HLPA03D723B Danfoss Holip Inverter

HLPA03D723B is a general-purpose inverter from Danfoss Holip HLP‑A series, 3.7 kW, 220 V three-phase/single-phase. It is suitable for constant-torque loads, with an overload capacity of 150% para 1 minuto, built-in PID and simple PLC, ideal for industrial applications such as plastic extrusion and conveyors. Model Explanation Code Meaning HLP Holip brand prefix A HLP‑A ...

  • Detalhes do produto

HLPA03D723B is a general-purpose inverter from Danfoss Holip HLP‑A series, 3.7 kW, 220 V three-phase/single-phase. It is suitable for constant-torque loads, with an overload capacity of 150% para 1 minuto, built-in PID and simple PLC, ideal for industrial applications such as plastic extrusion and conveyors.

  1. Model Explanation
CodeSignificado
HLPHolip brand prefix
UMHLP‑A general series (optimized for constant torque)
03D7Power code, corresponding to 3.7 kW
23Voltage code: 2=220 V, 3=three-phase (compatible with single-phase)
BHardware version/configuration (standard version)
  1. Principais parâmetros elétricos
ItemSpecification
Rated Power3.7 kW
Tensão de entrada220 V single/three-phase, 50 Hz (±15% wide voltage range)
Corrente de entrada nominalApprox. 17 UM
Rated Output Current17 UM (continuous)
Capacidade de sobrecarga150% para 1 min, 180% para 0.2 é
Output Frequency Range0.1~400 Hz (resolution 0.01 Hz)
Control ModeV/F control, built-in PID, simple PLC
Torque inicialUp to 150% rated torque at 1 Hz
CoolingForced air cooling
Protection DegreeIP20 (keypad)
Applicable Motor3.7 kW 220 V three-phase asynchronous motor
Standard KeypadOP‑AB01 (remotely mountable)
  1. Dimensões & Electrical Specifications

3.1 Physical Dimensions (Unidade: milímetros)

ItemValue
Largura (C)125
Altura (H)210
Profundidade (D)185
Mounting Holes4×φ5 (spacing: 100×190)
PesoApprox. 2.8 kg

Mounting Requirements: Mount vertically. Leave ≥100 mm clearance above and below, ≥50 mm left and right for ventilation. Avoid dust, oil, and humidity.

3.2 Electrical Installation

ComponenteRatingCable Size
Input Circuit Breaker (NFB)30 UM4 mm² (copper)
Input Contactor25 UM4 mm²
Output Cable4 mm² (shielded recommended)
Circuito de Controle1.5 mm² (shielded for signals)
Grounding≥4 mm², grounding resistance ≤10 Ω
  1. Wiring & Terminal Definitions

4.1 Main Circuit Terminals

TerminalFunção
R/L1, S/L2, T/L3220 V power input (monofásico: connect R/L1, S/L2)
Você, V, CInverter output (to motor)
Educação FísicaTerra protetora (must be securely connected)

4.2 Control Circuit Terminals (Padrão)

TerminalDescription
DI1~DI55 entradas digitais (programmable: FWD, REV, multi-speed)
DO1~DO22 saídas digitais (relay / open-collector optional)
AI1Analog input (0~10 V/4~20 mA, programmable)
AO1Analog output (0~10 V, for frequency/current)
+10V10 V DC supply (máx. 50 mA)
GNDAnalog / digital common
RS485Communication port (Modbus RTU)

Wiring Notes: Separate main power and control wiring. Use shielded cable for analog signals, grounded at one end. Avoid parallel routing with power cables.

  1. Características & Applications

Principais Funções

Built-in PID controller: Suitable for closed-loop control (pressure, flow, temperature)

Simple PLC: 16-step speed, program run, traverse function

Comprehensive protection: Overcurrent, sobretensão, subtensão, overheat, perda de fase, motor overload

Comunicação: RS485 standard, Modbus RTU, for centralized control

Aplicações Típicas

Plastic extruders: Optimized for constant torque, stable low-speed high-torque operation

Conveyors: Smooth start, multi-speed, load-adaptive

Mixers: High starting torque, strong overload capability

Packaging machinery: Precise speed control, positioning

  1. Replacement & Selection Guide

6.1 Same-Brand Upgrades

OriginalReplacementAdvantage
HLPA03D723BDanfoss FC‑051P3K7T2E20H3BFully compatible, upgraded functions, Danfoss support
HLPA03D723BHolip HLP‑A100 3.7 kW 220 VSame platform, parameter compatible

6.2 Cross-Brand Equivalents

MarcaModeloKey Match
InovaçãoMD200S3.7B220 V 3.7 kW, 17 UM, V/F control
InvtCHF100A‑3R7G‑2220 V 3.7 kW, 17 UM, built-in PID
DeltaVFD037E23A220 V 3.7 kW, 17 UM, torque boost

Critical Replacement Notes

  1. Voltage match: Must be 220 V input
  2. Current match: Rated current ≥17 A
  3. Mounting match: Dimensions and cooling compatible
  4. I/O match: Analog/digital interfaces compatible
  5. Parameter transfer: Save old parameters, reconfigure per new manual
  6. Fault Troubleshooting
Fault CodeSignificadoSoluções
OCOvercurrent1. Check motor load & isolamento
2. Increase acceleration time
3. Verify motor-inverter match
OVSobretensão1. Increase deceleration time
2. Add braking unit/resistor
3. Check mains voltage
UVSubtensão1. Check input voltage (≥187 V)
2. Tighten power terminals
3. Stabilize power supply
OHOverheat1. Improve ventilation (≤40°C)
2. Clean heatsink
3. Check fan operation
GFGround Fault1. Check motor/cable insulation
2. Garanta um aterramento confiável
3. Eliminate leakage
OLMotor Overload1. Reduce load
2. Check motor rated current setting
3. Increase torque boost
  1. Instalação & Maintenance

8.1 Installation Standards

Vertical mounting, away from direct sunlight and heat sources

Temperatura ambiente: -10°C~40°C (derate above 40°C)

Umidade: 5%~95% (sem condensação)

Altitude: ≤1000 m (derate above 1000 m)

8.2 Maintenance Schedule

Daily: Check temperature, fan noise, unusual odors

Quarterly: Clean heatsink, tighten terminals

Yearly: Check capacitors, replace worn fan

8.3 Braking Unit

For quick stop / high inertia: external braking unit HBR‑03D7 (para 3.7 kW)

Braking resistor: 50 Oh / 100 C (adjust per application)

  1. Technical Specifications

Modelo: HLPA03D723B (HOLIP HLP‑A Series)

Rated Power: 3.7 kW

Tensão de entrada: 220 V Single/Three Phase, 50 Hz (±15%)

Rated Output Current: 17 UM

Capacidade de sobrecarga: 150%/1 min, 180%/0.2 é

Control Method: V/F control, built-in PID, simple PLC

Torque inicial: 150% rated torque at 1 Hz

Dimensões (W×H×D): 125×210×185 mm

Peso: Approx. 2.8 kg

Practical Troubleshooting for HLPA03D723B (3.7kW/220V)

  1. Fault Codes (Most Common)

1.1 OC / Overcurrent

Causes: Motor jam, shorted cable, fast acceleration, poor motor insulation

Soluções:

  1. Check for seized motor or overload
  2. Increase acceleration time
  3. Inspect U/V/W cables for damage or short
  4. Run inverter without motor to isolate fault

1.2 OV / Sobretensão

Causes: Fast deceleration, high mains voltage, high-inertia load

Soluções:

  1. Increase deceleration time
  2. Add external braking resistor (≈50Ω/100W)
  3. Check if input exceeds 250 V

1.3 UV / Subtensão

Causes: Baixo 220 V, loose wiring, perda de fase

Soluções:

  1. Measure R/S/T voltage (no lower than 180 V)
  2. Tighten power terminals
  3. Single-phase: connect R & S only

1.4 OH / Overheat

Causes: Blocked vents, faulty fan, high ambient temp

Soluções:

  1. Clean heatsink and fan
  2. Verify fan operation
  3. Maintain ≥10 cm clearance top/bottom

1.5 OL / Motor Overload

Causes: Heavy load, wrong motor parameters, low torque

Soluções:

  1. Reduce load
  2. Check motor rated current setting
  3. Increase torque boost

1.6 GF / Ground Fault

Causes: Motor leakage, grounded cable, poor insulation

Soluções:

  1. Test motor insulation
  2. Check output cable for grounding
  3. Secure PE connection

1.7 CE / Communication Error

Causes: RS485 interference, wrong wiring

Soluções:

  1. Check A/B wiring polarity
  2. Use shielded cable, grounded at one end
  3. Route away from power cables
  4. Abnormal Operation (No Fault Code)

2.1 Keypad displays but motor does not run

Soluções:

  1. Check if in terminal control, no start signal
  2. Verify DI1 (FWD) is closed
  3. Check frequency reference (0 V/0 mA)

2.2 Motor vibration / noise

Soluções:

  1. Lower carrier frequency
  2. Tighten motor cables
  3. Increase torque boost at low speed

2.3 Frequency cannot rise / limited

Soluções:

  1. Check maximum frequency parameter
  2. Verify analog signal (0‑10 V/4‑20 mA)
  3. Check for false multi-speed input
  4. Important Notes for HLPA03D723B

220 V ONLY: DO NOT connect to 380 V (will damage IGBT module)

Top 3 falhas: OC, OV, UV

Single-phase input must be tightly secured; loose terminals often cause UV faults