Informações Básicas
Modelo: 200FEE
Tipo: BS88 Part4 / IEC60269-4 high-speed bolted dual-barrel fusível, aR class (for semiconductor protection only)
Corrente nominal: 200UM
Especificações Elétricas
IEC Rating: 690V e / 500Em DC
UL Rating: 700V e / 500Em DC
Quebrando Capacidade: 200o (AC rms); 50kA @500V DC
Pre-arcing I²t: 1900; Total clearing I²t: 7100@415V, 11400@660V
Dissipação de energia: 52C
No built-in fuse indicator; external kits TI700, MAI / MBI microswitch assemblies are available
Dimensões de montagem
Parafuso de montagem: M8
Terminal Centre Spacing: 71milímetros
Construção: Offset dual-barrel, bolt-connected blade terminals (blade end × blade end)
Tamanho total: 187mm de largura, 100mm de comprimento, 22mm high, Peso líquido: 89.6g
Aprovações & Padrões
CE, RoHS, Reconhecido pela UL
Padrões: BS88 Part4, CEI 60269-4
Aplicações Típicas
Short-circuit protection for frequency converters, retificadores, DC busbars, DC drives, thyristors and IGBT power semiconductors
Reference Models in the Same Series (FEE Series)
100FEE, 125FEE, 160FEE, 200FEE, 250FEE, 315FEE, etc.. Same design logic, only rated current differs
Notas de substituição
This is a BS88-4 aR high-speed semiconductor fuse. For domestic alternatives, verificar: aR classification, I²t value, capacidade de interrupção, M8 mounting and 71mm centre spacing. Ordinary gG/gL distribution fuses cannot be used as substitutes.
The 200FEE (FEE series BS88 Part4 aR high-speed dual-barrel fuse) has no original standard moulded fuse holder.
It is designed as M8 bolt-on blade terminals (blade end). The standard installation method is direct mounting onto busbars. Holders such as RS200H (Red Spot) are not required (RS200H is for BS88-2 gG distribution fuses and is incompatible with FEE high-speed semiconductor fuses).
Acessórios opcionais (Not Holders – Indicator / Microswitch Kits)
TI700: Fuse indicator kit (indicator flag + grampo)
MAI: Microswitch adapter (fuse blown alarm signal)
MBI: Microswitch adapter (alternative construction)
Two Engineering Solutions
- Standard Solution (Most common for VFD / DC busbars)
Direct busbar mounting with M8 bolts, 71mm terminal centre spacing. TI700 / MAI / MBI may be fitted for blown-fuse signalling as required.
- IP20 Enclosed Holder (Solução Alternativa)
No original Bussmann holder is available. Only third-party bolt-on high-speed fuse holders can be selected. Mandatory selection criteria:
Compatible with M8 terminals, 71mm centre spacing, rated ≥200A, 690V, aR class, breaking capacity ≥200kA
All FEE series models (100FEE /125FEE /160FEE /200FEE /250FEE /315FEE) adopt the same busbar bolt-on design; no original holders are supplied.
200FEE (FEE Series BS88 Part4) Torque de instalação & Tightening Specification
Observação: The manufacturer datasheet does not specify torque for this individual model. The values below are industry standard practice for Eaton BS88 fuses and busbar connections, widely used for VFD and DC bus projects.
Tamanho do parafuso: M8 (coarse pitch 1.25), 8.8 grade galvanized bolts preferred
✅ Recommended Torque: 10 N·m (±1 N·m)
Acceptable Range: 9 N·m (min) ~ 12 N·m (máx.)
Do not exceed 12 N·m: risk of deforming fuse copper terminals and uneven contact surfaces. Torque below 9 N·m causes high contact resistance, overheating and nuisance blowing.
- Washer Stack Order (from busbar outwards)
Busbar → Fuse blade terminal → Plain washer → Spring washer → Nut
Prohibited: Spring washer between fuse terminal and copper busbar; stacking multiple lugs on one side of a fuse terminal.
- Contact Surface Preparation (Critical – aR high-speed fuses are sensitive to contact resistance)
- Clean copper busbar and fuse terminal contact faces: remove oxidation with scouring pad / fine abrasive paper until bright, then wipe with isopropyl alcohol.
- A thin layer of conductive grease (joint compound) é permitido. Do not apply thick layers, to avoid creepage risk from excess grease squeezing out.
- Contact surfaces must be fully mated, free of burrs, gaps and trapped debris.
- Após a instalação, contact resistance can be checked with a micro-ohmmeter; target per terminal: <50mΩ.
- Tightening Procedure
- Hand-thread first to align the fuse, keep both terminals parallel and centred.
- Tighten with a torque wrench in one smooth movement; avoid repeated back-and-forth adjustment.
- Mark the bolt/nut with paint after torque is achieved for tamper/loosening check.
- Thermal recheck: after initial energising and 2 hours of load operation, power off and recheck torque. Annual inspection is recommended for long-term service.
- Acessórios (TI700 / MAI / MBI)
Microswitches and indicator flags are clip-on accessories. They do not share the main circuit M8 bolts. Do not squeeze or pull the fuse body during fitting; do not alter the compression of the main electrical joint.
- Práticas Proibidas
Do not use A2-70 stainless steel bolts and over-torque (stainless steel has lower yield strength and is prone to thread stripping).
Do not use impact wrenches for final tightening.
Do not force uneven or mismatched busbar thicknesses together.
Do not apply mechanical load or pry on the fuse body.
- Common for All FEE Series
100FEE /125FEE /160FEE /200FEE /250FEE /315FEE all use M8 terminals with the same 10 N·m torque specification.
Contator,disjuntor,sensor,Codificador,CLP,Conversor