Danfoss SM147A4ALB Scroll Compressor

(Performer hermetic scroll compressor) Pedido nº.: 120H0191, a fixed-speed scroll unit from the Danfoss SM series, designed for R22 central air conditioning applications. ✅ Model Decoding SM: Performer scroll series, air-conditioning duty 147: Displacement size 193.5 cm³/rev A: Motor version 4: 3-phase 380~415V 50Hz / 460V 60Hz ALB: Oil sight glass, internal motor protection, ODF ...

  • Detalhes do produto

(Performer hermetic scroll compressor)

Pedido nº.: 120H0191, a fixed-speed scroll unit from the Danfoss SM series, designed for R22 central air conditioning applications.

✅ Model Decoding

SM: Performer scroll series, air-conditioning duty

147: Displacement size 193.5 cm³/rev

UM: Motor version

4: 3-phase 380~415V 50Hz / 460V 60Hz

ALB: Oil sight glass, internal motor protection, ODF brazed connections, no economizer

📌 Core Technical Specifications

ItemParâmetro
RefrigeranteR22 (compatible only with R22 mineral oil 160P)
Fonte de energia3Ph 380–415V 50Hz / 460V 60Hz
Cooling Capacity32.6kW@50Hz;43.6kW@60Hz
Deslocamento193.5 cm³/r
Rotation Speed2900rpm(50Hz) / 3500rpm(60Hz)
RLA Rated Load Current20.7UM
LRA Locked Rotor Current147UM
MOC Maximum Operating Current26UM
Peso líquido67 kg, Peso bruto 71.75 kg
Pipe ConnectionsODF brazed, discharge 7/8″
ContornoOuter diameter φ243mm, height 509mm
CertificaçõesCE / UL / UKCA
Controle de capacidadeFixed speed, no variable frequency
Economizer❌ No subcooler/economizer port
Max Refrigerant Charge7.9kg

🧊 Typical Applications

Commercial air-cooled / water-cooled central air conditioning units

Modular chillers, screw compressor retrofit, refrigeradores de água industriais

Commercial constant temperature & humidity air conditioners (R22 system only; cannot directly replace R407C/R410A models)

⚠️ Maintenance & Notas de seleção

  1. Refrigeration Oil: 160P mineral oil. POE synthetic oil must not be mixed. Compressor replacement requires simultaneous oil & oil filter change.
  2. Built-in motor thermal protection. External phase sequence protector and high/low pressure protection are recommended.
  3. Single unit operation; multi-compressor parallel installation requires oil equalization solution (oil balance port size 1-3/4″ Rotolock).
  4. Maximum allowable operating pressure: High side 29.4bar, low side 25bar.
  5. Second-hand inspection focus: Resistência de isolamento, inter-turn test, oil colour, internal abnormal noise, high/low pressure leak test.

🔁 Equivalent / Referências Alternativas

SM147A3ALB: Different voltage version (código 3)

SM147A4CLB: Difference in connection and accessory configuration

SZ147A4ALB: Same displacement, for R407C (não diretamente intercambiável; refrigerant and lubricant differ)

SM147A4ALB Starting & Protection Circuit Selection List (3Ph 380~415V/50Hz, R22 Performer Scroll)

Compressor base electrical data: RLA=20.7A; MOC maximum continuous operating current=26A; LRA locked rotor current=147A; The compressor has built-in motor thermal protection. Complete external electrical and refrigerant pressure protection is still mandatory.

  1. Main Circuit Component Selection
ComponenteEspecificaçãoObservações
3-phase Main ContactorAC-3 400V ≥32A, coil AC220V/AC380V optionalSchneider LC1D32, LC1E32; AC-3 rated to withstand LRA inrush. AC-1 contactors are prohibited.
MCCB Molded Case Circuit BreakerType D 3P, rated 40A, instantaneous trip 10InType D for motor starting inrush, proteção contra curto-circuito. Type C not permitted.
Relé de sobrecarga térmicaFaixa de ajuste:18~24A, 3P, reinicialização manualSetpoint approx. 21UM; acts as secondary backup overload protection and cannot replace the compressor internal thermal protector.
Cabo de alimentação principalCopper ≥4mm² power cableUnidade única, length ≤30m; upgrade to 6mm² for long runs, use crimp lugs
Crankcase Heater220V, 80C, AC220VOil sump heating; mínimo 8 hours preheating before startup. Heater circuit independent and cut off before compressor starts.
  1. Refrigerant Pressure Protection (safety chain wired in series with contactor coil circuit)
DispositivoModelo recomendadoContextoModo de reinicialização
High Pressure SwitchDanfoss KP5 (alta pressão)Viagem:27bar; Reiniciar:21barReinicialização manual (mandatory), R22 service
Low Pressure SwitchDanfoss KP1 (baixa pressão)Viagem:1.8bar; Reiniciar:3.2barRedefinição automática, guards against low suction liquid floodback / low refrigerant charge
Oil Differential Pressure Protection (opcional)Danfoss MP54Trip if oil differential pressure <2.5bar with 120s delayStrongly recommended for large chillers

III. Sequência de fases & Proteção contra perda de fase (mandatory)

Sequência de fase / phase loss relay: 3-fase 380V, detects wrong phase, perda de fase & 3-desequilíbrio de fase

Recomendação: Schneider RM22TG20 or domestic 3-phase protection relay

Lógica: Cut contactor coil upon abnormal phase condition. Scroll compressor reverse rotation can destroy scroll wraps within seconds.

  1. Circuito de Controle (AC220V control)
  2. Fornecimento de controle: AC220V with C10 miniature circuit breaker (10UM)
  3. Series safety chain for coil circuit: Phase sequence protection NC → High pressure switch NC → Low pressure switch NC → Oil differential (optional NC) → Start/Stop Button → Contactor Coil
  4. Contatos auxiliares: Contactor NO auxiliary contact for latching; fault alarm wired from NO contacts of each protection device.
  5. Hard Rules for Scroll Compressor Startup Control
  6. Minimum off-delay: Espere pelo menos 3 minutes after shutdown before restart; controller 180s minimum stop delay is recommended.
  7. Maximum starts per hour: ≤6 times. Frequent starts accelerate bearing and scroll wrap wear.
  8. Forbidden operations: Start with pressure differential, test rotation in reverse, start without crankcase preheating.
  9. After internal protector trips: Power must be cut for cooling and reset. Do not repeatedly force power on for trial runs.
  10. Optional Sensors & Acessórios

Discharge temperature sensor (opcional): PT100, discharge overtemperature protection for high-temperature R22 operation

Transformador de corrente (opcional): 25/5UM, for real-time current monitoring by unit controller

Terminais: Crimp lugs recommended for compressor terminals, tightening torque 3.5~4N·m per Danfoss manual

VII. Simplified Typical Control Sequence

Power on → Phase sequence self-check OK → Crankcase heater energized → Preheating timer satisfied → Start enable signal → Contactor pulls in, compressor runs.

Trip on high pressure (reinicialização manual), baixa pressão, perda de fase / wrong phase: contactor de-energized immediately, unit stops and triggers fault alarm.

VIII. Selection Pitfall Checklist

  1. Thermal relay is only backup protection. The compressor built-in thermal protector will activate first. Do not use thermal relay as sole motor protection.
  2. High pressure protection must use manual reset. Auto-reset high pressure switches violate safety requirements.
  3. Phase sequence protection must never be omitted; reverse rotation can ruin scroll plates in tens of seconds.
  4. Crankcase heater cannot be omitted. For R22 mineral oil, refrigerant dissolves in oil at low standby temperature; startup without preheating risks bearing seizure from oil starvation.

Danfoss Performer SM Series (R22 fixed-speed scroll, single unit) Lista completa de modelos

SM series: R22 refrigerant, mineral oil 160P, air-conditioning scroll compressors; SZ series of same footprint for R407C; SY series covers larger displacement range.

Regra de nomenclatura: SM+displacement code+motor code+voltage code+suffix (connections/accessories); Código 4 = 380~415V 50Hz /460V 60Hz (main domestic engineering variant; SM147A4ALB uses code 4)

  1. Base Displacement Core Models (bare unit without ALB/CLB suffix)
Modelo BásicoDisplacement cm³/revCooling Capacity kW@50HzObservações
SM084112.0816.1Small modular units, fan coil units
SM090120.517.3Air-cooled modular, large residential central AC
SM100127.218.5Commercial air conditioning
SM110144.220.8Water chillers
SM112151.522.1Short body version
SM115156.823
SM120166.624.6Mainstream modular chiller model
SM124169.525.4Short body
SM147193.532.6Bare model of your SM147A4ALB
SM148194.533SM147 upgraded variant
SM160210.135.4Medium water chillers
SM161216.636.6
SM17022938.8
SM17523340.2
SM18024141.8
SM185249.943.7Largest single unit in SM range
SM200254.446.1Older large SM, mostly superseded by SY series for new projects
SM220288.452.7Older large SM
SM242333.261.3Older large SM
SM24834264Older large SM
SM444597117Built-in tandem parallel compressor
SM483649.8127Built-in tandem parallel compressor
  1. SM147 Full Suffix Variants (subfamily of your compressor)

SM147 bare unit, voltage codes: 3 /4 /9

SM147A3ALB: Código de tensão 3 variante

SM147A4ALB: Seu modelo, 380~415V 50Hz, ODF brazed ports, oil sight glass, no economizer, Order No.120H0191

SM147A4CLB: Different connection style, Rotolock port

SM147A9ALB: 60Hz North American voltage version

Explicação do sufixo:

ALB = ODF brazed pipe connections, oil sight glass, internal thermal protection, no economizer

CLB = Rotolock flange connections, oil sight glass, internal thermal protection

III. Voltage Code Definition (middle digit of model)

3: 200–230V 3-phase 60Hz

4: 380–415V 50Hz /460V 60Hz (main domestic engineering model)

9: 380V 3-phase 60Hz (North American unit)

  1. Platform Differentiation (avoid selection error)
  2. SM: R22, mineral oil 160P (this list)
  3. SZ: Same outer dimensions, R407C, POE synthetic oil, cannot directly replace SM
  4. SY: Larger displacement range, R22, high-capacity water chillers (SY240, SY300, SY380, SY550 etc., not part of SM series)
  5. End-of-Life Notice

SM200/SM220/SM242/SM248 are legacy large SM models, mostly discontinued. New projects are recommended to adopt SY series. SM084~SM185 remain mainstream stocked models.

Danfoss Performer SM Series (R22) Current Parameter Table

Observação: Power supply 3Ph 380~415V 50Hz; RLA=Rated Load Current; MOC=Maximum Continuous Operating Current; LRA=Locked Rotor Current; all single units, tandem compressors listed separately.

ModeloDisplacement cm³/revCooling Capacity kW@50HzRLA(UM)MOC(UM)LRA(UM)
SM084112.0816.111.214.184
SM090120.517.312.115.290
SM100127.218.512.81694
SM110144.220.814.418106
SM112151.522.114.818.5108
SM115156.82315.419.3112
SM120166.624.616.220.3118
SM124169.525.416.620.8122
SM147193.532.620.726147
SM148194.5332126.3149
SM160210.135.422.528.1160
SM161216.636.623.229163
SM17022938.824.330.4171
SM17523340.225.131.4176
SM18024141.82632.5182
SM185249.943.72733.8188
SM200254.446.128.435.5196
SM220288.452.732.240.3222
SM242333.261.336.846254
SM2483426438.247.7262

Tandem Integrated Compressors (dual scroll block)

ModeloDisplacement Cm³/revCooling Capacity kW@50HzRLA(UM)MOC(UM)LRA(UM)
SM44459711764.580.6440
SM483649.812770.287.8478

Notas Suplementares

  1. This table applies to suffix code 4 versões (A4ALB/A4CLB). Code3/9 variants (220V trifásico, 60Hz North America) have different current values and must not use this table.
  2. Thermal overload relay setting recommendation: RLA × 1.02 ~ 1.05, used as backup protection and shall not exceed MOC.
  3. LRA locked rotor current is used for contactor and circuit breaker short-time inrush sizing only, not continuous current rating.
  4. SM series only works with R22 + 160P mineral refrigeration oil; SZ series (R407C) of identical external shape has different current parameters and shall not be mixed.