Aplicativos: Sistemas HVAC, abastecimento de água com pressão constante, multi-pump parallel systems.
- Quadratic V/F (Square Curve, Dedicated for Fans & Bombas)
Voltage increases proportional to the square of frequency, matching the torque characteristic of fans and pumps for optimal energy efficiency.
Características: Greatly reduces motor excitation loss and reactive power under light load; even weaker low-speed torque.
Typical scenarios: Cooling tower fans, circulation pumps, dust extraction blowers.
- Boostable Torque V/F (Voltage Boost V/F)
Raises output voltage at low frequencies to compensate insufficient low-speed torque.
Aplicativos: Transportadores de correia, equipamento de mistura, light starting resistance loads.
- Controle vetorial de fluxo sem sensor (Parâmetro 99.04 = SENSORLESS)
The primary general heavy-load control of ACS580; no encoder required, standard for this 246 A model with no extra options needed.
Desempenho central
- 100% rated torque output at 0.5 Hz; high starting torque to overcome static friction
- Torque response <10 ms, far superior dynamic speed regulation over V/F control
- Supports precise current limiting, anti-stall protection and continuous heavy-load operation
- Static & rotating motor identification supported, compatible with new and old motors
Cargas Aplicáveis
Transportadores, misturadores, extrusoras, compressores, máquinas para trabalhar madeira, single heavy-duty motor drives.
Limitações
Cannot maintain full torque at zero speed (0 Hz); precise closed-loop speed control unavailable without encoder feedback.
III. Controle vetorial com codificador (Parâmetro 99.04 = ENCODER)
Requires optional FEN-01 / FEN-11 encoder interface module installed in the VFD expansion slot.
- Supports pulse encoders: HTML / TTL incremental encoders
- Closed-loop speed control with 100% continuous rated torque at 0 Hz
- Speed control accuracy ±0.01% of rated speed
- Enables simple positioning, jog operation and tension control
Aplicativos
Wire drawing machines, winding/unwinding equipment, high-precision transmission, machinery requiring zero-speed load holding.
- Two Operation Reference Modes (Speed Command Source, Independent of Above Motor Control Algorithms)
- Local Control (Panel Reference)
Frequency set via control panel knob / botões; local start-stop and speed adjustment for single-unit commissioning.
- Controle remoto (External Reference, Mainstream for Engineering)
Speed commands and start-stop signals come from external channels with flexible combinations:
- Analog reference: AI1/AI2 (0–10V / 4–20 mA)
- Multi-speed DI digital terminal reference: Até 7 fixed preset speeds
- Pulse frequency reference (optional IO module required)
- Fieldbus reference: Modbus RTU (padrão), Profibus DP, Profinet, Ethernet/IP, etc..
- PID closed-loop reference: Built-in process PID for closed-loop constant control of pressure/flow/temperature (core function for constant-pressure pump & fan water supply)
- Special Process Control Modes (Built-in Functions Based on Vector / V/F Core)
- PID Process Control
Independent onboard PID regulator; no external PLC required for automatic constant pressure and flow control of pressure, liquid level and temperature.
- Multi-pump Cycling Soft Start (HVAC Special Function)
One-drive-multiple circulating water supply, automatic alternation of main and auxiliary pumps, energy saving via sleep & wake-up logic.
- JOG Jogging Control
Low-speed jog triggered via DI terminals for equipment maintenance and commissioning.
- DC Pre-excitation
DC pre-magnetization before startup to boost instantaneous starting torque in vector mode.
- Parar / Anti-overcurrent Torque Limiting
Automatic torque limitation to avoid overcurrent faults under heavy load.
- Quick Selection & Distinction Table
| Tipo de controle | Encoder Required | Low-speed Torque | Uso típico |
| Quadratic V/F | Não | Baixo | Energy-saving control for fans & bombas |
| Linear V/F | Não | Moderate | Multi-motor parallel driving |
| Sensorless Vector | Não | Alto (Full torque at 0.5 Hz) | Transportadores, misturadores, general heavy loads |
| Vector with Encoder | FEN Module Required | Ultra-alto (Zero-speed torque holding) | Equipamento de enrolamento, high-precision transmission & posicionamento |
Applicable Scenarios of Closed-Loop Vector Control with Encoder for ABB ACS580-01-246A-4
Preface
This control mode uses parameter code 99.04=ENCODER. Optional FEN-01 (HTML) / FEN-11 (TTL) incremental encoder modules are mandatory. Real-time speed feedback from the motor shaft encoder delivers three core advantages:
- Contínuo 100% rated torque holding at 0 Hz (sensorless vector cannot hold load at zero speed)
- Speed control accuracy ±0.01% rated speed with no low-speed jitter or step loss
- Supports precise tension closed-loop control, multi-axis synchronization, simple positioning and constant-torque processes
Closed-loop vector control is only selected for working conditions requiring zero-speed load holding, high low-speed precision, stable tension, multi-axis synchronization and slip-free heavy start-stop. Ventiladores padrão, pumps and single ordinary conveyors can operate reliably with sensorless vector or V/F control only.
- Winding & Unwinding Industry (Most Typical High-power Application, Matching 132 kW Class 246 Um modelo)
Equipamento aplicável
Paper rewinders, plastic film extrusion winders, rubber calender winding/unwinding machines, non-woven slitting machines, metal foil wire drawing & máquinas de enrolamento, cable stranding machines
Mandatory Process Requirements for Closed-Loop Vector
- Smooth low-speed startup and constant tension maintenance during shutdown; no loose rolls, stretching or material breakage at zero speed
- Automatic constant tension as roll diameter dynamically changes between large and small reels, speed follows upstream master machine
- No tension fluctuation during high-low speed switching to prevent wrinkling or stretching deformation of web materials
- Multi-section linkage: Synchronized operation of unwinding-traction-winding three axes
Open-loop Disadvantages: Insufficient low-speed torque without encoder leads to web slipping and out-of-control tension.
- Posicionamento de alta precisão / Intermittent Reciprocating Heavy-duty Equipment
Equipamento aplicável
Large gantry feeders, heavy plate translation positioning tables, stone cutting feeders, cement block stacking conveyors, large packaging reciprocating cross-cutting machines
Process Requirements
- Precise stop at target positions with minimal repetitive positioning error; frequent jog & inching maintenance operations
- No position shifting or slipping when stationary under full load
- No speed overshoot during acceleration & desaceleração; no jitter or impact on heavy start-stop
III. High-inertia Overhauling / Vertical Lifting Constant-torque Loads (High-power 110/132 kW Heavy-duty Conditions)
Equipamento aplicável
Downward mine belt conveyors, large bucket elevators, heavy vertical mixers, lifting silo discharge drives
Process Pain Points Unsolvable by Open-loop Control
Reverse load generated by material self-weight requires full torque braking maintained at zero shutdown speed; overhaul runaway and overvoltage alarms easily occur at low descending speeds. Encoder closed-loop corrects speed in real time to suppress regenerative impact and stabilize DC bus voltage with braking units.
- Multi-motor Synchronized Production Lines (Long-distance High-power Synchronous Transmission)
Equipamento aplicável
Cement kiln chain conveyors, long-distance multi-drive mine belts, multi-layer drying synchronized roller tables, continuous metal pickling lines
Process Requirements
Rigid synchronization of multiple motors with minimal speed deviation across sections to avoid plate stretching, belt deviation and tearing. Closed-loop vector with encoder feedback achieves far superior multi-motor synchronization accuracy compared to open-loop sensorless vector.
- Heavy-duty Equipment for Extrusion, Kneading & High-viscosity Mixing
Equipamento aplicável
Plastic single/twin-screw extruders, rubber internal mixers, chemical high-viscosity reactor agitators, main asphalt mixing machines
Process Requirements
- Extremely high starting resistance for low-temperature high-viscosity materials; full torque output at 0 Hz to avoid startup stalling
- Constant extrusion torque throughout operation for uniform output thickness
- No torque ripple under steady low-speed operation for consistent product thickness
- Centrífugas & High-speed Precision Rotating Equipment
Equipamento aplicável
Large chemical separation centrifuges, high-speed paper dehydration centrifuges, large horizontal food centrifuges
Process Requirements
High-precision stable speed across wide speed ranges with minimal speed fluctuation during acceleration/deceleration. Real-time speed correction via encoder feedback at high operating speeds eliminates resonance and uneven material stratification.
VII. High-power Stenter, Contexto & Padder Equipment for Textile Printing & Dyeing
Equipamento aplicável
High-power stenters, water squeezing & calendering machines, continuous dyeing long lines
Process Requirements
Synchronized drafting of multiple rollers without fabric stretching or shrinkage; zero-speed load holding during low-speed fabric threading to avoid fabric accumulation and slipping; stable tension throughout operation.
VIII. Scenarios Unsuitable for Closed-Loop Vector Control (Select V/F or Sensorless Vector Directly)
- Fãs, torres de resfriamento, circulation pumps, dust extraction blowers (variable-torque loads with no zero-speed load holding demand)
- Single light-duty belt conveyors, small mixers, compressores (no high-precision synchronization or tension control requirements)
- One-drive-multiple parallel multi-motor systems (only scalar V/F control applicable; encoder closed-loop cannot support multi-motor parallel driving)
Quick Application Selection Reference Table
| Core Working Condition Requirement | Recommended Control Mode | Codificador (FEN Module) Obrigatório |
| Fãs, bombas, multi-motor parallel driving | Scalar V/F | Não |
| Ordinary conveyors, misturadores, compressores | Sensorless Vector | Não |
| Winding/unwinding, controle de tensão, zero-speed load holding | Closed-loop Vector with Encoder | FEN-01/FEN-11 Required |
| Multi-axis synchronization, posicionamento de precisão, high-inertia overhauling loads | Closed-loop Vector with Encoder | FEN Module Required |
| High-viscosity extrusion, kneading, high-power centrifuges | Closed-loop Vector with Encoder | FEN Module Required |
Supplementary Supporting Hardware (ACS580-01-246A-4 R8 Frame)
- HTL incremental encoder: Select FEN-01
- TTL differential encoder: Select FEN-11
- Braking resistors / braking units must be fitted for high-inertia overhauling scenarios to eliminate regenerative overvoltage faults