: iC65N 2P C16A Schneider A9F18216 Miniature Circuit Breaker
Primeiro, it should be clarified that A9F18216 is a disjuntor miniatura (MCB) of the iC65N series, not an RCBO (Residual Current Circuit Breaker with Overcurrent protection). An RCBO is an integrated device with overload, short-circuit and earth leakage protection, while A9F18216 only provides overload and short-circuit protection. For earth leakage protection, it must be used with an additional Vigi iC60 or QuickVigi iC60 residual current module.
Detalhamento do código do modelo
| Model Part | Significado |
| iC65N | Série de produtos: Série Acti9 iC65; N stands for 6kA breaking capacity |
| 2P | Número de pólos: 2 postes (Linha + Neutral) |
| C | Curva de tropeço: Tipo C, for power distribution and lighting circuits; instantaneous tripping at 5–10× rated current |
| 16UM | Corrente nominal: 16 amperes |
| A9F18216 | Schneider official order code |
Core Technical Specifications
| Item | Especificação detalhada |
| Tipo de produto | Disjuntor Miniatura (MCB) |
| Série | Acti9 iC65N |
| Número de poloneses | 2P (2-wire system, 2 protected poles) |
| Corrente nominal (Em) | 16UM |
| Curva de tropeço | Tipo C |
| Quebrando Capacidade (UTI) | 6o (400V e) |
| Tensão nominal | 230/400V e |
| Freqüência | 50/60Hz |
| Dimensões | 2 módulos (36mm width) |
| Montagem | Montagem em trilho DIN |
| Grau de Proteção | IP20 |
| Tripping Type | Thermal-magnetic (sobrecarga: bimetal strip; short-circuit: magnetic coil) |
| Applicable Standards | CEI 60898-1 |
Recursos do produto & Functions
- Reliable Protection: Provides overload and short-circuit protection to prevent electrical fires and equipment damage
- Type C Curve: Suitable for power distribution, lighting circuits and resistive loads, with good inrush current tolerance
- Design Compacto: 2-module width, saving space in distribution boards
- VisiTrip Indicator: Red mechanical window shows trip status for quick fault diagnosis
- Multiple Wiring Methods: Supports front, rear and rail-mounted wiring to meet various installation needs
- Wide Operating Temperature Range: -25°C a +40°C, adaptable to various environments
Difference from RCBO and Earth Leakage Protection Solutions
| Tipo de produto | Funções de proteção | Typical Model | Instalação |
| A9F18216 (iC65N 2P C16A) | Sobrecarga + Curto-circuito | A9F18216 | Standalone |
| RCBO (iC65N Vigi+) | Sobrecarga + Curto-circuito + Earth Leakage | A9D11216 (2P C16A 30mA Type A) | Integrated |
| MCB + Leakage Module | Sobrecarga + Curto-circuito + Earth Leakage | A9F18216 + A9Q41216 / A9V41216 | Module attached to right of MCB |
To upgrade A9F18216 to a system with earth leakage protection, you may choose:
QuickVigi iC60 2P 16A 30mA module (A9Q41216, 1.5 módulos, economia de espaço)
Vigi iC60 2P 16A 30mA module (A9V41216, 3 módulos, standard version)
Aplicativos
Suitable for overload and short-circuit protection in final distribution systems, especially for:
Lighting circuits in residential and commercial buildings
Circuits for small power equipment and resistive loads
Branch protection in distribution boards
Applications requiring flexible combination with earth leakage modules
Key Installation & Operating Instructions
- Montado em trilho DIN padrão de 35mm
- Operating temperature range: -25°C a +40°C
- Grau de poluição: 3
- Rated impulse withstand voltage (Um): 6kV
- Wiring capacity: máx.. 25mm² cable
- Mechanical endurance: 20,000 operating cycles
A9F18216 is a commonly used 2P 16A Type C MCB from Schneider’s Acti9 series, offering reliable overload and short-circuit protection. If earth leakage protection is required, a corresponding residual current module must be added, or an RCBO from the iC65N Vigi+ series (por exemplo, A9D11216) can be selected directly.
Supplementary Information for Schneider A9F18216: Official Ordering, Full Series List & Chinese Domestic Alternatives
- Official Ordering Information
| Item | Detalhes |
| Product Name | iC65N 2P C16A Miniature Circuit Breaker (MCB) |
| Official Order Code | A9F18216 |
| Série | Acti9 iC65N (N = 6kA breaking capacity) |
| Quadro atual | 63UM |
| Tensão nominal | 230/400V e |
| Freqüência | 50/60Hz |
| Quebrando Capacidade (UTI) | 6o (400V e) |
| Curva de tropeço | Tipo C (instantaneous trip at 5–10× In) |
| Número de poloneses | 2P (2-arame, Linha + Neutral) |
| Corrente nominal | 16UM |
| Dimensões | 2 módulos (36mm width) |
| Montagem | Montagem em trilho DIN |
| Grau de Proteção | IP20 |
| Applicable Standards | CEI 60898-1, GB 14048.2 |
| Capacidade de fiação | Máx.. 25mm² cable |
| Mechanical Endurance | 20,000 operating cycles |
| Warranty Period | 12 meses |
- Full Model List of iC65N Series (A9F Prefix)
The iC65N series is categorized by pole number. Order code rule: A9F + [Pole Code] + [Current Code]
Pole codes: 11=1P, 12=2P, 13=3P, 14=4P
Current codes: 06=6A, 08=8A, 10=10A, 13=13A, 16=16A, 20=20A, 25=25A, 32=32A, 40=40A, 50=50A, 63=63A
1P Models (A9F181xx)
| Corrente nominal | Código do pedido | Curva de tropeço |
| 6UM | A9F18106 | Tipo C |
| 8UM | A9F18108 | Tipo C |
| 10UM | A9F18110 | Tipo C |
| 13UM | A9F18113 | Tipo C |
| 16UM | A9F18116 | Tipo C |
| 20UM | A9F18120 | Tipo C |
| 25UM | A9F18125 | Tipo C |
| 32UM | A9F18132 | Tipo C |
| 40UM | A9F18140 | Tipo C |
| 50UM | A9F18150 | Tipo C |
| 63UM | A9F18163 | Tipo C |
2P Models (A9F182xx)
| Corrente nominal | Código do pedido | Curva de tropeço |
| 6UM | A9F18206 | Tipo C |
| 8UM | A9F18208 | Tipo C |
| 10UM | A9F18210 | Tipo C |
| 13UM | A9F18213 | Tipo C |
| 16UM | A9F18216 | Tipo C |
| 20UM | A9F18220 | Tipo C |
| 25UM | A9F18225 | Tipo C |
| 32UM | A9F18232 | Tipo C |
| 40UM | A9F18240 | Tipo C |
| 50UM | A9F18250 | Tipo C |
| 63UM | A9F18263 | Tipo C |
3P Models (A9F183xx)
| Corrente nominal | Código do pedido | Curva de tropeço |
| 6UM | A9F18306 | Tipo C |
| 8UM | A9F18308 | Tipo C |
| 10UM | A9F18310 | Tipo C |
| 13UM | A9F18313 | Tipo C |
| 16UM | A9F18316 | Tipo C |
| 20UM | A9F18320 | Tipo C |
| 25UM | A9F18325 | Tipo C |
| 32UM | A9F18332 | Tipo C |
| 40UM | A9F18340 | Tipo C |
| 50UM | A9F18350 | Tipo C |
| 63UM | A9F18363 | Tipo C |
4P Models (A9F184xx)
| Corrente nominal | Código do pedido | Curva de tropeço |
| 6UM | A9F18406 | Tipo C |
| 8UM | A9F18408 | Tipo C |
| 10UM | A9F18410 | Tipo C |
| 13UM | A9F18413 | Tipo C |
| 16UM | A9F18416 | Tipo C |
| 20UM | A9F18420 | Tipo C |
| 25UM | A9F18425 | Tipo C |
| 32UM | A9F18432 | Tipo C |
| 40UM | A9F18440 | Tipo C |
| 50UM | A9F18450 | Tipo C |
| 63UM | A9F18463 | Tipo C |
Special Models (Tipo D / High Breaking Capacity)
| Modelo | Descrição | Código do pedido |
| iC65N 2P D16A | Curva tipo D (10–14×In), for motor loads | A9F18216D |
| iC65H 2P C16A | High breaking capacity 10kA | A9F18216H |
| iC65L 2P C16A | Low breaking capacity 4.5kA | A9F18216L |
- Chinese Domestic Brand Alternatives (2P C16A MCB)
| Marca | Série | Modelo | Quebrando Capacidade | Principais recursos | Referência de Preço |
| CHINT | Editora-63 | NXB-63 2P C16A | 6o | Leading domestic brand, econômico, CCC certified | 40–50% of Schneider |
| DELIXI | DZ47s | DZ47s 2P C16A | 6o | Well-known domestic brand, qualidade confiável, widely used | 40–50% of Schneider |
| NAXIN | NDM1 | NDM1-63 2P C16A | 6o | Industrial-grade quality, suitable for engineering projects | 50–60% of Schneider |
| Interruptor Changshu | CH1 | CH1-63 2P C16A | 6o | Established state-owned enterprise, mature technology | 50–60% of Schneider |
| People Electric | RMK-63 | RMK-63 2P C16A | 6o | Affordable price, suitable for bulk purchase | 30–40% of Schneider |
Key Selection Guidelines for Alternatives
- Matching breaking capacity: Ensure alternative ≥6kA, same as iC65N
- Matching tripping curve: Type C for power/lighting; Type D for motors
- Dimension compatibility: All 2 módulos (36milímetros), DIN rail mount, fits distribution boards
- Complete certification: Must have CCC; CE recommended for industrial use
- Wiring capacity: Ensure max. wiring ≥25mm² to meet site requirements
- Earth Leakage Protection Upgrade Solutions
Two options to upgrade A9F18216 with earth leakage protection:
Option 1: MCB + Leakage Module Combination
| Module Type | Modelo | Especificação | Largura | Código do pedido |
| QuickVigi iC60 | 2P 16A 30mA AC | Compactar 1.5 módulos | 27milímetros | A9Q41216 |
| Vigi iC60 | 2P 16A 30mA AC | Padrão 3 módulos | 63milímetros | A9V41216 |
| Vigi iC60 | 2P 16A 30mA A | Detects pulsating DC leakage | 63milímetros | A9V42216 |
Option 2: Direct Replacement with RCBO
| Schneider RCBO Model | Descrição | Código do pedido |
| iC65N Vigi+ 2P C16A 30mA A | Integrated leakage protection | A9D11216 |
| iC65N Vigi+ 2P C16A 30mA AC | Integrated leakage protection | A9D10216 |
A9F18216 is the standard 2P C16A model in the Schneider iC65N series with clear ordering information. The series covers various pole numbers and current ratings. Abundant Chinese domestic alternatives are available for flexible selection based on project budget and quality requirements. Earth leakage protection can be achieved by adding a leakage module or replacing with an RCBO to ensure safe and reliable electrical systems.
Full Model List of Schneider A9F18216 in the Same Series (iC65N Series)
- Model Coding Rule Explanation
The coding rule for A9F-prefixed order codes of Schneider iC65N series MCBs is as follows:
| Code Part | Significado |
| A9F | Product category: Acti9 iC65 MCB |
| 17 | Type B curve (instantaneous trip at 2–5×In) |
| 18 | Curva tipo C (instantaneous trip at 5–10×In, standard for lighting & distribuição) |
| 19 | Curva tipo D (instantaneous trip at 10–14×In, for motor loads) |
| 1/2/3/4 | Número de pólos: 1=1P, 2=2P, 3=3P, 4=4P |
| 01/02/04/06…63 | Corrente nominal: 1UM, 2UM, 4UM, 6UM…63UM |
- Lista completa de modelos (By Pole Number)
2.1 1P Models (A9F[17/18/19]1xx)
| Corrente nominal | Tipo B (A9F171xx) | Tipo C (A9F181xx) | Tipo D (A9F191xx) |
| 1UM | A9F17101 | A9F18101 | A9F19101 |
| 2UM | A9F17102 | A9F18102 | A9F19102 |
| 4UM | A9F17104 | A9F18104 | A9F19104 |
| 6UM | A9F17106 | A9F18106 | A9F19106 |
| 8UM | A9F17108 | A9F18108 | A9F19108 |
| 10UM | A9F17110 | A9F18110 | A9F19110 |
| 13UM | A9F17113 | A9F18113 | A9F19113 |
| 16UM | A9F17116 | A9F18116 | A9F19116 |
| 20UM | A9F17120 | A9F18120 | A9F19120 |
| 25UM | A9F17125 | A9F18125 | A9F19125 |
| 32UM | A9F17132 | A9F18132 | A9F19132 |
| 40UM | A9F17140 | A9F18140 | A9F19140 |
| 50UM | A9F17150 | A9F18150 | A9F19150 |
| 63UM | A9F17163 | A9F18163 | A9F19163 |
2.2 2P Models (A9F[17/18/19]2xx)
| Corrente nominal | Tipo B (A9F172xx) | Tipo C (A9F182xx) | Tipo D (A9F192xx) |
| 1UM | A9F17201 | A9F18201 | A9F19201 |
| 2UM | A9F17202 | A9F18202 | A9F19202 |
| 4UM | A9F17204 | A9F18204 | A9F19204 |
| 6UM | A9F17206 | A9F18206 | A9F19206 |
| 8UM | A9F17208 | A9F18208 | A9F19208 |
| 10UM | A9F17210 | A9F18210 | A9F19210 |
| 13UM | A9F17213 | A9F18213 | A9F19213 |
| 16UM | A9F17216 | A9F18216 | A9F19216 |
| 20UM | A9F17220 | A9F18220 | A9F19220 |
| 25UM | A9F17225 | A9F18225 | A9F19225 |
| 32UM | A9F17232 | A9F18232 | A9F19232 |
| 40UM | A9F17240 | A9F18240 | A9F19240 |
| 50UM | A9F17250 | A9F18250 | A9F19250 |
| 63UM | A9F17263 | A9F18263 | A9F19263 |
2.3 3P Models (A9F[17/18/19]3xx)
| Corrente nominal | Tipo B (A9F173xx) | Tipo C (A9F183xx) | Tipo D (A9F193xx) |
| 1UM | A9F17301 | A9F18301 | A9F19301 |
| 2UM | A9F17302 | A9F18302 | A9F19302 |
| 4UM | A9F17304 | A9F18304 | A9F19304 |
| 6UM | A9F17306 | A9F18306 | A9F19306 |
| 8UM | A9F17308 | A9F18308 | A9F19308 |
| 10UM | A9F17310 | A9F18310 | A9F19310 |
| 13UM | A9F17313 | A9F18313 | A9F19313 |
| 16UM | A9F17316 | A9F18316 | A9F19316 |
| 20UM | A9F17320 | A9F18320 | A9F19320 |
| 25UM | A9F17325 | A9F18325 | A9F19325 |
| 32UM | A9F17332 | A9F18332 | A9F19332 |
| 40UM | A9F17340 | A9F18340 | A9F19340 |
| 50UM | A9F17350 | A9F18350 | A9F19350 |
| 63UM | A9F17363 | A9F18363 | A9F19363 |
2.4 4P Models (A9F[17/18/19]4xx)
| Corrente nominal | Tipo B (A9F174xx) | Tipo C (A9F184xx) | Tipo D (A9F194xx) |
| 1UM | A9F17401 | A9F18401 | A9F19401 |
| 2UM | A9F17402 | A9F18402 | A9F19402 |
| 4UM | A9F17404 | A9F18404 | A9F19404 |
| 6UM | A9F17406 | A9F18406 | A9F19406 |
| 8UM | A9F17408 | A9F18408 | A9F19408 |
| 10UM | A9F17410 | A9F18410 | A9F19410 |
| 13UM | A9F17413 | A9F18413 | A9F19413 |
| 16UM | A9F17416 | A9F18416 | A9F19416 |
| 20UM | A9F17420 | A9F18420 | A9F19420 |
| 25UM | A9F17425 | A9F18425 | A9F19425 |
| 32UM | A9F17432 | A9F18432 | A9F19432 |
| 40UM | A9F17440 | A9F18440 | A9F19440 |
| 50UM | A9F17450 | A9F18450 | A9F19450 |
| 63UM | A9F17463 | A9F18463 | A9F19463 |
- Special Versions (Quebrando Capacidade / Expansão de função)
| Modelo | Descrição | Código do pedido | Observações |
| iC65H 2P C16A | High breaking capacity 10kA | A9F18216H | H = High breaking |
| iC65L 2P C16A | Low breaking capacity 4.5kA | A9F18216L | L = Low breaking |
| iC65N 2P C16A R | With overload alarm contact | A9F18216R | R = With alarm contact |
| iC65N 2P C16A DC | For DC circuits only | A9F18216DC | For DC system protection |
- Unified Key Technical Specifications
All A9F-prefixed iC65N models share the following core parameters:
Capacidade de ruptura (UTI): 6o (400V e)
Tensão nominal: 230/400V e
Freqüência: 50/60Hz
Dimensões: 1P=1 module (18milímetros), 2P=2 modules (36milímetros), 3P=3 modules (54milímetros), 4P=4 modules (72milímetros)
Montagem: Montagem em trilho DIN
Grau de Proteção: IP20
Tripping type: Thermal-magnetic (sobrecarga: bimetal strip; short-circuit: magnetic coil)
Applicable standards: CEI 60898-1, GB 14048.2
- Guia de seleção
- Tripping Curve Selection
Tipo B: For pure resistive loads (por exemplo, lâmpadas incandescentes)
Tipo C: For general power and lighting loads (mais comumente usado)
Tipo D: For inductive loads such as motors and transformers
- Pole Number Selection
1P: Protects line only, for single-phase lighting circuits
2P: Protects line + neutral, for single-phase socket circuits
3P: Protects three phases, for three-phase power circuits
4P: Protects three phases + neutral, para sistemas trifásicos de quatro fios
- Breaking Capacity Selection
Type N (6o): For general residential and commercial buildings
Type H (10o): For industrial sites or distribution systems near transformers
Type L (4.5o): For simple lighting systems
Contator,disjuntor,inversor solar,medidor elétrico,baterias solares
















NH42-63-318x560.png)