OMRON MM2KP Mechanical Latching Relay - Contator,disjuntor,sensor,Codificador,CLP,Conversor

Conversamos: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Sobre Contato |

 OMRON MM2KP Mechanical Latching Relay - Contator,disjuntor,sensor,Codificador,CLP,Conversor

elétrica/

OMRON MM2KP Mechanical Latching Relay

MM2KP = MMK Series, 2-pólo (DPDT), cased, plug-in mechanical latching (bistable dual-coil) relay Model Definition: Milímetros: MM series power-type latching relay 2: 2 contact sets, DPDT (2C) K: Mechanical latching (dual coil, DEFINIR / REINICIAR, pulse-operated, retains contact state after power loss) P: Plastic enclosed housing, plug-in socket mounting type ✅ Key Specifications Contacts: DPDT ...

  • Detalhes do produto

MM2KP = MMK Series, 2-pólo (DPDT), cased, plug-in mechanical latching (bistable dual-coil) relé

Definição de modelo:

Milímetros: MM series power-type latching relay

2: 2 contact sets, DPDT (2C)

K: Mechanical latching (dual coil, DEFINIR / REINICIAR, pulse-operated, retains contact state after power loss)

P: Plastic enclosed housing, plug-in socket mounting type

✅ Key Specifications

  1. Contatos: DPDT 2C, silver Ag contacts

Rated load: AC220V 5A; DC24V 4A

Max switching voltage: AC250V / CC250V; Max switching current 5A

Capacidade máxima de comutação: 1100VA / 96C

  1. Bobinas (Two independent coils: DEFINIR + REINICIAR)

Available coil voltages:

AC: 6/12/24/100(110)/200(220)VAC

CC: 12/24/48/100(110)/125/200(220)CCV

Exemplo: MM2KP DC24: SET coil 275Ω / 87mA; RESET coil 220Ω / 109mA

Drive requirement: Pulse ≥100ms, continuous power not required. Contact state remains after coil power removal.

  1. Tempo

Operate time ≤60ms; Reset time ≤30ms

Max operating frequency: 1800 operações/hora

  1. Vida útil

Vida mecânica: ≥2,500,000 operations

Vida elétrica: ≥500,000 operations (na carga nominal)

  1. Condições ambientais: -10~+55℃, sem condensação; Humidity 5~85%RH
  2. Montagem: 11-pin socket (PL11 / 11PFA), socket installation; Peso aprox.. 375g
  3. Resistência Dielétrica: Coil to contact AC2000V, between contacts of different poles AC2000V

✅ Operating Principle (Destaques)

Dual-coil mechanical latching (bistable relay)

Apply pulse to SET coil → contacts switch and mechanically latch. Contact state is maintained after coil power off.

Apply pulse to RESET coil → contacts reset and latch.

Vantagens: Zero steady-state power consumption. Ideal for power, energy storage and signal circuits requiring state retention after power loss.

Distinção: MM2K = bare relay without housing; MM2KP = cased P type; MM2XKP = enhanced version for DC loads.

✅ Typical Application Scenarios

Monitoramento de energia, relay protection circuits, signal memory circuits

Construção de proteção contra incêndio, emergency power supply, energy storage control

Remote maintained switches, state latching for primary/secondary circuits

Suitable for applications requiring switch state retention and prohibiting continuous coil energization.

✅ Selection & Informações de substituição

  1. Extended series:

MM3KP: 3-pole 3C; MM4KP: 4-pole 4C; MM2XKP: DC-load enhanced model

  1. Domestic replacement guideline: Dual-coil bistable relay, DPDT 5A, 11-pin socket type. Pay attention to SET/RESET coil resistance values. Single-coil bistable relays cannot be directly substituted.
  2. Common failure points:

Pulse width <100ms → unreliable SET / REINICIAR

Swapped SET and RESET coils will not burn the relay, but state switching fails

Erosão de contato: No absorption circuit (varistor / diodo de roda livre) para cargas indutivas

✅ Matching Socket

PL11 / 11PFA (11-pin socket)

OMRON MM2KP Overall Dimensions (Ficha técnica oficial, Unidade: milímetros)

Corpo do relé (without socket): W54.5 × D80.5 × H119 (máx.)

C: 54.5 máx. (largura)

D: 80.5 máx. (profundidade)

H: 119 máx. (total height including transparent cover)

Overall Height when assembled with PL11 socket

MM2KP mounted on PL11 socket: Total height approx.151mm

Furos de montagem (direct base mounting, no socket)

2 × Φ4.5 mounting holes, distância central: 22 ±0.2 mm

Peso

MM2KP: aprox.. 375 g

Series dimension comparison (for cabinet layout)

MM2KP: 54.5(C) ×80.5(D) ×119(H)

MM3KP: 64.5(C) ×80.5(D) ×119(H)

MM4KP: 70.5(C) ×80.5(D) ×119(H)

Notas:

  1. MM2XKP (DC load enhanced version) shares identical outer dimensions with MM2KP, with curved protective plate on side. Cabinet side clearance ≥55mm is recommended.
  2. Dimension tolerance: ±0.4mm for non-specified dimensions.

OMRON MM2KP Mechanical Latching Relay Operating Principle

MM2KP is a dual-coil mechanically latched bistable relay. The key difference from conventional relays: Coils are energized only during state transition. No continuous power required in steady state. Contact state is locked by internal mechanical latch and magnetic structure, retained after power loss.

Estrutura Interna

Two independent coils: SET coil and RESET coil, electrically separated. Armature coupled with mechanical latch assembly + DPDT (2C) contact sets.

SET coil: Drives mechanism to switch contacts to NO closed position and latch.

RESET coil: Reverse drive to release latch, contacts return to NC position.

Full Operating Sequence

  1. Initial reset state

Mechanical latch stays at reset position: NC fechado, NÃO aberto. Both coils de-energized. State maintained purely by mechanical latch with zero coil power consumption.

  1. SET operation (SET pulse)

Apply pulse ≥100ms to SET coil (DC/AC available). Electromagnetic force pulls armature and flips mechanical latch to locked position.

Contacts switch: NÃO fechado, NC aberto.

After pulse termination and SET coil de-energized, mechanical latch holds position without rebound.

DC version operate time ≤60ms; AC version ≤30ms.

  1. RESET operation (RESET pulse)

Apply pulse ≥100ms to RESET coil. Electromagnetic force pushes armature in reverse direction to release mechanical latch.

Contacts return to initial state: NÃO aberto, NC fechado.

After RESET coil de-energized, mechanical latch retains reset state again.

✅ Critical rule: SET and RESET coils must not be energized simultaneously. Concurrent energization will result in SET state, which is an invalid drive condition and prohibited in circuit design.

Comparison with conventional relays & permanent magnet bistable relays

  1. Standard electromagnetic relay: Contact closed only when coil continuously energized; contacts release immediately after power loss, state lost.
  2. MM2KP: Mechanical latch is the primary holding mechanism; magnetic force only toggles the latch. Zero steady-state power, state retention after power loss. Mixed coil voltages are available (por exemplo. SET AC220V, RESET DC24V).
  3. Permanent magnet bistable relay: State held by permanent magnet, no mechanical latch.

Core Electrical Key Points (Engineering Focus)

Minimum pulse width: 100EM. Shorter pulse causes unreliable occasional failure of SET/RESET.

Coils are pulse-only driven. Prolonged continuous energization will overheat and burn coils.

Bistable characteristic: State changes only upon receiving opposite pulse. Contact status remains unchanged during power drop and power reboot.

Terminal Logic Summary (PL11 11-pin socket)

SET coil: one pair of terminals

RESET coil: separate pair of terminals

Contatos: 2 sets DPDT (Comum C, Normalmente aberto NÃO, NC normalmente fechado)

OMRON MM2KP Mechanical Latching Relay Application Scenarios

Core selection criteria: Pulse drive, retenção de estado de desligamento, zero steady-state power consumption, DPDT transfer contacts, transparent cased housing + 11-pin socket mounting. Mainly used for memory and state latching circuits, widely adopted in power secondary systems.

  1. Sistema de energia (Aplicação Primária)
  2. Secondary signal memory circuit for HV/LV switchgear

Latching protection alarm: When fault triggers protection, protection device sends SET pulse. MM2KP latches alarm signal. Alarm remains active even if protection device loses power or fault disappears. RESET signal (manual or circuit) is required for reset, convenient for maintenance to trace transient faults.

  1. Circuit breaker position memory & remote signalling retention circuit

Record circuit breaker open/close status. Switch position is preserved during temporary loss of DC control supply. Remote signalling state will not be lost after power restart.

  1. Auxiliary latching circuit for relay protection

Model compliant with JEC-174D power auxiliary relay standard. Used for trip retention, interlock latching and fault signal circuits, replacing traditional mechanical signal relays.

  1. DC panel, UPS & energy storage cabinet state latching

Latch overvoltage, undervoltage and battery fault signals; fault record retained after power outage.

  1. Fire Protection & Emergency Power Systems
  2. Fire linkage signal memory: Triggered by fire alarm pulse, linkage output latched. Linkage state preserved after fire host power cycle, reinicialização manual necessária.
  3. EPS emergency power supply, Gabinete ATS: Fault state latching to record switching events.
  4. Automação Industrial & Controle de Equipamentos
  5. Equipment fault memory, shutdown latching circuit

Máquinas-ferramentas, linhas de produção, bombear & valve units: Sobrecarga / emergency stop triggers SET pulse to latch shutdown. Equipment will NOT automatically resume operation after power restart until manual reset, melhorando a segurança.

  1. State feedback circuit for remotely pulsed actuators (válvulas, dampers).
  2. Test benches and trial equipment: One-shot event memory to record trigger events.
  3. Trânsito Ferroviário & Distribuição de energia predial
  4. Audível & visual alarm latching circuit for ring main units and power distribution rooms.
  5. Power cabinets in metro / tunnel applications, event state retention during temporary power interruption.

✅ Selection Limitations (Notas de Engenharia, Aplicativos inadequados)

  1. Not for high-speed cycling: Max rated 1800 operações/hora, not applicable for high-frequency switching.
  2. Somente controle de pulso: Continuous energization of SET/RESET coils is forbidden, coil burnout will occur.
  3. Avaliação de contato: AC220V 5A, DC24V 4A. Not for high-current main circuits; only suitable for secondary signal circuits.
  4. Ambiente: -10~+55℃, condensation not permitted.

✅ Replacement Guidelines

Frequent DC load switching (CC110V): Select MM2XKP (enhanced contact model for DC)

More contact sets required: MM3KP (3 transfer contacts), MM4KP (4 transfer contacts)

Anterior:

Deixe uma resposta

Deixe um recado