Conductive multi-point level electrode (conductivity level sensor), used for multi-point level detection of conductive liquids. Usually paired with Carlos Gavazzi level relays (such as VN-series controllers).
✅ Model Definition
VNY: Y-type conductive level probe with standard nylon housing and screw terminal wiring (no pre-wired cable).
4: 4 electrode rods, enabling level detection at 4 measuring points.
Related models: VNY1 / VNY2 / VNY3 / VNY4; VN = cable outlet type; VNI = isolated electrode version.
📌 Key Specifications
- Eletrodos: 4 AISI316 stainless steel probes, 5 mm diameter, standard length 1 m (can be cut on-site as required).
- Habitação: Red nylon, montagem roscada. Especificação de thread: 1½” ISO228-1 pipe thread.
- Fiação: Terminais de parafuso, Classificação de proteção IP67.
- Princípio de medição: Conductivity type. Only suitable for conductive liquids (água, sewage, coolant, etc.); NOT for pure deionized water or oils.
- Medium temperature range: 0~90℃.
- Aplicativo: Alto / nível baixo, multi-stage level alarm, water tank / sump level control.
🛠 Typical Applications
Fornecimento de água & drenagem, sewage lift pits, torres de resfriamento, boiler water make-up, water treatment equipment
AVAC, conductive liquid level monitoring in food & indústria de bebidas, industrial tank level switches
📋 Selection Guidelines
The VNY4 is only an electrode probe. It cannot operate standalone. It must be connected to an external conductivity level controller (por exemplo. Carlo Gavazzi VN-series level relays).
Electrode length: Standard 1 m. Can be cut on-site; take care with insulating sleeves.
Medium restrictions: Oils, pure water and non-conductive liquids cannot be measured. Use special material versions for highly corrosive media.
Instalação: Top-mounted vertical installation. Electrodes must not touch each other and should be kept away from tank walls.
🔁 Cross-reference & Alternativas
VN4: Same 4-electrode design with PVC cable outlet instead of screw terminals.
VNYI4: 4-electrode isolated electrode version, preferred for scaling or interference-prone conditions.
Alternativa doméstica: Local conductive level rod (4-pólo, 316eu, 1.5″ fio, IP67).
⚠️ Common Troubleshooting
- False switching: Electrode scaling → grind and clean; low liquid conductivity makes conductivity technology unsuitable.
- Sem sinal: Fiação solta, short circuit from electrodes touching tank wall, controller power supply fault.
- Corrosão: High chloride content in medium → upgrade to titanium electrode version.
Carlo Gavazzi VNY4 (4‑pole Conductivity Level Electrode) Casos de aplicação
VNY4 advantage: 4 measuring points, which can simultaneously implement: low-low level (proteção contra funcionamento a seco da bomba), nível baixo (pump start), high level (pump stop), high-high level (overflow alarm). No mechanical sticking issues as seen with float switches. Used with Carlo Gavazzi CLD4MA / CLP4MA level relays.
Caso 1: HVAC Cooling Tower Make-up Water Tank (Prédio / Factory HVAC)
Working condition: Cooling tower make-up tank, industrial circulating water, temperature 0~60℃. Liquid contains ions and is conductive.
4-point assignment
- LL Low-low level: Interlock to shut off make-up pump to prevent dry-running.
- L Low level: Activate make-up solenoid valve / make-up pump.
- H High level: Stop water make-up.
- HH High-high level: Acoustic & visual overflow alarm.
Selection reason: VNY4 nylon housing resists water vapour, IP67, tank-top 1½” montagem roscada. Not affected by flow turbulence unlike float switches.
Observação: For heavily scaling water, prefer VNYI4 isolated electrode version to reduce false triggering.
Caso 2: Sewage Lift Pit / Underground Sump (Fornecimento de água & Tratamento de Águas Residuais)
Working condition: Domestic sewage, impurity-laden conductive wastewater, automatic drainage control for sewage pump rooms.
4-point assignment
- LL: Extremely low level, block drain pump start (proteção contra funcionamento a seco).
- eu: Low water level, start pump 1.
- H: High water level, stop pump 1; further level rise triggers standby pump 2.
- AH: Ultra-high level, overflow alarm, sinal para PLC / building automation system.
Características: Sewage carries solids which often jam float switches. Conductive electrodes have no moving parts and longer maintenance intervals.
Risk note: Regular electrode grinding and cleaning required for scaling sewage. Upgrade to titanium electrodes for high-chloride wastewater.
Caso 3: Comida & Beverage Process Tanks (CIP Cleaning Water, Conductive Dosing Liquids)
Working condition: CIP cleaning tanks in beverage plants, ion-containing water tanks, fermenter cleaning fluids. Conductive medium, max temperature 90℃.
4-point logic: Low-low protection, low level feed start, high level feed stop, high-high overflow alarm, interlock inlet valve.
Limitação: Pure deionized water cannot be used. For viscous syrup media, VNYI4 isolated electrode is recommended to avoid false level readings from liquid clinging.
Caso 4: Boiler Softened Water / Raw Water Pre-treatment Tanks (Indústria de tratamento de água)
Working condition: Raw water tanks and softening tanks in water plants and boiler rooms, tap water / groundwater.
Lógica de controle: 4-stage level for automatic water make-up plus two-stage safety alarm, interlocked with PLC for pump house monitoring.
Vantagem: AISI316 electrodes resist chloride corrosion from tap water. Probes can be cut on-site to match tank depth.
Caso 5: Small Chemical Storage Tanks (Dilute Conductive Acid / Alkali Solutions)
Working condition: Dilute acid, alkali conductive waste liquid tanks, process safety interlock.
4 measuring points: Low-low level (feed pump protection), low level start feed, high level stop feed, high-high level overflow emergency inlet valve shutoff.
Observação: Material assessment required for strongly corrosive media. Standard VNY4 is only suitable for weakly corrosive dilute solutions; special electrodes for heavy corrosion.
Caso 6: Vehicle Wash Circulation Water Tank (Automotive Washing Machine OEM)
Working condition: Recirculating clean water tank for car wash equipment, conductive aqueous detergent solution, high vibration environment.
4 pontos: Proteção contra funcionamento a seco, make-up start, make-up stop, overflow alarm, integrated into the wash machine control cabinet.
For heavy vibration applications, VN4 cable outlet version can replace VNY screw terminal model to prevent loose terminals.
Seleção Geral & Notas de aplicação
- Medium must be conductive. Oils, ultra-pure water and organic solvents cannot use VNY4. Capacitance level probes are required instead.
- VNY4 is only a probe. Must be paired with 4-point level controllers such as CLD4MA / CLP4MA and cannot be wired directly to PLC.
- Metal tanks can use the tank body as common electrode. For non-metallic tanks, o 4 electrodes include the common electrode.
- Instalação: Vertical tank-top mounting. Electrodes must be kept away from tank walls and must not short-circuit against each other.
Failure Prediction (Common On-site Issues)
Scaling: Sludge / limescale on electrode surface causes unstable level signals → regular grinding and cleaning. Use VNYI4 isolated electrode for scaling-prone media.
Low liquid conductivity: Unstable signals. Conductivity technology is not suitable; switch to ultrasonic or capacitance level meter.
Carlo Gavazzi V-series Conductive Level Probes Full Model List
Main core series: VN / VNY / VNI / VNYI (1½” rosca de tubo, AISI316 electrodes, standard rod length 1000 mm); auxiliary compact series: VPC, PPV, TV / VTI
- VNY Series (Screw terminal wiring, standard non-isolated electrodes, VNY4 parent series)
VNY1: 1 electrode
VNY2: 2 eletrodos
VNY3: 3 eletrodos
VNY4: 4 electrodes ✅
- VNYI Series (Terminais de parafuso, isolated electrode version, preferred for scaling / material clinging conditions)
VNYI1: 1 electrode
VNYI2: 2 eletrodos
VNYI3: 3 eletrodos
VNYI4: 4 eletrodos
- VN Series (PVC cable outlet, 2 m standard cable, standard non-isolated electrodes)
VN1: 1 electrode
VN2: 2 eletrodos
VN3: 3 eletrodos
VN4: 4 eletrodos
- VNI Series (PVC cable outlet, 2 m standard cable, isolated electrodes)
VNI1: 1 electrode
VNI2: 2 eletrodos
VNI3: 3 eletrodos
VNI4: 4 eletrodos
VN / VNI cables can be extended. Exemplo: VNI1-10M = 10-metre cable version.
- VPC Compact PVC Housing Series (Small threads, short electrodes, for small equipment)
VPC105: 1 electrode, ½” fio, 500 mm electrode length
VPC205: 2 eletrodos, ½” fio, 500 mm electrode length
VPC110: 1 electrode, 1″ fio, 1000 mm electrode length
VPC210: 2 eletrodos, 1″ fio, 1000 mm electrode length
VPC310: 3 eletrodos, 1″ fio, 1000 mm electrode length
- VPP PVDF Insulation Corrosion-resistant Series (Small threads)
VPP105: 1 electrode, ½” fio
VPP205: 2 eletrodos, ½” fio
VPP110: 1 electrode, 1″ fio
VPP210: 2 eletrodos, 1″ fio
VPP310: 3 eletrodos, 1″ fio
- TV / VTI Teflon Insulated Series (Strongly corrosive applications)
VT1 / VTI1: 1 electrode
VT2 / VTI2: 2 eletrodos
VT3 / VTI3: 3 eletrodos
VT4 / VTI4: 4 eletrodos
VT = standard; VTI = isolated electrode; 1 m silicone cable outlet.
Series Comparison Table
| Série | Tipo de saída | Isolamento de eletrodo | Habitação | Fio | Aplicação Típica |
| VNY | Terminal de parafuso | Padrão | Nylon 6 | 1½” | Water tanks, torres de resfriamento, local cabinet wiring (VNY4) |
| VNYI | Terminal de parafuso | PE isolated | Nylon 6 | 1½” | Sewage, scaling-prone or viscous conductive liquids |
| VN | 2m cabo de PVC | Padrão | Nylon 6 | 1½” | Tank top where cable routing is easier than terminal wiring |
| VNI | 2m cabo de PVC | PE isolated | Nylon 6 | 1½” | Scaling applications with direct cable exit |
| VPC | Terminal de parafuso | Educação Física | PVC | ½”/1″ | Máquinas pequenas, compact tanks |
| PPV | Terminal de parafuso | PVDF | PP | ½”/1″ | Mildly corrosive media |
| VT/VTI | 1m silicone cable | Teflon | Teflon | 1½” | Dilute acid / alkali chemical corrosion |
Matching Controllers (Obrigatório; probe cannot work alone)
CLD4MA, CLP4MA (4-point level relays, compatible with VNY4 / VNYI4 / VN4 / VNI4); CLD2MA for 2-electrode probes; CLD3MA for 3-electrode probes.
Naming Rule Summary
- VNY = V+NY (NY = Nylon + Terminal de parafuso, nylon housing with screw terminals)
- VN = V+N (nylon housing, saída de cabo)
- Suffix I = Isolated electrode (prevents false triggering from liquid film clinging)
- Final digit = number of electrodes (1/2/3/4)