Danfoss FC-051P2K2T4E20H3BXCXXXSXXX Variable Frequency Drive - Contator,disjuntor,inversor solar,medidor elétrico,baterias solares

Conversamos: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Sobre Contato |

Danfoss FC-051P2K2T4E20H3BXCXXXSXXX Variable Frequency Drive - Contator,disjuntor,inversor solar,medidor elétrico,baterias solares

elétrica/

Danfoss FC-051P2K2T4E20H3BXCXXXSXXX Variable Frequency Drive

Ordem Oficial nº.:132F0022 ⚠️ Important Notice: Danfoss FC51 series is approaching end-of-life. Final order cutoff date: 30 Jun 2026; final delivery cutoff date: 30 Sep 2026. Para novos projetos, evaluation of iC2-Micro as alternative is recommended. Model Code Decoding Code Description FC-051 Série de produtos: VLT Micro Drive FC51 compact general-purpose variable frequency drive P2K2 Rated ...

  • Detalhes do produto

Ordem Oficial nº.:132F0022

⚠️ Important Notice: Danfoss FC51 series is approaching end-of-life. Final order cutoff date: 30 Jun 2026; final delivery cutoff date: 30 Sep 2026. Para novos projetos, evaluation of iC2-Micro as alternative is recommended.

  1. Model Code Decoding
CódigoDescrição
FC-051Série de produtos: VLT Micro Drive FC51 compact general-purpose unidade de frequência variável
P2K2Potência nominal: 2.2 kW (3 HP)
T43-entrada de fase, 380–480 V AC (50/60 Hz)
E20Ingress protection rating: IP20 (chassis mounting, for cabinet internal installation)
H3Built-in Class A1/B RFI filter (Category C1 environment)
BIntegrated brake chopper (external brake resistor connectable)
XWithout local control panel LCP (LCP11/LCP12 must be ordered separately if required)
CPCB with conformal coating, suitable for humid and dusty harsh environments
XXXNo auxiliary power modules equipped
SXXXStandard factory firmware version
  1. Parâmetros elétricos principais

Matched motor: 3-phase asynchronous motor, 2.2 kW

Corrente de saída nominal: 5.3 UM

Capacidade de sobrecarga: 150% de corrente nominal para 60 segundos

Control modes: VVC+ vector control / U/f control

Faixa de frequência de saída: 0–200 Hz (VVC+); 0–400 Hz (U/f)

Comunicação: Onboard RS485 (Modbus RTU)

Tamanho do quadro: M2

Peso líquido: 1.75 kg; Gross weight: 1.95 kg

III. Standard Hardware Configuration

✅ Built-in EMC filter

✅ Integrated brake chopper

✅ Conformal coated printed circuit board

❌ No control panel supplied (commissioning requires external panel or MCT10 software)

❌ Brake resistor not included (a ser encomendado separadamente)

  1. Aplicações Típicas

Fãs, bombas de água, transportadores, máquinas de embalagem, pequenas máquinas-ferramentas, equipamento de mistura, textile machinery and other general constant-torque / variable-torque loads.

  1. Aquisições & Replacement Tips
  2. Stock availability is tight as FC51 enters end-of-life phase;
  3. Next-generation direct alternative model: iC2-Micro 2.2 kW, 3-fase 400 V;
  4. Optional panels for this unit:

LCP11: Digital panel (without potentiometer)

LCP12: Digital panel with built-in potentiometer;

  1. Wiring reminder: Maximum shielded motor cable length applies when the built-in H3 filter is activated.

FC-051P2K2T4E20H3BXCXXXSXXX (Order No.132F0022|Frame M2, 2.2 kW, 380 V) Full List of Compatible Accessories

The drive is delivered without control panel, brake resistor and door-mount kit. Below are original manufacturer compatible models sorted by application:

  1. Local Control Panels (Essential for Commissioning)
Número do pedido.ModeloDescrição
132B0100LCP11Digital control panel, without potentiometer, IP54 rated panel, for basic parameter setting and parameter copying
132B0101LCP12Digital control panel with integrated potentiometer, supports local speed adjustment, preferred for on-site commissioning

⚠️ Code X in model designation = panel excluded; panel must be purchased separately.

  1. Remote Door-Mount Kits for Control Panels
Número do pedido.EspecificaçãoPropósito
132B01121.5 m cable door mounting kitMount LCP11/LCP12 on control cabinet door
132B01023 m cable door mounting kitLong-distance cabinet door installation, including sealing assembly

III. Proteção & Mounting Upgrade Kits (For M2 Frame Only)

Número do pedido.NomeFunção
132B0109IP21 Protection Kit for M2Original unit IP20; protection class upgraded to IP21 (NEMA Type1) após a instalação
132B0106De-coupling partition kit M1/M2Improve heat dissipation and reduce electromagnetic interference for multi-drive side-by-side installation

DIN rail mounting kit is only available for M1 frame. M2 frame does NOT support DIN rail mounting.

  1. Sistema de freio (Code B = Built-in Brake Chopper)

Recommended Brake Resistor Specifications (Danfoss Official Specification)

Minimum resistance value: 90 Oh

Recommended power rating: ≥200 W (normal start-stop); selecione 400 W for frequent braking

Danfoss does not provide standard brake resistors with dedicated order numbers. Source externally according to 90 Oh / ≥200 W specification. Increase power rating for heavy-duty cycles.

  1. Comissionamento & Acessórios de comunicação
  2. PC commissioning cable

FC51 has onboard RS485 terminals. Use USB-to-RS485 adapter together with free MCT10 commissioning software (available for download on official website; Order No.130B1000 refers to software CD media).

  1. Fieldbus Expansion Note

FC51 has no slots for optional communication cards. Only native Modbus RTU over RS485 is supported; Profibus, EtherNet/IP and other fieldbuses cannot be added.

  1. Optional Filter & Reactors

This unit is equipped with built-in H3 = Class A1/B RFI filter (Category C1)

No extra input EMC filter required for standard cabinet installation;

For long motor cables or high-interference sites: install external 3-phase input AC line reactor (6 A reactor matched for 2.2 kW, 400 Sistema V)

Use shielded motor cables; recommended maximum cable length ≤15 m when built-in filter is enabled.

VII. Peças de reposição (M2 Frame)

132B0127|FC51 M2 Frame spare parts pack (terminal cover, RS485 connector, earthing screws)

VIII. Matching Drive Motor (Standard Selection)

3-phase asynchronous motor 2.2 kW, 380 V; rated current ≈4.8~5.2 A, compatible with drive rated output current 5.3 UM

  1. Next-Generation Alternative Inverter (FC51 End-of-Life Backup)

iC2-Micro 2.2 kW 3-phase 400 V. Highly compatible terminal definitions and installation dimensions, applicable as replacement for new projects.

Quick Selection Guidelines

  1. Single unit on-site commissioning: LCP12 (132B0101) recomendado;
  2. Cabinet door operation required: select 132B0112 (1.5 eu) / 132B0102 (3 eu);
  3. Frequent start-stop and rapid braking: externally source 90 Ω ≥200 W brake resistor;
  4. Multiple drives installed side-by-side: equip M2 de-coupling partition kit 132B0106.

Anterior:

Deixe uma resposta

Deixe um recado