B&R 3DM486.6 Digital Mixed I/O Module

Modelo de Informação Básica:3DM486.6 Brand: B&R Automation Product Family: Sistema 2005 (Legacy PCC Backplane System) Tipo de módulo: Digital Mixed I/O Module ⚠️ Status: Manufacturer Discontinued (Obsoleto). Only stock and second-hand spare parts available. New projects are recommended to migrate to the X20 series. Core Channel Specifications Item Parameter Digital Input (DE) 16 canais, 24 CCV, Pia/Fonte ...

  • Detalhes do produto

Informações Básicas

Modelo:3DM486.6

Marca: B&R Automação

Família de produtos: Sistema 2005 (Legacy PCC Backplane System)

Tipo de módulo: Digital Mixed I/O Module

⚠️ Status: Manufacturer Discontinued (Obsoleto). Only stock and second-hand spare parts available. New projects are recommended to migrate to the X20 series.

  1. Core Channel Specifications
ItemParâmetro
Entrada Digital (DE)16 canais, 24 CCV, Sink/Source compatible (NPN/PNP universal)
Input Filter Time1 EM
Saída digital (FAZER)16 canais, Transistor Sourcing Output, 24 CCV
Per-channel Output Current0.5 UM / point
Maximum Total Module Output Current8 UM
Isolamento ElétricoGalvanic isolation between input bank and output bank; no isolation between individual channels
DiagnósticoOutput short-circuit / detecção de sobrecorrente, per-channel LED status indication
  1. Elétrica & Especificações Ambientais
  2. Consumo de energia

Backplane 5 V: 1.2 C

Campo 24 Alimentação V: 2.2 C

  1. Recursos de proteção

Thermal shutdown upon output short-circuit, inductive load protection, external supply reverse polarity protection

  1. Condições Ambientais

Temperatura operacional: 0 ~ +60 °C

Armazenar & Temperatura de Transporte: -25 ~ +70 °C

Umidade relativa: 5%~95 %, sem condensação

Classe de Proteção: IP20 (for cabinet mounting only)

  1. Especificações Mecânicas

Sistema 2005 single-width module

Peso: aprox.. 0.32 kg

  1. Mandatory Terminals (Not included with module, order separately)

The module is equipped with sockets; terminal blocks must be ordered separately. 2 pcs of 18-pin terminals required

7TB718.9: Screw terminal block, 1.5 mm²

7TB718.91: Cage Clamp spring terminal block, 1.5 mm²

X1 connector: DO1~DO16; X2 connector: DI1~DI16

  1. Compatibilidade de software

Minimum supported Automation Studio version: V2.6

Corresponding hardware upgrade package required: V1.0.1.0

  1. Opções de substituição (Key Information)

1) Drop-in compatible within the same platform (Retain System2005 backplane & CPU)

No direct pin-to-pin upgraded model. Similar reference within series:

3DM476.6: 16DE + 16FAZER, supports DC/AC24 V inputs (different electrical characteristics for selection)

2) Platform Migration (Novos projetos / complete cabinet retrofit, System2005 → X20)

Functionally equivalent combination:

X20DI9371 (16DE) + X20DO9322 (16FAZER)

Vantagens: Stable long-term availability, sufficient stock, enhanced diagnostic functions.

  1. Aplicações Típicas

Máquinas de embalagem, textile equipment, printing presses, legacy production line retrofits; used for signal acquisition from proximity switches and pushbuttons, and driving small loads such as solenoid valves and indicator lamps.

⚠️ Selection & Precauções de manutenção

  1. Output is Sourcing type (PNP). Connect load negative terminal to 0 V; cannot be directly wired for sinking drive.
  2. Do not exceed 0.5 A continuous current per channel; total module output current must not exceed 8 UM.
  3. Freewheeling diodes must be wired in parallel for inductive loads (válvulas solenóides).
  4. System2005 backplane modules cannot be plugged directly into X20 bases; backplane bus protocols are incompatible.
  5. When purchasing discontinued spare parts, distinguish refurbished / used / brand-new surplus stock and confirm warranty terms.

If required, I can provide:

1) Complete terminal pin assignment table

2) Standard DI/DO wiring schematic

3) Configuration key points for Automation Studio hardware setup

B&R 3DM486.6 Hardware Installation Manual (Versão do campo)

Product Platform: B&Sistema R 2005 PCC

Tipo de módulo: 16DE / 16DO Digital Mixed I/O Module

Status: Manufacturer discontinued, for spare part use only

Escopo: Cabinet assembly, fiação, power-on commissioning, solução de problemas

Índice

  1. Instruções de segurança
  2. Produto & Lista de acessórios
  3. Instalação Mecânica (Backplane Mounting Procedure)
  4. Complete Terminal Pin Assignment
  5. Especificações de fiação elétrica (DI/DO Schematic)
  6. Ambiental & Dimensões de montagem
  7. Power-on Inspection & LED Indicator Definition
  8. Automation Studio Configuration Guidelines
  9. Operational Restrictions & Falhas Comuns
  10. Atualizar & Replacement Guidance
  11. Mandatory Safety Instructions
  12. Module insertion / removal must be performed with power disconnected! Hot-plugging System2005 backplane modules is strictly prohibited; it may permanently damage backplane bus interfaces.
  13. Implement ESD protection before handling; wear anti-static wrist strap. Circuit boards are sensitive to electrostatic discharge.
  14. Fuses must be installed for external 24 Fonte de alimentação VCC; reverse polarity of power supply is forbidden.
  15. Freewheeling diodes must be fitted in parallel to inductive loads (válvulas solenóides, contatores) driven by output channels.
  16. Module protection rating IP20, installation inside control cabinet only. Do not expose directly to dust or moisture.
  17. Galvanic isolation exists between DI bank and DO bank; no channel-to-channel isolation. Separate low-level I/O cables from power cables during wiring.
  18. Módulo & Acessórios obrigatórios

Main Module

Modelo: 3DM486.6

Canais: 16×DI (24 VDC Sink/Source) + 16×DO (24 VDC Sourcing transistor output, 0.5 Um por canal)

Terminals to be ordered separately (Not supplied with module)

7TB718.9: 18-pin screw terminal block, max conductor cross-section 1.5 mm²

7TB718.91: 18-pin Cage Clamp spring terminal block, max conductor cross-section 1.5 mm²

Quantity required: 2 blocos terminais (X1 for DO, X2 for DI)

  1. Mechanical Installation Steps for System2005 Backplane
  2. Confirm complete power-off of the entire PCC rack; isolate the power supply module from mains.
  3. Align the bottom guide slots of the module with the DIN rail backplane guides and slide horizontally into the slot.
  4. Press the side latches inward until an audible click confirms the module is locked to the backplane.
  5. Verify the rear gold-plated bus connector is fully seated against the backplane connector without tilting or gaps.

⚠️ Do not pry the module with screwdrivers. Para remover, release side latches and pull the module out parallel to the backplane.

  1. Vertically insert the 7TB718 terminal plugs into the lower X1 and X2 sockets of the module until fully engaged.

Mounting Clearance Requirements

Maintain minimum 25 mm ventilation space above and below each module;

Operating ambient temperature 0 ℃ ~ +60 ℃. Implement cabinet temperature reduction if operating continuously above 55 ℃.

  1. Complete Terminal Pin Assignment

X1 = Output Terminal (DO1~DO16)

X2 = Input Terminal (DI1~DI16)

X1 (DO Output, 18 Alfinete)

AlfineteSinalDescrição
1DO1Saída digital 1
2DO2Saída digital 2
3DO3Saída digital 3
4DO4Saída digital 4
5DO5Saída digital 5
6DO6Saída digital 6
7DO7Saída digital 7
8DO8Saída digital 8
9DO9Saída digital 9
10DO10Saída digital 10
11DO11Saída digital 11
12DO12Saída digital 12
13DO13Saída digital 13
14DO14Saída digital 14
15DO15Saída digital 15
16DO16Saída digital 16
17+24V_OUTCommon positive supply for outputs (internally routed on module)
180V_GNDCommon ground for outputs

✅ Output Type: Sourcing / PNP Output

When DO is activated, +24 V is present on DO pin. Connect one terminal of load to DO, the other terminal to 0 V.

X2 (DI Input, 18 Alfinete)

AlfineteSinalDescrição
1DI1Entrada Digital 1
2ED2Entrada Digital 2
3DI3Entrada Digital 3
4DI4Entrada Digital 4
5DI5Entrada Digital 5
6DI6Entrada Digital 6
7DI7Entrada Digital 7
8DI8Entrada Digital 8
9DI9Entrada Digital 9
10DI10Entrada Digital 10
11DI11Entrada Digital 11
12DI12Entrada Digital 12
13DI13Entrada Digital 13
14DI14Entrada Digital 14
15DI15Entrada Digital 15
16DI16Entrada Digital 16
17COM+24VCommon positive for inputs (used for NPN / Sinking sensors)
18COM_0VCommon ground for inputs (used for PNP / Sourcing sensors)

Two DI Wiring Configurations

  1. PNP Sensor (Sourcing Type)

Sensor positive → DI channel; Sensor negative → 0 V; Connect module X2.18 to field 0 V

  1. NPN Sensor (Sinking Type)

Sensor positive connected to 24 V; Sensor output → DI channel; Connect module X2.17 to field +24 V

Input hardware filter: Fixado em 1 EM, non-adjustable via software.

  1. Classificações Elétricas

Backplane 5 V power draw: 1.2 C

Campo 24 V power draw: 2.2 C

Maximum continuous per-channel output: 0.5 A DC24 V

Global module output current limit: 8 UM; prolonged overload not permitted

Isolamento: Galvanic isolation between DI bank and DO bank; no isolation between individual channels

Proteção: Thermal shutdown for output short-circuit, proteção contra polaridade reversa

  1. Dimensões do Módulo (milímetros)

Largura: 25 (System2005 single-width module)

Altura: 130

Profundidade: 86

Peso: aprox.. 320 g

  1. LED Indicator Definition

One LED assigned per channel on module front face:

DI LED ON: High level detected on corresponding input channel

DO LED ON: Output enabled in program and hardware output switched ON

Power status: Standby LEDs illuminated when backplane supply is normal; no LED response upon backplane communication failure.

  1. Automation Studio Hardware Configuration Guidelines
  2. Minimum supported AS version: V2.6 and above
  3. Hardware library selection: `3DM486.6` System 2005 DM module
  4. Address mapping: Follow rack slot sequence; slot numbering starts from CPU and extends backward
  5. Diagnostics support: Software readable faults for output short-circuit and overload

Important: Cannot be installed directly onto X20 backplane; bus protocols are incompatible!

  1. Fault Troubleshooting Matrix
Sintoma de falhaPossible Root CauseAção Corretiva
No LED illumination on moduleBackplane power absent / Poor module seating / Damaged backplaneRe-seat module after full power-off; Inspect 3PS465/3PS476 power supply modules
DO LED ON, external load inactiveMissing external 24 Alimentação V, cable break, failed loadMeasure voltage at X1.17/18; Inspect load wiring
Recurring short-circuit alarms on outputsShorted load, per-channel current exceeding 0.5 UM, missing freewheeling diode for inductive loadsInstall freewheeling diodes; distribute load current; Inspect cables for insulation damage
Fluctuating DI signalsInterferência eletromagnética, insufficient filtering, excessively long cablesRoute DI cables separately; add RC snubber circuits; check supply voltage ripple
Individual channel failureChannel burned out due to overcurrent; non-repairableSubstitua o módulo
  1. Retrofit & Replacement Guidance

Same Platform Compatibility (No CPU/Backplane Modification)

Similar model: 3DM476.6 (Supports AC24 V inputs; pin assignment differs, wiring modification required)

Platform Upgrade System2005 → X20 (Recommended for New Projects)

Functionally equivalent combination:

X20DI9371 (16DE) + X20DO9322 (16FAZER)

Vantagens: Long-term production availability, stable spare part supply, enhanced diagnostic capability.

  1. Wiring Engineering Specifications
  2. Separate I/O signal cables from power cables, minimum separation distance ≥30 cm; use shielded cables if separation cannot be achieved.
  3. Install independent fuses for all 24 VDC circuits (3~5 A recommended rating).
  4. Implement single-point earthing inside control cabinet; reliably connect signal ground and protective earth.
  5. Recommended cable cross-section: 0.75~1.0 mm².