Pedido nº.: 2708863, PROFIBUS DP Modular Isolated Bus Repeater
- Definição de modelo
PSI: Process Signal Interface series
REP: Repetidor
PROFIBUS: Bus type PROFIBUS DP
12MB: Max communication rate 12 Mbps
- Especificações principais
| Item | Parâmetro |
| Número do pedido. | 2708863 |
| Nome do produto | PSI-REP-PROFIBUS/12MB |
| Protocolo de ônibus | PROFIBUSDP (RS485, IEC61158) |
| Velocidade de comunicação | 9.6k ~ 12Mbps, DIP switch for manual or auto baud rate detection |
| Fonte de energia | DC 18~30V (nominal 24VDC) |
| Isolamento | 4-way galvanic isolation (Fonte de energia, Segment A bus, Segment B bus, painel traseiro) |
| Montagem | Montagem em trilho DIN 35mm |
| Temperatura operacional | -20℃ ~ +60 ℃ |
| Topologia | Linha, estrela, tree; supports cascading for bus extension |
| Funções | Bit retiming, faulty message filtering, switchable bus termination resistor |
| Certificações | CE, UL, cULus, ATEX, EAC, KC |
| Material da Habitação | PA6.6-FR, grey RAL7042 |
- Product Functions
- Bus Extension: Extend PROFIBUS cable length; repeater recovers signal waveform, multi-stage cascading supported.
- Galvanic Isolation: 4-segment isolation eliminates ground loop interference, segregates networks at different potential levels for enhanced EMC performance.
- Signal Shaping: Bit sampling + bit retiming to suppress jitter and filter corrupted interference packets.
- Modular Backplane Bus: Integrated DIN rail backplane allows direct combination with PSI-MOS fiber converters to build hybrid PROFIBUS copper/fiber networks.
- Active termination resistor, redundant power supply supported.
- Cenários típicos de aplicação
Segmental isolation for large-scale factory PROFIBUS DP networks
Networking of devices with differing ground potentials (conversores de frequência, motores, field instruments)
Long-distance PROFIBUS wiring and compensation for bus signal attenuation
PROFIBUS bus isolation in hazardous areas (Certificação ATEX)
Retrofit and expansion of PROFIBUS legacy systems in steel, papel, water treatment and automotive production lines
- Seleção de modelo & Alternativas
✅ Identical replacement: 2708863 (PSI-REP-PROFIBUS/12MB), original unique part number
No fully pin-to-pin domestic alternative from Fênix Contato.
Alternative similar PROFIBUS repeaters: Siemens PROFIBUS repeater, Weidmüller PROFIBUS isolated repeater (funções semelhantes, but limited modular backplane capability and incompatible with PSI-MOS optical modules).
- Instalação & Diretrizes de Manutenção
- Do not reverse PROFIBUS A/B wiring on the two bus ports.
- Bus termination resistors: enable only at the physical endpoints of each segment; disable for intermediate nodes.
- Interruptor DIP: auto baud rate mode suitable for most field applications; fixed baud rate for high-speed stable operation.
- 24VDC isolated power supply recommended to reduce common-mode interference.
- Solução de problemas: read module LEDs to identify power failure, Segment A bus fault or Segment B bus fault.
- Barramento de backplane: Phoenix dedicated backplane connectors required when combining with PSI-MOS fiber converters.
- HS Code Reference (Foreign Trade)
85176290 (Other digital repeaters, equipamento de comunicação). Final customs classification subject to local customs authority.
- Second-Hand Inspection Checklist
- Power on and verify power indicator.
- Connect Segment A and B separately to master/slave devices and test 12Mbps communication.
- Measure isolation resistance to confirm intact 4-way isolation without breakdown.
- Validate DIP switch functions.
- Inspect housing for burn marks and terminal blocks for oxidation.
PHOENIX 2708863|PSI-REP-PROFIBUS/12MB Application Scenarios
Posicionamento central: PROFIBUS DP Modular Isolated Repeater. Core benefits: bus segment isolation, signal reshaping & regeneração, breaking the 32-node limit per electrical segment, hybrid networking with PSI-MOS fiber modules, max 12Mbps high-speed communication, Zona ATEX 2 certificação de área perigosa.
- General Network Use Cases
- Bus Distance Extension
PROFIBUS twisted pair has limited transmission distance at 12Mbps. A repeater regenerates signal waveform and extends the bus by segmentation; multi-stage cascading is available.
Princípio: Each independent segment achieves maximum cable length corresponding to its baud rate, solving signal attenuation and inter-symbol jitter over long cables.
- Node Quantity Expansion
PROFIBUS standard limits max 32 devices per electrical segment. The repeater creates isolated new segments, total nodes = n×32 (n = number of segmens). Preferred solution for legacy projects adding inverters, remote I/O and DP instruments when node capacity is exhausted.
- Ground Potential Difference Isolation (Aplicação mais comum)
Different workshops, high/low voltage cabinets and motor fields may have ground loop voltage ranging from tens to hundreds of volts, which causes intermittent DP communication dropout or burns DP transceiver chips.
The module features 4-way isolation (Poder / Segment A / Segment B / Painel traseiro) to cut ground loops and protect PLC and field instruments.
- Segmented Fault Isolation to Improve System Availability
Split one long bus into multiple isolated segments. Curto-circuito, cable break or heavy interference on one segment will not propagate to the whole network. Only the faulty segment stops operation; the rest of the network remains online for easy fault localization.
- Topology Modification: Convert Linear Bus to Star/Tree Branches
Native PROFIBUS only supports linear topology. This repeater creates independent DP branch segments to implement star topology for distributed device clusters. Each branch operates independently without interference from the main trunk.
- Hybrid Copper-Fiber Bus Networking (Unique Advantage of This Model)
Combined with Phoenix PSI-MOS PROFIBUS fiber converters via DIN rail backplane connectors, a modular station can be built to form hybrid PROFIBUS copper + fiber networks for long-distance cross-area deployment and high-EMI environments using optical transmission.
- Aplicações Específicas da Indústria
✅ Automotive Welding & Linhas de montagem
Large quantities of DP servos, conversores de frequência, robots and distributed I/O; high ground potential differences and strong EMI from welding machines.
Benefícios: segment isolation, DP bus protection, node expansion, supporting 12Mbps high-speed motion control communication.
✅ Steel, Metalurgia & Rolling Lines
Alta temperatura, large motors and high-power drives with severe EMI and differing rack ground potentials.
Benefícios: isolate segments at different potentials, prevent ground loop damage to DP interfaces, extend bus across rolling mill areas.
✅ Water Treatment, Wastewater Plants & Estações de bombeamento
Widely distributed DP pressure/level transmitters and valves over large plant footprints with long cable runs.
Benefícios: bus extension and segmentation; suppress interference from high-power pumps; legacy system retrofit and expansion.
✅ Chemical & Pharmaceutical Plants (Zona ATEX 2)
Module carries ATEX certification for PROFIBUS networks in Zone 2 áreas perigosas.
Used for bus isolation between hazardous field areas and non-hazardous control cabinets, and segmented protection for field instrument segments.
✅ Paper & Textile Production Lines
Multiple DP frequency converter clusters for continuous production lines where full-line shutdown is unacceptable.
Segmentation ensures local faults do not stop the whole production line and accelerates fault location.
✅ Power Plants, Cimento & Mining DCS/PLC Systems
Wide plant layout with high-power equipment and ground potential drift; DP bus connects remote I/O and fieldbus instruments.
- Frequent Retrofit Scenarios
- Legacy PROFIBUS System Expansion: Original DP segment reaches 32-node limit. Add repeaters to create new segments without PLC master replacement.
- Troubleshooting Unstable Communication: Frequent intermittent dropout caused by ground loop interference; install isolated repeaters.
- Speed Upgrade: Original long cable limited operation to 1.5Mbps. Segmentation allows upgrade to 12Mbps high-speed DP.
- Inter-cabinet Networking: Communication between separate control cabinets with potential differences, isolated via repeaters.
- Cenários não aplicáveis
No protocol conversion. Physical-layer PROFIBUS DP repeater only, cannot convert to Profinet or Modbus.
Zona 2 certified only, not suitable for Zone 0 / Zona 1 intrinsically safe hazardous areas.
Proteção IP20, for cabinet mounting only; not for direct outdoor field installation.
- Supporting Selection Tips
Backplane combination: use PSI-MOS-PROFIB/FO series optical modules for long-distance fiber transmission.
Redundância: module supports dual 24VDC redundant power supply; recommended for critical production lines.
Topology notes: each segment must be terminated independently. The repeater’s two ports belong to two separate bus segments.
Working Principle of PROFIBUS DP Modular Isolated Repeater (PSI-REP-PROFIBUS/12MB, 2708863)
Core nature: RS485 physical-layer signal regeneration + galvanic isolation + bit retiming. No parsing of DP application-layer protocols, only electrical signal processing. It is a physical-layer device, NOT a gateway or protocol converter.
- Fundamental Principle Breakdown
PROFIBUS DP is based on RS485 differential bus. Long cables, high node count and ground potential differences introduce three major issues: atenuação de sinal, instabilidade de sinal (phase drift) and common-mode ground loop interference.
The repeater divides the bus into two electrically independent segments (Side A, Side B) and executes three core operations:
- Recepção: Read differential A/B signals from Segment A.
- Signal Shaping & Bit Retiming: Recover clean square-wave clock and eliminate transmission-induced jitter and distortion.
- Driven Forwarding: Send newly regenerated differential signals to Segment B with fresh driver levels.
⚠️ Only valid DP bit streams are forwarded; corrupted spike/interference packets are filtered out.
1.1 Signal Regeneration (Bit Retiming, Key Feature of This Model)
Low-cost generic RS485 repeaters merely amplify signals without clock recovery, so jitter accumulates and communication remains unstable after multi-stage cascading.
This Phoenix model is an active repeater with retiming:
Internal PLL locks onto and synchronizes with incoming data stream.
Extracts bit clock and reconstructs standard square waveform.
Outputs new differential signals with clean edges.
Vantagem: Supports multi-stage cascading without cumulative jitter, enabling 12Mbps high-speed DP operation.
1.2 4-Way Galvanic Isolation (Core Anti-Interference Feature)
Modelo 2708863: Isolation between power supply, Segment A bus, Segment B bus and backplane bus.
Isolation components: high-speed digital isolators (not low-speed conventional optocouplers), rated for 12Mbps bandwidth.
Função: cut off ground loop current between Segment A and Segment B.
In field sites, potential differences of tens to hundreds of volts may exist between devices/cabinets. Ground loop current creates common-mode interference on DP shield and signal lines, leading to intermittent communication or permanent damage to RS485 transceivers. After isolation, Segment A and Segment B have independent reference grounds; potential differences cannot cross segments.
1.3 Segmento & Fault Isolation
Curto-circuito, cable break or severe interference on Segment A → repeater detects anomaly and prevents faulty/short-circuit signals from propagating to Segment B.
Fault is confined to one segment; rest of DP network remains operational for segmented troubleshooting.
1.4 Baud Rate Recognition via DIP Switches
Auto mode: automatically detects DP baud rate on power-up (9.6k ~12Mbps) and synchronizes.
Fixed mode: baud rate locked via DIP switch for high-speed stable production lines to avoid misdetection.
1.5 Modular Backplane Bus (Unique to PSI Series)
Modules communicate via built-in backplane connectors on DIN rail.
This repeater can be directly assembled with PSI-MOS PROFIBUS fiber transceivers on the same rail without extra wiring to realize PROFIBUS electrical ↔ optical conversion, building hybrid copper/fiber bus networks.
- Signal Flow Diagram
DP Segment A (Mestre / E/S / Conversor de frequência)
↓ (Differential A/B signals)
【Isolated Side A Receiver Circuit】
PLL bit clock reconstruction + corrupted packet filtering
【Isolated Side B Driver Circuit】
DP Segment B (Independent segment, máx. 32 nós)
- Critical Boundary Notes (Armadilhas Comuns)
- Physical-layer device only, no PROFIBUS protocol parsing
Does not interpret DP telegrams, perform address forwarding or protocol conversion. Cannot convert to Profinet / Modbus. Only forwards raw binary bit streams.
- Port A and Port B belong to two fully independent bus segments
Termination resistors must be configured separately for each segment!
✅ Enable termination only at the physical endpoints of each segment
✅ Repeater ports act as segment start points. Termination on repeater ports is disabled by default (unless that port is the physical end of its segment).
- Node count limit: máx. 32 DP nodes per segment (the repeater itself is not a DP slave and does NOT count towards the 32-node limit).
- Cascading: multi-stage cascading supported, but total latency must stay within PROFIBUS DP timing budget.
- Comparison with Generic RS485 Repeaters
| Item | Generic RS485 Repeater | PSI-REP-PROFIBUS/12MB (2708863) |
| Clock Handling | Simple signal amplification, no bit retiming | PLL bit retiming, waveform reconstruction |
| Velocidade máxima | Many limited to 1.5Mbps | Up to 12Mbps |
| Isolamento | Some have only single isolation | 4-way independent isolation (Poder / UM / B / Painel traseiro) |
| Fault Containment | Faults easily pass through to opposite side | Segment isolation, blocks fault propagation |
| Expansão | No backplane, incompatible with optical modules | DIN rail backplane, directly compatible with PSI-MOS optical modules |
- Typical Operational Example
PLC master transmits DP telegram on Segment A → repeater Side A receives differential signals, galvanic isolation applied, PLL reconstructs clean bit stream and filters glitches → isolated Side B driver outputs regenerated differential signals → inverters and remote I/O on Segment B receive the telegram. Bidirectional half-duplex communication works in reverse direction identically.
Contator,disjuntor,sensor,Codificador,CLP,Conversor





















NH42-63-318x560.png)