Pepperl+Fuchs WE77/Ex-2 Installation & Wiring Guide WE77/Ex-2: Dual-channel NAMUR isolated switch amplifier (intrinsically safe barrier). Must be installed in safe-area control cabinet only. Blue terminals = intrinsically safe side (connect to field explosion-proof sensors). White/red terminals = non-intrinsically safe side (connect to PLC and power supply). Nome do produto: Isolated Intrinsically Safe Switch Amplifier Note: WE77/Ex-2 ...

  • Detalhes do produto

Pepperl+Fuchs WE77/Ex-2 Installation & Guia de fiação

WE77/Ex-2: Dual-channel NAMUR isolated switch amplifier (intrinsically safe barrier). Must be installed in safe-area control cabinet only. Blue terminals = intrinsically safe side (connect to field explosion-proof sensors). White/red terminals = non-intrinsically safe side (connect to CLP and power supply).

Nome do produto: Isolated Intrinsically Safe Switch Amplifier

Observação: WE77/Ex-2 is an obsolete legacy model. Recommended replacement for new projects: KFA6-SR2-Ex2

  1. Definição de código de modelo

WE77: Família de produtos, NAMUR switch amplifier

Ex: Intrinsically safe explosion-proof design

2: Dual-channel version (WE77/Ex-1 = single-channel)

Two power supply variants:

  1. WE77/Ex-2 115V: 115V AC supply
  2. WE77/Ex-2 230V: 230V (220V) Alimentação CA, most common in China
  3. Funções principais

Intrinsically safe isolated barrier for NAMUR sensors and dry contact mechanical switches located in hazardous areas. It isolates and transmits binary switch signals from hazardous area to control system in safe area. Equipped with LB Lead Breakage detection, supports reverse operation mode. Each channel has independent relay change-over contact output.

Field side: Intrinsically safe circuit EEx ia IIC, suitable for Zone0/1/2 hazardous locations

Control side: Passive relay dry contact output (non-intrinsically safe)

Supported inputs: NAMUR proximity sensors (EN60947-5-6), passive mechanical contacts

  1. Principais especificações elétricas

Intrinsically Safe Parameters (Lado do campo)

U₀: 13.5 Em DC

I₀: 62 mA

P₀: 125 mW

Explosion group: IIB / CII

Permitted external values: IIB: Co=0.929µF, Lo=5mH; CII: Co=0.23µF, Lo=3mH

NAMUR Input

Open circuit voltage ≈8V DC, short-circuit current ≈8mA

Switching threshold: 1.2~2.1mA, hysteresis approx.0.2mA

Lead breakage detection: Fault alarm upon cable disconnection

Saída de relé (1 SPDT change-over contact per channel)

Avaliação de contato: 250V AC /4A; 24VDC/4A

Tempo de resposta: Pull-in ≈10ms, Drop-out ≈20ms

Frequência máxima de comutação: <10Hz

Vida mecânica: 10⁷ switching cycles

Fonte de energia

230Versão V: 198~253V AC, 45~65Hz; Power dissipation approx.2.5W

115Versão V: 103.5~126V AC, 45~65Hz

  1. Mecânico & Dados Ambientais

Dimensão: 40(C) ×104(H) ×110(D) milímetros

Peso: approx.410g

Montagem: DIN rail clip mounting

Enclosure protection: IP20 (apenas para instalação em gabinete)

Temperatura ambiente: -25℃ ~ +60 ℃

Terminais: Terminais de parafuso

  1. Informações de certificação

Certificado ATEX: PTB 02 ATEX 2065 / PTB Ex-79/2043X

Explosion marking: II (1) GD [EEx ia] CII

  1. Atribuição de terminais (WE77/Ex-2)

Channel1 field input: terminal 1(-), 2(+)

Channel2 field input: terminal 8(+), 9(-)

Channel1 relay output: 10/11/12 (change-over contact)

Channel2 relay output: 13/14/15 (change-over contact)

Fonte de energia: 17, 18

  1. Aplicativo

Químico, farmacêutico, óleo & gas hazardous locations: Signal isolation for NAMUR proximity sensors, explosion-proof limit switches, explosion-proof level switches. Relay signals are sent to PLC/DCS DI modules.

  1. Peças de reposição & Notas de substituição
  2. WE77/Ex-2 no longer recommended for new projects by manufacturer. Substituição direta: KFA6-SR2-Ex2 (dual-channel NAMUR safety barrier, saída de relé, equivalent function, smaller footprint)
  3. For maintenance of existing systems: Only surplus / stock spare parts available. Confirm 115V or 230V variant before procurement, the two versions are not interchangeable.
  4. Single-channel equivalent: WE77/Ex-1, replacement KFA6-SR1-Ex
  5. Solução de problemas comuns
  6. Nenhuma resposta de entrada: Check for LB lead breakage alarm on NAMUR loop; verify external capacitance/inductance does not exceed intrinsic safety limits
  7. Relay fails to switch: Confirm power supply variant matches device rating; verify input current falls within NAMUR operating range
  8. Frequent false lead breakage alarm: Excessive cable length with high distributed capacitance/inductance, or damaged cable insulation
  9. Instalação Mecânica
  10. Trilho DIN: Montagem em trilho DIN padrão de 35 mm. Hook top clip onto rail, press module down to lock. Para remover: Lift bottom latch and pull outward.
  11. Ambiente Operacional

Temperatura ambiente: -25℃ ~ +60 ℃, cabinet ventilation required; mantenha longe de fontes de calor, vibration and corrosive gas

Classe de proteção IP20, gabinete interno apenas para uso, not for open or humid direct exposure

Mounting clearance: Small gaps between adjacent modules recommended for heat dissipation

  1. Mandatory Explosion Protection Rules

✅ Unit must be mounted in safe area, NEVER install in Zone0/1/2 hazardous areas

✅ Intrinsically safe cables (azul) and non-intrinsically safe cables (poder, saída de relé) must run in separate trunking/conduits, cannot share same conduit

  1. Terminal Table
Grupo TerminalTerminal nº.DescriçãoCircuit Classification
Channel1 Field NAMUR Input (Blue IS Terminals)1(-), 2(+)Channel1: NAMUR proximity sensor / explosion-proof dry contactIntrinsically safe EEx ia IIC
Channel2 Field NAMUR Input (Blue IS Terminals)8(+), 9(-)Channel2: NAMUR proximity sensor / explosion-proof dry contactIntrinsically safe EEx ia IIC
Channel1 Relay Change-over Output10, 11, 1211 Comum, 10 NC Normally Closed, 12 NÃO Normalmente abertoNon-intrinsically safe relay
Channel2 Relay Change-over Output13, 14, 1514 Comum, 13 NC Normally Closed, 15 NÃO Normalmente abertoNon-intrinsically safe relay
Fonte de energia17, 18Entrada de energia CA: Select 115V /230V variant, não intercambiávelNon-intrinsically safe

Importante: NAMUR field wiring is polarity sensitive. Reversed polarity will trigger LB lead breakage fault and unit malfunction.

  1. Wiring Schemes

Esquema 1: NAMUR Proximity Sensor (Mais Comum)

Channel1: 2-wire NAMUR sensor → Terminals 1(-), 2(+)

Channel2: 2-wire NAMUR sensor → Terminals 8(+), 9(-)

NAMUR loop includes LB lead breakage monitoring: Quebra de cabo, short circuit or reversed polarity will trigger channel fault LED.

Esquema 2: Explosion-proof Passive Dry Contact (Interruptor de limite)

Dry contact directly connected to IS terminals, lead breakage detection remains active. No external supply for contact; WE77/Ex-2 provides approx.8V/8mA IS drive internally.

Relay Output Wiring (to PLC DI)

Each channel is SPDT passive change-over contact, não é necessário fornecimento externo

Channel1: 11 Comum, 12 NÃO, 10 NC

Channel2: 14 Comum, 15 NÃO, 13 NC

Contact maximum rating: 250V e / 4UM; 24VDC /4A. Do not overload to avoid contact burnout.

Fiação de energia

Terminais 17 & 18 for AC supply:

WE77/Ex-2 230V version: AC 198~253V (Mainland China standard)

WE77/Ex-2 115V version: AC 103.5~126V

⚠️ Hardware differs between two power versions, NOT interchangeable.

  1. Seleção de cabos (Explosion Compliance Mandatory)
  2. Intrinsically safe side (Blue terminals to field instrument): Blue IS cable recommended, conductor cross-section ≥0.5mm², rated voltage ≥500V
  3. Intrinsically safe loop must be verified for maximum permitted cable capacitance Co and inductance Lo:

IIC application: Co ≤0.23µF, Lo ≤3mH

IIB application: Co ≤0.929µF, Lo ≤5mH

Excessive cable length causes distributed capacitance/inductance over-limit, invalidating intrinsic safety certification.

  1. Shielded cable: Shield single-point earthed at control room end, shield floating at hazardous area side to prevent earth loop current.
  2. Wiring Procedure (Safety Sequence)
  3. Desligar! Isolate all power sources and confirm zero voltage before wiring
  4. Connect field intrinsically safe cables first (blue terminals), verify polarity
  5. Connect relay output cables to PLC DI modules
  6. Connect module power terminals 17 &18 last
  7. Tighten all screw terminals, no loose strands or exposed copper causing short circuit
  8. Verificação pré-energia: IS cables separated from power cables, no mixed routing
  9. Power-on commissioning: Power on without field load first and check channel LEDs. Connect field sensors, test switching action and LB fault function.
  10. Comissionamento & Indicação LED

LED independente por canal: Illuminated when valid input signal present; LB lead breakage fault will extinguish LED / trigger fault alarm

Modo de operação: Reversible mode available (relay de-energizes when input activates), configurable per project requirement

Lead breakage test: Disconnect field sensor wire, module shall detect line fault and activate LB alarm.

  1. Critical Prohibitions & Armadilhas Comuns
  2. ❌ Megger insulation test is forbidden on intrinsically safe terminals! High voltage from megger will destroy internal IS circuit and permanently damage unit. Remove all IS wiring before any cable high voltage test.
  3. ❌ Never route 220V power cables or non-IS signal wires into blue intrinsically safe terminals; intrinsic safety protection will be destroyed.
  4. ❌ IS circuits and non-IS circuits cannot share same cable or trunking.
  5. ❌ Do not install WE77/Ex-2 in hazardous area.
  6. ❌ Do not exceed Co/Lo intrinsic safety limits, explosion certification will be invalid.
  7. ❌ Do not overload relay contacts; damaged relay contacts cannot be repaired separately, full module replacement required.
  8. Earthing Instruction

WE77/Ex-2 is transformer-isolated safety barrier; galvanic isolation between IS side and control side. Module housing connected to cabinet protective earth as standard, resistência de terra ≤4Ω. Isolated barrier does NOT require dedicated intrinsic safety earth like zener barriers.

  1. Post Power-On Quick Fault Diagnosis
  2. Sem iluminação LED após ligar: Check voltage at terminal 17/18, confirm 115V/230V model match, check loose power terminals.
  3. Persistent LB fault alarm: ①NAMUR polarity reversed; ②broken cable; ③cable distributed capacitance/inductance over-limit; ④field sensor damaged.
  4. Sensor switches but relay does not toggle: Verify NAMUR current within operating range; check NO/NC contact selection.
  5. Unintended relay chattering/false switching: Flutuação de energia, interferência eletromagnética. Use shielded cable and separate strong/weak signal wiring.

WE77/Ex-2 Intrinsically Safe Blue Terminals & Non-Intrinsically Safe Relay Terminal Current Parameters

Distinguish between intrinsic safety certified maximum short-circuit current Io (explosion parameter) and NAMUR normal operating current. Non-intrinsically safe side is relay contact rated current.

🔵 Blue Terminals: Intrinsically Safe Field Input Side

WE77/Ex-2 230V version (Mainland China mainstream)

  1. Intrinsic safety maximum short-circuit current Io = 62mA (certified explosion parameter. In short-circuit condition, module limits output current below this value to maintain explosion safety)
  2. NAMUR normal operating current: Open circuit ≈8V DC, static short-circuit current ≈8mA; Switching threshold 1.2~2.1mA per NAMUR standard

Note for 115V WE77/Ex-2 variant: Io=31mA. Always confirm power supply version during selection.

⚠️ Importante: 62mA is the safety limit short-circuit current, NOT normal working current. Under normal NAMUR sensor operation, loop current is only a few milliamps.

⚪ White Terminals: Non-intrinsically Safe Relay Output (Terminais 10/11/12,13/14/15)

SPDT change-over contact rated load current (carga resistiva) per channel

CA 250V: 4UM (cosφ>0.7)

CC 24V: 4UM

DC 60V: 0.6UM

CC 220V: 0.1UM

Max contact power rating: 500VA; Overload will cause contact erosion, module non-repairable.

Adicional: Module Power Terminals (17,18)

Total power dissipation approx.2.5W. For 230V AC supply, power loop current is low, aprox..0.01UM.

Summary Table

Grupo TerminalItemValorObservações
Blue IS Terminals (230Modelo V)Intrinsic safety limit short-circuit current Io62mAExplosion protection short-circuit limit
Blue IS TerminalsNAMUR normal short-circuit current≈8mANAMUR sensor operating current
White Non-IS Relay ContactsRated current at AC250V / CC24V4UMCarga resistiva, independent per channel