TeSys Deca GV2ME Disjuntor do motor (MPCB), push-button operated, terminais de braçadeira de parafuso
✅ Core Technical Specifications
Poloneses: 3P
Thermal overload setting range: 2.5~4 A
Potência do motor correspondente (400V trifásico): 1.5 kW
Tensão operacional nominal Ue: 690V e, 50/60 Hz
Insulation voltage Ui: 690V; Tensão suportável de impulso Uimp: 6kV
Magnetic short-circuit trip: aprox.. 13×In ≈ 51A (proteção instantânea contra curto-circuito)
Rated short-circuit breaking capacity Icu: 100kA @ 400 V
Categoria de utilização: AC-3 (for direct-on-line motor starting); built-in isolation function + proteção contra perda de fase
Controlar: Red STOP pushbutton, black START pushbutton, with TEST position
Montagem: Padrão de trilho DIN; IP20 (finger-safe on front face)
✅ Model Code Definition
GV2: TeSys GV2 motor circuit breaker series
MEU: Push-button version (rotary knob version: GV2P)
08: Current rating code, corresponding to 2.5–4A
C: China version with CCC certification
✅ Protection Functions
- Proteção contra sobrecarga térmica: Time-delayed tripping for continuous motor overload & rotor bloqueado; adjustable within 2.5~4A via the setting dial
- Magnetic short-circuit protection: Instant trip for phase-to-phase short circuit
- Phase-loss protection: Accelerated tripping when one phase is lost, preventing motor burnout
- Built-in start/stop operation: Can be used alone for small-motor direct start, or paired with contactors for star-delta / auto-transformer starting circuits
✅ Compatible Accessories (Field-mountable)
GVAN: Contato auxiliar (1NÃO+1NC, for ON/OFF & trip status feedback)
GVAX: Contato de alarme (differentiates overload trip from short-circuit trip)
GVAD: Viagem de manobra / undervoltage trip coil
GV2AF3: Barramento, adapter & interlock module
✅ Seleção & Referência de substituição
Same-series knob variant: GV2P08C (identical thermal-magnetic curve & tripping parameters, 2.5-4A)
Alternativas domésticas: Delixi CDM6e-M, Chint NS2-25 08 (2.5~4A motor protector)
Higher frame upgrade: GV3ME series with same current rating
✅ Wiring Guidelines
Line side L1/L2/L3: Conecte a fonte de alimentação trifásica; Load side T1/T2/T3: Conecte o motor
Contatos auxiliares (se instalado): Para CLP fault feedback & pilot lamp circuits
Setting rule: Align the dial with the motor rated current on nameplate; avoid long-term setting near the upper limit of the range
✅ Solução de problemas comuns
- Trips immediately on startup: Mostly short circuit. Verifique o enrolamento do motor & cable insulation; may also be caused by magnetic trip threshold mismatch
- Trips after running for a period: Sobrecarga. Verify actual motor current, load condition and thermal setting; check poor heat dissipation
- Phase-loss tripping: Check three-phase incoming voltage and loose terminal connections
✅ GV2-ME08C (Tipo de botão)
Operação: Push-button start/stop (black START, red STOP)
Intervalo atual: 2.5~4A; same tripping characteristics as GV2P08C
Características: Small panel cutout; designed for local cabinet operation; no obvious mid-position trip indication
Aplicativo: Standard domestic panel build, fãs comuns & bombas de água (most widely used model)
✅ GV2P08C (Rotary Knob Type)
Operação: Alça rotativa (knob control)
Intervalo atual: 2.5~4A (same as GV2ME08C)
Recurso principal: Clear trip mid-position; you can distinguish manual opening from fault tripping at a glance; supports external door-mounted extension handle GV2APN
Vantagens: Compliant with UL508 Type E; higher SCCR short-circuit rating; ideal for export equipment, door-mounted operation and strict safety specifications
📋 Comparison Table
| Item | Gv2me08c | GV2P08C |
| Operação | Push-button start/stop | Rotary knob handle |
| Indicação de viagem | No dedicated mid-position | Locked mid-position after trip |
| Door extension handle | Não compatível | Compatible with GV2APN |
| Tipo de terminal | Braçadeira de parafuso (suffix C) | Braçadeira de parafuso (suffix C) |
| Curva de viagem | Identical thermal-magnetic curve | Same tripping parameters |
| Uso típico | Domestic cabinet local operation | Export machines & door-mounted control |
Step-by-Step MPCB Selection Guide
Applicable to GV2ME / GV2P thermal-magnetic motor circuit breakers, only for three-phase asynchronous DOL motors; NOT for resistive loads, soft starters or inverter output circuits.
Etapa 1: Collect 3 key data from motor nameplate
- Corrente nominal In (most critical)
- Tensão nominal (typically 380/400V AC three-phase)
- Potência nominal (only for reference; never select purely by power)
Common mistake: Two 1.5kW motors with different pole counts have different rated currents; power-only selection frequently leads to mis-setting.
Etapa 2: Select the thermal setting range (core rule)
The MPCB adjustment range must fully contain the motor rated current, preferably in the middle third of the range
Fórmula:
Lower limit of breaker range < Motor rated current < Upper limit of breaker range
Recomendação: Place In within 30%~70% of the total range; avoid setting near the upper end
✅ Example: Motor rated current = 3.2A
Select GV2ME08C (2.5~4A); set dial to 3.2A.
❌ If In=3.9A, it still fits but sits close to the upper limit; frequent nuisance tripping will occur under continuous heavy load.
Thermal setting principles
Continuous loads (fãs, bombas de água): Set thermal current = motor nameplate rated current
Long starting inertia (grandes fãs, trituradores): Increase to 1.05~1.1×In; never exceed 1.1×In
Frequent jogging & shock loads: Do not simply raise the setting; use a separate thermal relay + contactor combination instead
Viagem termal: Sobrecarga, rotor bloqueado & proteção contra perda de fase (time-delayed);
Viagem magnética: Fixed non-adjustable short-circuit protection (13× upper range value, instantâneo).
Etapa 3: Choose operation type (Botão / Botão)
GV2MExxC (push-button, por exemplo. GV2-ME08C): Baixo custo, local cabinet operation, no clear trip mid-position
GV2Pxx (botão rotativo): Visible trip mid-position; add external door handle; suitable for export machines & fault identification
Etapa 4: Choose terminal type
Sufixo C: Terminais de fixação de parafuso (standard for domestic projects)
Sufixo 3: Terminais de mola (no-tool fast wiring; preferred for automated panel mass production)
Etapa 5: Verifique a tensão, capacidade de interrupção & utilization category
- Tensão nominal: Max 690V AC (400V standard)
- Short-circuit breaking capacity Icu: Must exceed the prospective short-circuit current at the installation point
Ordinary end circuits in small control cabinets: 100kA@400V of GV2 is sufficient
Circuits close to transformers with high short-circuit current: Add upstream fuses if Icu is insufficient
- Utilization category AC-3: Only valid for direct-on-line motor starting
❗ Not applicable: Star-delta starters, partidas suaves, inverter output terminals, Motores CC, resistive heating loads, heavy-duty reversing mechanisms.
Etapa 6: Configure accessories based on control scheme
- Local direct start (no PLC): Use MPCB alone with built-in pushbuttons
- Remote PLC control: MPCB only for isolation & proteção, paired with contactors; add GVAN auxiliary contacts (1NÃO+1NC) for running/fault feedback; add GVAX alarm contacts to separate overload trip from short-circuit trip
Optional extras: Shunt trip GVAD10, undervoltage trip GVAD01, interconnection busbar GV2AF3
Etapa 7: Exclude unsuitable applications
❌ Inverter output side
❌ DC motors
❌ Resistive loads (aquecedores, iluminação)
❌ Frequent forward/reverse operations (prone to false tripping; use separate thermal relays)
❌ Outdoor / corrosivo / dusty environments (must install inside an IP-rated enclosure)
Resumo de seleção rápida
- Read motor rated current from nameplate (primary data; power is only reference)
- Pick a GV2 model whose current range covers In, keep In away from the upper limit
- Select operation: Push-button GV2ME / Rotary knob GV2P
- Select terminals: Screw C / Primavera 3
- Check short-circuit current to confirm breaking capacity is adequate
- Add auxiliary contacts / trip contacts according to control requirements
Exemplo prático
Motor: 3-fase 400V, 1.5kW, rated current = 3.0A
Current range match: 2.5~4A → GV2ME08C
Set dial to 3.0A
Cabinet local operation without door handle → Push-button type
→ Final model: GV2-ME08C