Informações Básicas
Modelo:3DM486.6
Marca: B&R Automação
Família de produtos: Sistema 2005 (Legacy PCC Backplane System)
Tipo de módulo: Digital Módulo de E/S misto
⚠️ Estado: Manufacturer Discontinued (Obsoleto). Only stock and second-hand spare parts available. New projects are recommended to migrate to the X20 series.
- Core Channel Specifications
| Item | Parâmetro |
| Entrada Digital (DE) | 16 canais, 24 CCV, Sink/Source compatible (NPN/PNP universal) |
| Input Filter Time | 1 EM |
| Saída digital (FAZER) | 16 canais, Transistor Sourcing Output, 24 CCV |
| Per-channel Output Current | 0.5 UM / apontar |
| Maximum Total Module Output Current | 8 UM |
| Isolamento Elétrico | Galvanic isolation between input bank and output bank; sem isolamento entre canais individuais |
| Diagnóstico | Output short-circuit / detecção de sobrecorrente, per-channel LED status indication |
- Elétrica & Especificações Ambientais
- Consumo de energia
Painel traseiro 5 V: 1.2 C
Campo 24 Alimentação V: 2.2 C
- Recursos de proteção
Thermal shutdown upon output short-circuit, inductive load protection, external supply reverse polarity protection
- Condições Ambientais
Temperatura operacional: 0 ~ +60 °C
Armazenar & Temperatura de Transporte: -25 ~ +70 °C
Umidade relativa: 5%~95 %, sem condensação
Classe de Proteção: IP20 (for cabinet mounting only)
- Especificações Mecânicas
Sistema 2005 single-width module
Peso: aprox.. 0.32 kg
- Mandatory Terminals (Não incluído no módulo, encomendar separadamente)
The module is equipped with sockets; terminal blocks must be ordered separately. 2 pcs of 18-pin terminals required
7TB718.9: Bloco terminal de parafuso, 1.5 mm²
7TB718.91: Cage Clamp spring terminal block, 1.5 mm²
X1 connector: DO1~DO16; X2 connector: DI1~DI16
- Compatibilidade de software
Minimum supported Automation Studio version: V2.6
Corresponding hardware upgrade package required: V1.0.1.0
- Opções de substituição (Informações importantes)
1) Drop-in compatible within the same platform (Retain System2005 backplane & CPU)
No direct pin-to-pin upgraded model. Similar reference within series:
3DM476.6: 16DE + 16FAZER, supports DC/AC24 V inputs (different electrical characteristics for selection)
2) Platform Migration (Novos projetos / complete cabinet retrofit, Sistema2005 → X20)
Functionally equivalent combination:
X20DI9371 (16DE) + X20DO9322 (16FAZER)
Vantagens: Stable long-term availability, sufficient stock, enhanced diagnostic functions.
- Aplicações Típicas
Máquinas de embalagem, equipamento têxtil, impressoras, legacy production line retrofits; used for signal acquisition from proximity switches and pushbuttons, and driving small loads such as solenoid valves and indicator lamps.
⚠️ Selection & Precauções de manutenção
- Output is Sourcing type (PNP). Connect load negative terminal to 0 V; cannot be directly wired for sinking drive.
- Do not exceed 0.5 A continuous current per channel; total module output current must not exceed 8 UM.
- Freewheeling diodes must be wired in parallel for inductive loads (válvulas solenóides).
- System2005 backplane modules cannot be plugged directly into X20 bases; backplane bus protocols are incompatible.
- When purchasing discontinued spare parts, distinguish refurbished / usado / brand-new surplus stock and confirm warranty terms.
Se necessário, Eu posso fornecer:
1) Complete terminal pin assignment table
2) Standard DI/DO wiring schematic
3) Configuration key points for Automation Studio hardware setup
B&R 3DM486.6 Hardware Installation Manual (Versão do campo)
Plataforma de Produto: B&Sistema R 2005 PCC
Tipo de módulo: 16DE / 16DO Digital Mixed I/O Module
Status: Manufacturer discontinued, for spare part use only
Escopo: Cabinet assembly, fiação, power-on commissioning, solução de problemas
Índice
- Instruções de segurança
- Produto & Lista de acessórios
- Instalação Mecânica (Backplane Mounting Procedure)
- Complete Terminal Pin Assignment
- Especificações de fiação elétrica (DI/DO Schematic)
- Ambiental & Dimensões de montagem
- Power-on Inspection & Definição do indicador LED
- Automation Studio Configuration Guidelines
- Operational Restrictions & Falhas Comuns
- Atualizar & Replacement Guidance
- Mandatory Safety Instructions
- Module insertion / removal must be performed with power disconnected! Hot-plugging System2005 backplane modules is strictly prohibited; it may permanently damage backplane bus interfaces.
- Implement ESD protection before handling; wear anti-static wrist strap. Circuit boards are sensitive to electrostatic discharge.
- Fuses must be installed for external 24 Fonte de alimentação VCC; reverse polarity of power supply is forbidden.
- Freewheeling diodes must be fitted in parallel to inductive loads (válvulas solenóides, contatores) driven by output channels.
- Module protection rating IP20, installation inside control cabinet only. Do not expose directly to dust or moisture.
- Galvanic isolation exists between DI bank and DO bank; no channel-to-channel isolation. Separate low-level I/O cables from power cables during wiring.
- Módulo & Acessórios obrigatórios
Main Module
Modelo: 3DM486.6
Canais: 16×DI (24 VDC Sink/Source) + 16×DO (24 VDC Sourcing transistor output, 0.5 Um por canal)
Terminals to be ordered separately (Not supplied with module)
7TB718.9: 18-bloco terminal de parafuso de pino, max conductor cross-section 1.5 mm²
7TB718.91: 18-pin Cage Clamp spring terminal block, max conductor cross-section 1.5 mm²
Quantity required: 2 blocos terminais (X1 for DO, X2 for DI)
- Mechanical Installation Steps for System2005 Backplane
- Confirm complete power-off of the entire PCC rack; isolate the power supply module from mains.
- Align the bottom guide slots of the module with the DIN rail backplane guides and slide horizontally into the slot.
- Press the side latches inward until an audible click confirms the module is locked to the backplane.
- Verify the rear gold-plated bus connector is fully seated against the backplane connector without tilting or gaps.
⚠️ Do not pry the module with screwdrivers. Para remover, release side latches and pull the module out parallel to the backplane.
- Vertically insert the 7TB718 terminal plugs into the lower X1 and X2 sockets of the module until fully engaged.
Requisitos de folga de montagem
Maintain minimum 25 mm ventilation space above and below each module;
Temperatura ambiente operacional 0 ℃ ~ +60 ℃. Implement cabinet temperature reduction if operating continuously above 55 ℃.
- Complete Terminal Pin Assignment
X1 = Output Terminal (DO1~DO16)
X2 = Input Terminal (DI1~DI16)
X1 (DO Output, 18 Alfinete)
| Alfinete | Sinal | Descrição |
| 1 | DO1 | Saída digital 1 |
| 2 | DO2 | Saída digital 2 |
| 3 | DO3 | Saída digital 3 |
| 4 | DO4 | Saída digital 4 |
| 5 | DO5 | Saída digital 5 |
| 6 | DO6 | Saída digital 6 |
| 7 | DO7 | Saída digital 7 |
| 8 | DO8 | Saída digital 8 |
| 9 | DO9 | Saída digital 9 |
| 10 | DO10 | Saída digital 10 |
| 11 | DO11 | Saída digital 11 |
| 12 | DO12 | Saída digital 12 |
| 13 | DO13 | Saída digital 13 |
| 14 | DO14 | Saída digital 14 |
| 15 | DO15 | Saída digital 15 |
| 16 | DO16 | Saída digital 16 |
| 17 | +24V_OUT | Common positive supply for outputs (internally routed on module) |
| 18 | 0V GND | Common ground for outputs |
✅ Output Type: Fornecimento / PNP Output
When DO is activated, +24 V is present on DO pin. Connect one terminal of load to DO, the other terminal to 0 V.
X2 (Entrada DI, 18 Alfinete)
| Alfinete | Sinal | Descrição |
| 1 | DI1 | Entrada Digital 1 |
| 2 | ED2 | Entrada Digital 2 |
| 3 | DI3 | Entrada Digital 3 |
| 4 | DI4 | Entrada Digital 4 |
| 5 | DI5 | Entrada Digital 5 |
| 6 | DI6 | Entrada Digital 6 |
| 7 | DI7 | Entrada Digital 7 |
| 8 | DI8 | Entrada Digital 8 |
| 9 | DI9 | Entrada Digital 9 |
| 10 | DI10 | Entrada Digital 10 |
| 11 | DI11 | Entrada Digital 11 |
| 12 | DI12 | Entrada Digital 12 |
| 13 | DI13 | Entrada Digital 13 |
| 14 | DI14 | Entrada Digital 14 |
| 15 | DI15 | Entrada Digital 15 |
| 16 | DI16 | Entrada Digital 16 |
| 17 | COM+24V | Common positive for inputs (used for NPN / Sinking sensors) |
| 18 | COM_0V | Common ground for inputs (used for PNP / Sourcing sensors) |
Two DI Wiring Configurations
- Sensor PNP (Sourcing Type)
Sensor positive → DI channel; Sensor negative → 0 V; Connect module X2.18 to field 0 V
- Sensor NPN (Sinking Type)
Sensor positive connected to 24 V; Sensor output → DI channel; Connect module X2.17 to field +24 V
Input hardware filter: Fixado em 1 EM, non-adjustable via software.
- Classificações Elétricas
Painel traseiro 5 V power draw: 1.2 C
Campo 24 V power draw: 2.2 C
Maximum continuous per-channel output: 0.5 A DC24 V
Global module output current limit: 8 UM; prolonged overload not permitted
Isolamento: Galvanic isolation between DI bank and DO bank; sem isolamento entre canais individuais
Proteção: Thermal shutdown for output short-circuit, proteção contra polaridade reversa
- Dimensões do Módulo (milímetros)
Largura: 25 (System2005 single-width module)
Altura: 130
Profundidade: 86
Peso: aprox.. 320 g
- Definição do indicador LED
One LED assigned per channel on module front face:
DI LED ON: High level detected on corresponding input channel
DO LED ON: Output enabled in program and hardware output switched ON
Power status: Standby LEDs illuminated when backplane supply is normal; no LED response upon backplane communication failure.
- Automation Studio Hardware Configuration Guidelines
- Minimum supported AS version: V2.6 and above
- Hardware library selection: `3DM486.6` System 2005 DM module
- Address mapping: Follow rack slot sequence; slot numbering starts from CPU and extends backward
- Diagnostics support: Software readable faults for output short-circuit and overload
Importante: Cannot be installed directly onto X20 backplane; bus protocols are incompatible!
- Matriz de solução de problemas de falhas
| Sintoma de falha | Possível causa raiz | Ação Corretiva |
| No LED illumination on module | Backplane power absent / Poor module seating / Damaged backplane | Re-seat module after full power-off; Inspect 3PS465/3PS476 power supply modules |
| DO LED ON, external load inactive | Missing external 24 Alimentação V, cable break, failed load | Measure voltage at X1.17/18; Inspect load wiring |
| Recurring short-circuit alarms on outputs | Shorted load, per-channel current exceeding 0.5 UM, missing freewheeling diode for inductive loads | Install freewheeling diodes; distribute load current; Inspect cables for insulation damage |
| Fluctuating DI signals | Interferência eletromagnética, insufficient filtering, excessively long cables | Route DI cables separately; add RC snubber circuits; check supply voltage ripple |
| Individual channel failure | Channel burned out due to overcurrent; não reparável | Substitua o módulo |
- Reforma & Replacement Guidance
Same Platform Compatibility (No CPU/Backplane Modification)
Similar model: 3DM476.6 (Supports AC24 V inputs; pin assignment differs, modificação de fiação necessária)
Platform Upgrade System2005 → X20 (Recomendado para novos projetos)
Functionally equivalent combination:
X20DI9371 (16DE) + X20DO9322 (16FAZER)
Vantagens: Long-term production availability, stable spare part supply, enhanced diagnostic capability.
- Wiring Engineering Specifications
- Separate I/O signal cables from power cables, minimum separation distance ≥30 cm; use shielded cables if separation cannot be achieved.
- Install independent fuses for all 24 VDC circuits (3~5 A recommended rating).
- Implement single-point earthing inside control cabinet; reliably connect signal ground and protective earth.
- Recommended cable cross-section: 0.75~1.0 mm².