Definição de código de modelo
Breakdown of NSYCVF165M230PF
| Segmento de código | Significado | Descrição |
| NSY | Prefixo da série do produto | General mark for Schneider ClimaSys cabinet cooling products |
| CV | Subsérie | ClimaSys CV series standard cabinet filter fan |
| F | Tipo de produto | Fã |
| 165 | Air flow rate | Rated airflow 165m鲁/h at 50Hz, 193m鲁/h at 60Hz |
| M | Tipo de montagem | Side mounting on cabinet |
| 230 | Tensão nominal | 230V e |
| P | Protection configuration | Equipped with pre-filter |
| F | Air outlet configuration | Fitted with front grille |
- Parâmetros de especificação principal
| Categoria | Technical Index | Observações |
| Parâmetros Básicos | ||
| Tipo de produto | Cabinet Filter Fan | ClimaSys CV series, IP54 protection |
| Air Flow | 165m³/h (50Hz) / 193m³/h (60Hz) | Measured with standard G2 filter |
| Faixa de tensão | 175~253V AC | Compatible with most 230V power grids worldwide |
| Tensão nominal | 230V 50/60Hz | Dual frequency compatibility |
| Parâmetros Elétricos | ||
| Poder | 16.3C (50Hz) / 14.3C (60Hz) | High energy efficiency |
| Atual | 0.12UM (50Hz) / 0.94UM (60Hz) | Low power consumption design |
| Conexão | Faston terminal + power cable | Fácil instalação |
| Physical Parameters | ||
| External Dimension | 268×248×104mm | Altura×Largura×Profundidade |
| Cutout Size | 223×223mm | Standard cabinet mounting hole |
| Material | Air outlet grille: ASA+PC thermoplastic | Anti-aging, grey RAL 7035 |
| Peso | 1.14kg | Stable installation, low resonance |
| Parâmetros de desempenho | ||
| Classe de Proteção | IP54 | Dustproof and splashproof, suitable for outdoor cabinets |
| Bearing Type | Rolamento de esferas | Longa vida útil, baixo ruído |
| Nível de ruído | 50~51dB | Quiet operation, applicable near office areas |
| Max Static Pressure | 50Pa (0m³/h) | Resists certain air resistance |
| Parâmetros Ambientais | ||
| Temperatura operacional | -20℃~60℃ | Ampla faixa de temperatura para ambientes agressivos |
| Temperatura de armazenamento | -40℃~70℃ | Reliable transportation and storage |
| Certificação | REACH, RoHS | Compliant with environmental standards |
- Full Series Model List
| Modelo | Air Flow(m³/h) | Tensão | Configuração | Cutout Size(milímetros) | External Size(milímetros) |
| NSYCVF38M230PF | 39 | 230V e | Grille + Filtro | 117×117 | 137×137×85 |
| NSYCVF54M230PF | 54 | 230V e | Grille + Filtro | 148×148 | 170×170×92 |
| NSYCVF85M230PF | 85 | 230V e | Grille + Filtro | 170×170 | 190×190×95 |
| NSYCVF165M115PF | 165/193 | 115V e | Grille + Filtro | 223×223 | 268×248×104 |
| NSYCVF165M230PF | 165/193 | 230V e | Grille + Filtro | 223×223 | 268×248×104 |
| NSYCVF165M24DPF | 165/193 | 24Em DC | Grille + Filtro | 223×223 | 268×248×104 |
| NSYCVF300M230PF | 300/350 | 230V e | Grille + Filtro | 262×262 | 300×300×110 |
| NSYCVF550M230PF | 550/650 | 230V e | Grille + Filtro | 336×336 | 380×380×120 |
| NSYCVF850M230PF | 838/980 | 230V e | Grille + Filtro | 400×400 | 450×450×130 |
| NSYCVF850M400PF | 838/980 | 400V e | Grille + Filtro | 400×400 | 450×450×130 |
- Cross-brand Replacement Comparison
| Marca | Modelo | Air Flow(m³/h) | Tensão | Classe de Proteção | Cutout Size(milímetros) | Vantagens de substituição |
| Rittal | 3239200 | 74/87 | 230V e | IP54 | 148×148 | Tool-free quick installation |
| Rittal | 3241700 | 160/190 | 230V e | IP54 | 223×223 | High-efficiency energy saving series |
| Stego | FK 66230 | 165/193 | 230V e | IP54 | 223×223 | Integrated temperature control, intelligent start-stop |
| Pfannenberg | 1041230 | 160/190 | 230V e | IP54 | 223×223 | Long filter service life, low maintenance frequency |
| RS PRO | 130-853 | 165/193 | 115V e | IP54 | 223×223 | Econômico, sufficient stock |
- Solução de problemas de falhas comuns & Manutenção
| Fenômeno de falha | Possíveis causas | Inspection Steps | Maintenance Solution |
| Fan not running | 1. Power disconnected | 1. Test power voltage | 1. Reconnect power supply |
| 2. Motor burnout | 2. Check motor winding resistance | 2. Replace identical motor | |
| 3. Stuck bearing | 3. Manually rotate fan blade | 3. Clean and lubricate bearing | |
| 4. Control circuit failure | 4. Inspect loose Faston connector | 4. Reconnect or replace connector | |
| Reduced airflow | 1. Clogged filter | 1. Check filter blockage | 1. Clean or replace G2 filter |
| 2. Dust accumulated on blades | 2. Inspect blade cleanliness | 2. Clean blades with soft brush | |
| 3. Subtensão | 3. Measure operating voltage | 3. Adjust voltage to rated value | |
| 4. Rotação reversa | 4. Verify mounting direction | 4. Reinstall fan outward air discharge | |
| Ruído anormal | 1. Worn bearing | 1. Locate noise source | 1. Replace bearing or whole fan |
| 2. Unbalanced fan blade | 2. Check blade deformation and attachments | 2. Correct balance and clear debris | |
| 3. Loose mounting | 3. Tighten mounting screws | 3. Fasten all screws | |
| 4. Vibration resonance | 4. Observe cabinet vibration | 4. Add shock pad or adjust position | |
| Proteção contra sobrecorrente | 1. Motor short circuit | 1. Test insulation resistance | 1. Replace motor |
| 2. Excessive bearing friction | 2. Check bearing flexibility | 2. Lubricate or replace bearing | |
| 3. Sobretensão | 3. Measure operating voltage | 3. Restore normal voltage |
- Ambiente de aplicação & Casos da Indústria
Cenários Aplicáveis
- Automação Industrial: Cooling for PLC, inverter and servo drive cabinets
- Sistema de energia: Heat dissipation for outdoor ring main units, box substations and charging pile control boxes
- Telecommunication: Ventilation for base station cabinets, optical distribution boxes and data center server cabinets
- Trânsito Ferroviário: Temperature control for signal boxes and converter cabinets
- Nova Energia: Cooling for photovoltaic inverters and energy storage control cabinets
Non-recommended Scenarios
- Corrosive atmosphere such as chemical and marine environment (anti-corrosion model required)
- Heavy dust sites like mines and cement plants (extra pre-filter needed)
- Submerged or long-term rain exposure (IP54 only splash-proof)
- Fully sealed space without air inlet circulation
Casos Típicos
Automobile Factory: Installed on welding robot cabinets, failure rate reduced by 70% against high temperature
Power Grid Company: Eliminated switch misoperation, equipment service life extended 3 vezes
Centro de dados: Hierarchical cooling with air conditioner, energy consumption cut by 20%
- Dicas de seleção & Avoidance Guide
Quick Calculation Rule
- Airflow demand = Cabinet volume × (8~10) m³/h, suitable for 16~20m³ cabinet
- Voltage selection: 230V for general industry, 115V for North America, 24V for DC system
- Mounting mark: M=side, MF=top, FB=bottom
Operation Warnings
- Inspect and replace G2 filter every 3 months to avoid airflow drop and motor overload
- Keep air outlet outward and match air inlet for effective ventilation
- Adopt cabinet air conditioner when external temperature is 5℃ higher than internal temperature
- Restrict voltage fluctuation within ±10% to guarantee service life
- Confirm UL, CE and other certifications for export use
- Order Information
Modelo: NSYCVF165M230PF
Pedido nº.: NSYCVF165M230PF (Global unified)
Conteúdo do pacote: 1 axial fan motor, 1 cutting template, 1 pre-filter, 1 air outlet grille, 1 power cable, 2 protective grilles