CHINT NM1LE-250S-4300-200A MCCB - Contator,disjuntor,inversor solar,medidor elétrico,baterias solares

disjuntor/

CHINT NM1LE-250S-4300-200A MCCB

MarcaReplacement Model
SchneiderEZD250E4200ELN (integrated leakage)
SchneiderNSX250N 4P 200A TM200D + Vigi NSX 250
ABBA2C250 TMF200/2000 4P integrated leakage
ABBTmax T2N250 TMD200/2000 4P + RC221
Siemens3VM1250-4ED32-0AA0
MitsubishiNV250-SV 4P 200A
DELIXICDM1LE-250/4300 200A
DELIXICDM3LS-250S/4300A 200A
TENGENTGM1LE-250/4300 200A
Changshu SwitchCM1L-250/4300 200A
NADERNDM1L-250/4300 200A
HUYUHUM1LE-250/4300 200A

  • Detalhes do produto

NM1LE-250S-4300-200A is a moulded case residual current circuit breaker (RCCB/MCCB with earth leakage protection) from CHINT (NM1LE Series).

  1. Full Model Explanation

NM1LE: Series code

N: CHNT company code

M: Moulded case circuit breaker

1: Design sequence

LE: With earth leakage / residual current protection

250: Frame rating current 250A (maximum frame current for this series)

S: Breaking capacity class (Standard type, ultimate breaking capacity Icu=30kA)

4300: Poloneses & functions

4: 4 postes (3P+N)

3: Thermal-magnetic trip with overload + proteção contra curto-circuito

00: No accessory trips (no undervoltage, no shunt trip)

200UM: Rated operational current In=200A (continuous permissible current)

  1. Key Technical Parameters (NM1LE-250S/4300 200A)
ItemValue
Rated operational voltage UeAC 400V/415V (3-phase 4-wire)
Rated insulation voltage Ui800V
Rated impulse withstand voltage Uimp8kV
Rated frequency50Hz
Ultimate breaking capacity Icu30o (Type S standard)
Service breaking capacity Ics15o
Trip characteristicThermal-magnetic (distribution type)
Rated residual operating current IΔn50mA / 100mA / 200mA (3 adjustable steps)
Residual operating timeStandard type ≤ 0.1s (time‑delay optional)
Number of poles4P (Pole N type A: no overcurrent trip, always closed)
MountingTipo fixo (front connection mainly)
Applicable standardsGB/T 14048.2, CEI 60947-2
  1. Principais Funções
  2. Proteção contra sobrecarga: Thermal trip delays and trips when current exceeds 200A.
  3. Proteção contra curto-circuito: Magnetic trip operates instantly within 30kA short-circuit current.
  4. Residual current (earth leakage) proteção: Detects current imbalance between phase and neutral; trips quickly at set values (50/100/200mA) to prevent electric shock and electrical fires.
  5. Infrequent switching: Can be used as a main switch for circuits and equipment.
  6. Aplicações Típicas

3-phase 4-wire distribution systems, industrial equipment, building power distribution, construction temporary power, main circuits in shopping malls and factories, and other occasions requiring earth leakage + sobrecarga + short-circuit triple protection.

Complete Technical Data Sheet

CHINT NM1LE-250S/4300 200A

All parameters are from CHINT official catalog and manual, applicable to NM1LE-250S/4300 200A (4-pole moulded case residual current circuit breaker).

  1. Basic Identification Parameters
ItemKey ValueNotas
Full product nameMoulded case residual current circuit breaker (disjuntor de fuga à terra)Distribution protection type
Brand/SeriesCHINT / NM1LE SeriesUpgraded first generation
Full modelNM1LE-250S/4300 200AStandard front connection, no accessory trips
Frame rating current250UMMax rated current supported by this frame
Rated operational current In200UMLong‑term permissible operating current
Poloneses4 postes (3P+N)Pole N has no overcurrent trip, always closed
Breaking capacity classType S (Padrão)Type H (high breaking) available for same frame
Tipo de viagemViagem termomagnéticaLong‑time delay overload + instantaneous short‑circuit protection
ComplianceGB/T 14048.2, CEI 60947-2CCC certified
  1. Main Circuit Electrical Parameters
ItemKey ValueNotas
Rated operational voltage UeAC 400V/415VFor 3-phase 4-wire systems
Rated insulation voltage Ui800VMaximum insulation withstand voltage
Rated impulse withstand voltage Uimp8kVSurge & lightning overvoltage capability
Rated frequency50HzFor domestic mains power systems
Rated ultimate short-circuit breaking capacity Icu (AC400V)30oMax safe breaking short-circuit current
Rated service short-circuit breaking capacity Ics (AC400V)15oCan continue normal operation after breaking
Arc distance≤100mmMax arc flash during short-circuit breaking
ConnectionFront connection (padrão)Rear connection & plug-in type optional
Main terminal torque12N·mFor M8×16 terminal screws
Recommended copper conductor≥70mm² (solid) / 120mm² (stranded)Copper busbar / cable recommended
  1. Protection Characteristics
ItemKey ValueNotas
Proteção contra sobrecarga (thermal trip)Non-tripping at 7.2In; trips within 1h at 1.3InReference temp +30°C, inverse time delay
Proteção contra curto-circuito (magnetic trip)Instantaneous setting 12In (2400UM)Distribution type, reliable at 120% setting
Protection functionsSobrecarga, short-circuit, residual current (earth leakage)Can be used for infrequent circuit switching
Inlet/outletTop inlet, bottom outlet (padrão)Reverse connection strictly prohibited
  1. Earth Leakage Protection Parameters
ItemKey ValueNotas
Rated residual operating current IΔn50mA / 100mA / 200mA, 3 adjustable stepsDIP switch on device
Rated residual non-operating current IΔn00.5×IΔnThreshold to avoid nuisance tripping
Residual operating time (padrão)≤0.1s (fast type)Trips within 100ms on earth fault
Earth leakage typeAC typeReliable for sinusoidal AC residual current
Test circuitBuilt-in test circuitWith test button; test at least monthly
Earth fault indicationRed mechanical indicatorPops out after earth leakage trip
  1. Environmental & Parâmetros Mecânicos
ItemKey ValueNotas
Operating ambient temperature-5℃ ~ +40℃Derate required beyond this range
Storage temperature-25℃ ~ +70 ℃Non-energized storage
Altitude≤2000mDerate for higher altitude
Pollution degree3Suitable for industrial distribution
Installation categoryIIIFor distribution circuits and main equipment circuits
Ingress protectionIP30 (except terminals)Solid foreign object protection, not waterproof
Mechanical endurance10,000 operaçõesNo-load operating cycles
Electrical endurance4,000 operaçõesAt rated load
Mounting orientationVertical or horizontal mounting allowedInverted mounting not permitted
  1. Dimensões (4-pólo, unit: milímetros)
DimensionValueNotas
Width W188Total width of 4-pole unit
Height L165Including terminals
Depth H102Body thickness
Horizontal mounting hole spacing140Center-to-center left-right
Vertical mounting hole spacing126Center-to-center up-down
Mounting hole diameter Ød4.5For M4 mounting screws
Minimum clearance≥25mm side, ≥5mm top/bottomFor side-by-side installation

Alternative Models from Other Brands

All below match the core specification:

4 postes (3P+N), 250Um quadro, 200A rated current, Icu ≥30kA at AC400V, thermal-magnetic overload + proteção contra curto-circuito, AC-type earth leakage (50/100/200mA adjustable), no accessory trips, front fixed connection.

  1. Domestic High-Compatible Alternatives

(Dimensões, preço, function highly matched; ideal for direct replacement)

  1. MarcaReplacement ModelKey Matching ParametersDescription
    DELIXICDM1LE-250/4300 200AIcu=30kA, 4P 200A, 50/100/200mA adjustable, thermal-magnetic1:1 design with NM1LE, high compatibility, no cabinet modification
    DELIXICDM3LS-250S/4300A 200AIcu=35kA, 4P 200A, adjustable leakage, thermal-magneticNew upgraded series, higher performance
    TENGENTGM1LE-250/4300 200AIcu=30kA, 4P 200A, 50/100/200mA adjustableDirectly compatible with NM1LE
    Changshu SwitchCM1L-250/4300 200AIcu=35kA, 4P 200A, adjustable leakageIndustrial rade high reliability
    NADERNDM1L-250/4300 200AIcu=35kA, 4P 200A, adjustable leakageStable for construction & industry
    HUYUHUM1LE-250/4300 200AIcu=30kA, 4P 200A, 3-step leakageCost-effective direct replacement

    Joint-venture / International Brands

(Higher performance for premium projects & severe conditions)

MarcaReplacement ModelKey Matching ParametersDescription
SchneiderEZD250E4200ELN (integrated leakage)Icu=36kA, 4P 200A, 30/100/300mA adjustableEconomic universal type
SchneiderNSX250N 4P 200A TM200D + Vigi NSX 250UTI=50kA, 4P 200A, multi‑range leakageHigh‑end industrial grade
ABBA2C250 TMF200/2000 4P integrated leakageIcu=36kA, 4P 200A, adjustable leakageEconomic building distribution
ABBTmax T2N250 TMD200/2000 4P + RC221Icu=36kA, 4P 200A, multi‑range leakageHeavy industrial & foreign projects
Siemens3VM1250-4ED32-0AA0Icu=36kA, 4P 200A, 30/100/300mA adjustableStandard international type
MitsubishiNV250-SV 4P 200AIcu=36kA, 4P 200A, 100/200/500mA adjustableHigh reliability for precision equipment
  1. Key Replacement Notes
  2. Mounting dimension check: Domestic models (CDM1LE, TGM1LE, etc.) are highly compatible with NM1LE for direct replacement. International brands often differ in size and hole spacing.
  3. Minimum breaking capacity: Icu at AC400V must be ≥30kA to ensure safety.
  4. Leakage matching: Prefer 50/100/200mA adjustable; use fast‑acting type ≤0.1s, not time‑delay.
  5. Poloneses & N-pole characteristic: Must be 4P (3P+N), with N-pole without overcurrent trip, always closed.
  6. Compliance: All replacements must be CCC certified and comply with GB/T 14048.2 / CEI 60947-2.