Siemens 3RB2056-1FC2 Electronic Overload Relay

Status: Discontinued by original manufacturer, Class 10E, S6 frame, electronic motor protection relay Basic Specifications Order No.: 3RB2056-1FC2 Current setting range: 50 … 200 A Frame size: S6 (compatible with S6 contactors such as 3RT1056) Classe de viagem: Class 10E (fixo, não ajustável) Matched motor power at 400V 50Hz: 30~90 kW Main circuit connection: Busbar connection Auxiliary ...

  • Detalhes do produto

Status: Discontinued by original manufacturer, Class 10E, S6 frame, electronic motor protection relay

Especificações básicas

Pedido nº.: 3RB2056-1FC2

Current setting range: 50 … 200 UM

Tamanho do quadro: S6 (compatible with S6 contactors such as 3RT1056)

Classe de viagem: Class 10E (fixo, não ajustável)

Matched motor power at 400V 50Hz: 30~90 kW

Conexão do circuito principal: Conexão de barramento

Circuito auxiliar: Terminais de parafuso, auxiliary contacts 1NO + 1NC

Modo de reinicialização: Manual / automatic reset selectable

Montagem: Direct snap-on to S6 contactor or standalone mounting

Classe de proteção: IP20

Tensão nominal de isolamento: 1000V e, impulse withstand voltage 8kV

Faixa de frequência: 50/60Hz

Temperatura operacional: -25℃ ~ +60 ℃

Funções de proteção

Tipo eletrônico, different from bimetallic thermal relays:

Inverse-time overload protection

Perda de fase / proteção de desequilíbrio de fase

Motor stall protection

Built-in test button for loop testing

Distinção de modelo (Easily Confused Models in the Same Series)

3RB2056-1FC2: Class10E, descontinuado

3RB2056-2FC2 / 2FX2: Class20E, heavy-duty start version, most common replacement

Replacement Selection Suggestions

  1. Substituição direta com a mesma especificação: 3RB2056-2FC2 (Class20E); if Class10 is strictly required, prioritize the new generation 3RB3056 series electronic relé de sobrecarga
  2. Matching contactor: Siemens 3RT1056 (S6)
  3. Alternativa doméstica: Domestic electronic thermal relay with 50-200A, S6 footprint, 1NÃO+1NC, Aula10

Notas principais

3RB2056-1FC2 is an older imported 3RB2 model, discontinued by Siemens. Stock units are only available from inventory. New projects are generally recommended to adopt the new 3RB30 series.

3RB2056-1FC2 (S6 / 50-200UM / Class10E) Fiação & Manual de Comissionamento

Observações: Electronic type requiring auxiliary power supply A1/A2; main circuit adopts busbar connection (S6, matched with 3RT1056 contactor), not through-core type; Contatos: 95-96 (NC normalmente fechado), 97-98 (NÃO normalmente aberto), 1NÃO+1NC

  1. Definição de terminal

A1, A2: Auxiliary power supply terminals (AC/DC 24V or 110~240V, depending on sub-version). The 3RB20 draws power here. The electronic relay must be powered up for phase loss/unbalance protection to work.

95, 96: Contato normalmente fechado (NC) → Standard usage: wired in series into the contactor coil control circuit to cut off and stop the motor on overload trip

97, 98: Contato normalmente aberto (NÃO) → For fault alarm, PLC fault input or fault indicator light

Circuito principal: Upper busbar connects to contactor output, lower busbar connects to motor (L1/L2/L3 straight through. The thermal relay does not break the main circuit, only the control circuit)

Painel frontal: Current adjustment knob (50-200UM), M/A DIP switch (manual / auto reset), TEST test button, RESET reset button

  1. Diagrama de fiação padrão (Direct-On-Line Start Circuit)

1) Circuito Principal

3-phase power supply → Circuit breaker → 3RT1056 (S6 contactor) → 3RB2056-1FC2 busbar input → 3RB busbar output → Motor

2) Circuito Auxiliar

  1. A1/A2: Connected to control power supply (to power the electronic board of thermal relay)
  2. Contactor coil circuit: Power supply → Stop button → Start button (travamento automático) → 95-96 (NC) → Contactor coil → Power supply neutral
  3. Fault signal: 97-98 parallel to fault indicator or PLC DI point

Importante: 95-96 is the protection series contact, opens on trip; 97-98 closes synchronously to output fault signal

3) Montagem autônoma (Not clipped onto contactor)

Main circuit remains busbar connection, auxiliary terminals unchanged, fixed separately on backplate. A1/A2 must be powered.

Observação: 3RB20 has no A3/A4 remote reset terminals (remote reset is available on 3RB21 only). Only local panel reset or automatic reset is supported.

  1. M / A Reset DIP Switch

M = Manual Reset (Recommended for safety circuits) : After overload / phase loss trip, the RESET button on panel must be pressed to reset; no automatic restart

A = Auto Reset : Automatically resets after approx. 3 minutes delay after tripping, suitable for low-risk fans with unattended operation; A mode is strictly prohibited for equipment with entanglement hazard

  1. Complete Commissioning Procedure (Before Power-on → No-load → On-load)

Etapa 1: Pre-power Check (Desligar)

  1. Check rated current on motor nameplate, set the current knob to motor rated current (Ou seja)

Exemplo: Motor rated 88A → Align knob at 88A; do not set directly to 200A

Range 50-200A, Class10E fixed and non-adjustable

  1. Set M/A DIP switch per process requirement (M is default)
  2. Check tightening torque of busbar bolts, no loose 3-phase busbar connections; secure auxiliary terminal screws
  3. Teste de continuidade com multímetro: 95-96 conducting normally; 97-98 open normally

Etapa 2: Power on Auxiliary Supply and Test Functions (No High Voltage on Main Circuit!)

  1. Supply power only to A1/A2, no 380V on main circuit
  2. Imprensa [TESTE] botão:

95-96 abre, 97-98 closes → Contact action normal

Release TEST and press RESET to restore normal state

TEST only simulates contact action, does not simulate real overload current, it is a loop verification

  1. Redefinir teste: For M mode, RESET button must be pressed to restore after test; for A mode wait for auto reset (M mode is used during commissioning generally)

Etapa 3: Energize Main Circuit and No-load Test Run

  1. Close main circuit, start motor for no-load operation
  2. Measure 3-phase no-load current with clamp meter and record; confirm no severe unbalance
  3. If 3-phase current deviation>20%, verifique o motor, wiring and power supply first. The electronic relay will trip for phase loss/unbalance protection directly

Etapa 4: On-load Operation and Current Verification (Crítico)

  1. After motor runs stably at rated load, measure 3-phase operating current with clamp meter
  2. If steady operating current is 70A, set the knob to 70A;
  3. Pay attention not to run below the lower limit of the range if starting inrush current is high and rated current is near 50A lower limit;

Definition of Class10E: Trips within 10s at 7.2 vezes a corrente nominal, suitable for standard motors; not suitable for heavy-duty long-start applications (use 3RB2056-2FC2 Class20E for heavy duty)

Etapa 5: Fault Simulation and Acceptance

  1. Cut off one phase (power off before operation), energize and verify: thermal relay triggers phase loss protection, 95-96 opens to stop motor
  2. Registro: setting current, modo de reinicialização, trip logs
  3. Acceptance criteria: Sobrecarga, phase loss and phase unbalance trigger reliable tripping; self-locking circuit and fault signal output normal
  4. Quick Fault Troubleshooting
  5. Nenhuma viagem por sobrecarga: ① A1/A2 no power supply (no supply = no protection for electronic relay); ② setting current too high; ③ TEST button failure
  6. Trip immediately upon energizing: Desequilíbrio trifásico grave, curto-circuito no enrolamento do motor, setting current too low
  7. Cannot auto reset after trip: DIP switch at M (normal); if switch at A and still no auto reset, device aging
  8. Normal no-load, trips frequently under load: Sobrecarga do motor, bearing jam, large supply voltage drop, setting current too low
  9. Important Safety Reminders

This is an electronic thermal relay. Protection fails if A1/A2 power is lost! This differs fundamentally from traditional bimetallic 3RU thermal relays

S6 busbar requires strict tightening torque. Poor contact causes heating and false tripping

Automatic reset mode A is forbidden for safety-critical equipment (transportadores, misturadores)

  1. Matching Replacement Reference

Same frame Class10: New generation 3RB3056

Same frame Class20: 3RB2056-2FC2 (heavy-duty start)

3RB2056-1FC2 (S6 / 50-200UM / Class10E) Falhas & Soluções

Pre-reminder: Electronic relay loses all protection without A1/A2 supply, different from traditional bimetallic 3RU. No fault indicator LEDs. Troubleshooting relies on TEST button, multimeter and clamp meter.

Falta 1: No trip when motor is overloaded (Protection failure)

Sintoma: Motor overheats obviously, 95-96 contacts of thermal relay do not act and motor does not stop

Causa 1: A1/A2 auxiliary supply lost, wrong voltage or loose terminals (Most frequent)

Remédio: Measure A1/A2 voltage; verify supply specification; tighten auxiliary terminals. Continuous power supply is required for current detection

Causa 2: Current knob set far higher than motor rated current

Remédio: Reset to motor rated current per nameplate, verify with clamp meter under operation

Causa 3: Loose main busbar bolts, poor contact and abnormal internal sampling

Remédio: Desligar, tighten 3-phase busbar to S6 specified torque; check busbar for oxidation and discoloration from heat

Causa 4: Internal sampling board damaged or component aging (High risk for discontinued stock units)

Remédio: Run TEST test. If 95-96 does not switch when TEST pressed → relay damaged, substitua diretamente

Falta 2: Normal no-load, frequent tripping under load (Falso disparo)

Sintoma: Starts fine without load, trips shortly after loading, 95-96 abre

Causa 1: Configuração de corrente muito baixa; Class10E trips fast, not fit for heavy-duty long-start motors

Remédio: Verifique a corrente nominal do motor; use 3RB2056-2FC2 (Class20E) for heavy starting applications

Causa 2: 3-phase current unbalance, perda de fase, burnt contactor contacts

Remédio: Measure 3-phase currents with clamp meter; trip triggered if deviation>20%; check upstream contactor and power supply

Causa 3: Loose busbar generates heat and sampling drift causes false overload judgement

Remédio: Pare o equipamento, check busbar temperature and oxidation, reapertar

Causa 4: Ambient temperature over 60℃, má ventilação do gabinete

Remédio: Melhorar o resfriamento; reserve current margin for high-temperature environments

Falta 3: Immediate trip when energizing / começando (Trip on switch-on)

Sintoma: Thermal relay trips as soon as main circuit is energized before motor rotates

Causa 1: Curto-circuito no enrolamento do motor, insulation failure, mechanical seizure or stall

Remédio: Disconnect motor, teste de isolamento com megômetro; check bearing by hand rotation

Causa 2: Interference on A1/A2 supply, large control voltage fluctuation

Remédio: Add filter on control supply; separate supply from variable frequency drives and large contactors

Causa 3: DIP switch at A auto reset, fault still present and re-trips immediately after closing

Remédio: Switch to M manual reset, eliminate root fault before re-energizing, avoid repeated trial switching

Falta 4: Cannot reset after tripping (RESET button ineffective)

Sintoma: After protection triggers, 95-96 cannot restore conduction even after pressing RESET

Causa 1: Root fault persists (sobrecarga contínua, perda de fase, convulsão) so protection latches

Remédio: Cut main circuit, eliminate load fault then reset

Causa 2: DIP switch at M manual reset but A1/A2 supply drops

Remédio: Reset only with stable A1/A2 supply; reset not possible when power is lost

Causa 3: Atolamento mecânico interno, contact welding or electronic board latch-up

Remédio: Power off and rest for 5 minutes and retry; if still fails TEST test, substituir unidade

Suplemento: 3RB20 has no remote reset terminals. Remote reset is available only on 3RB21. Do not add external remote reset wiring.

Falta 5: Auto reset mode A fails to reset automatically

Sintoma: Set to auto reset, no recovery after long waiting post trip

Causa 1: A1/A2 auxiliary supply interrupted, auto-reset timer stops when power is lost

Remédio: Keep A1/A2 continuously powered

Causa 2: Fault remains active (persistent overload, perda de fase), protection stays latched and will not reset

Remédio: Root fault must be cleared first

Causa 3: Unit aging, auto-reset timing circuit failure

Remédio: Change to M manual reset; replace if auto reset is mandatory

Falta 6: TEST button no response (Contacts do not switch on TEST press)

Sintoma: Only A1/A2 powered, 95-96 remains closed and 97-98 stays open when TEST pressed

Causa 1: A1/A2 no power supply or mismatched voltage

Remédio: Measure auxiliary supply voltage

Causa 2: TEST button mechanically jammed or internal electronic board damaged

Remédio: Power off and clean; replace relay if still invalid

TEST only verifies auxiliary contact loop, does not simulate real overload current. Passing TEST only confirms contact loop works, not current sampling.

Falta 7: No fault signal output from 97-98 after trip (PLC no fault feedback)

Sintoma: Motor stops after trip but NO fault signal output

Causa 1: Loose wiring or broken wire on 97-98 terminais

Remédio: Measure continuity of 97-98 under tripped state

Causa 2: Insufficient contact rating, voltage drop when driving low-power PLC DI

Remédio: Confirm contact load rating; add intermediate relay if required

Causa 3: Internal auxiliary contact burnt and damaged

Remédio: Run TEST test; replace relay if 97-98 does not close

Falta 8: Random intermittent tripping during operation

Sintoma: Current reading normal, trips irregularly

Causa 1: Intermittent loose connection on busbar or auxiliary terminals (vibração, thermal expansion)

Remédio: Retighten all terminals and check cabinet vibration

Causa 2: Control supply fluctuation and harmonic interference (common with VFD circuits)

Remédio: Add isolation on control loop; this model is not recommended directly on VFD output, dedicated motor protection relay preferred

Causa 3: Unit aging, sampling circuit drift (Common for old discontinued stock)

Remédio: Substitua o relé, prefer 3RB30 new generation

Falta 9: Relay latches to trip immediately after auxiliary power on, motor not energized

Sintoma: 380V main circuit not powered, 95-96 opens right after A1/A2 supply is switched on

Causa: Internal electronic board failure, damaged sampling circuit

Remédio: Replace overload relay

Standard Field Troubleshooting Flow

  1. Confirm A1/A2 auxiliary power supply normal (First check for electronic relay)
  2. Trigger TEST button to verify contact operation
  3. Measure 3-phase operating current with clamp meter and cross-check setting value
  4. Inspect 3-phase voltage, contactor contacts, motor insulation and busbar tightness
  5. Confirm M/A reset mode matches process requirements
  6. If all above checks pass and fault persists → Relay internal damage

Critical Pitfall Notes

  1. Not recommended for direct use on VFD output side; harmonics cause false detection
  2. Auto reset mode A must not be used long-term on safety equipment (transportadores, misturadores)
  3. Este modelo foi descontinuado; inventory spares suffer higher electronic board aging risk than newer 3RB30 series
  4. S6 busbar loose torque causes continuous heating and sampling drift false tripping

SIRIUS 3RB2 Electronic Overload Relay Series Overview

Series includes: 3RB20 (Versão padrão, no remote reset), 3RB21 (Enhanced version with remote reset terminals); All discontinued by OEM, only spare stock available. Electronic type requiring A1/A2 auxiliary supply; Proteção: sobrecarga, perda de fase, desequilíbrio de fase, parar; Standard contacts 1NO+1NC; Conexão do barramento do circuito principal; Frame sizes S6 / S10 / T12; Current range 50~820A

Definição de código de modelo (3RB2 □ □□ □□□)

3RB20: Versão básica, no remote reset (3RB2056-1FC2 belongs here)

3RB21: Versão aprimorada, with remote reset terminals A3/A4

5th-6th digits: 56=S6 (50-200UM); 66=S10/S12 (55-630UM)

Prefixo 1 = Class10E; prefixo 2 = Class20E (heavy-duty start)

Sufixo:

FC2: Terminais de parafuso, direct snap-on to contactor

FF2: Montagem autônoma, terminais de parafuso

FW2: Terminais de mola, snap-on

FX2: Terminais de mola + standalone mounting

GC2 / GF2 / MC2 / MF2: S10/S12 specifications

  1. 3RB20 Series List (No Remote Reset)
Número do pedido.Faixa AtualQuadroClasse de viagemContator correspondenteObservações
3RB2056-1FC250–200AS6Class10E3RT1056Snap-on, terminais de parafuso, main subject, descontinuado
3RB2056-1FF250–200AS6Class10E3RT1056Autônomo, terminais de parafuso
3RB2056-1FW250–200AS6Class10E3RT1056Snap-on, terminais de mola
3RB2056-1FX250–200AS6Class10E3RT1056Autônomo, terminais de mola
3RB2056-2FC250–200AS6Class20E3RT1056Heavy-duty snap-on, terminais de parafuso, popular replacement
3RB2056-2FF250–200AS6Class20E3RT1056Heavy-duty standalone, terminais de parafuso
3RB2056-2FW250–200AS6Class20E3RT1056Heavy-duty snap-on, terminais de mola
3RB2056-2FX250–200AS6Class20E3RT1056Heavy-duty standalone, terminais de mola
3RB2066-1GC255–250AS10Class10E3RT1065Snap-on, terminais de parafuso
3RB2066-1GF255–250AS10Class10E3RT1065Autônomo, terminais de parafuso
3RB2066-1MC2160–630AT12Class10E3RT1066Snap-on, terminais de parafuso
3RB2066-1MF2160–630AT12Class10E3RT1066Autônomo, terminais de parafuso
3RB2066-2GC255–250AS10Class20E3RT1065Heavy-duty snap-on, terminais de parafuso
3RB2066-2GF255–250AS10Class20E3RT1065Heavy-duty standalone, terminais de parafuso
3RB2066-2MC2160–630AT12Class20E3RT1066Heavy-duty snap-on, terminais de parafuso
3RB2066-2MF2160–630AT12Class20E3RT1066Heavy-duty standalone, terminais de parafuso
3RB2011 + 3UF18630–820AT14Class10E3TF68/3TF69CT combination solution
  1. 3RB21 Series List (With Remote Reset A3/A4)

Suitable for PLC remote reset; protection functions and current ranges same as 3RB20

| 3RB2156-1FC2 | 50-200UM | S6 | Class10E | Remote reset, snap-on, terminais de parafuso |

| 3RB2156-1FF2 | 50-200UM | S6 | Class10E | Remote reset, autônomo, terminais de parafuso |

| 3RB2156-2FC2 | 50-200UM | S6 | Class20E | Serviço pesado + reinicialização remota |

| 3RB2166-1GC2 | 55-250UM | S10 | Class10E | S10 remote reset |

| 3RB2166-1MC2 | 160-630UM | T12 | Class10E | S12 remote reset |

| 3RB2166-2GC2 | 55-250UM | S10 | Class20E | S10 heavy duty + reinicialização remota |

| 3RB2166-2MC2 | 160-630UM | T12 | Class20E | S12 heavy duty + reinicialização remota |

| 3RB2111 + 3UF18 | 630-820UM | T14 | Class10E | CT combination, reinicialização remota |

 

  1. Common Series Parameters
  2. Auxiliary supply: A1/A2, AC/DC 24V or AC110~240V (depends on sub-version). Protection fails when supply is lost
  3. Contatos auxiliares: 95-96 (NC), 97-98 (NÃO), 1NÃO+1NC, 5Uma classificação
  4. Reiniciar: M/A DIP switch (manual / auto reset); 3RB21 adds A3/A4 remote reset
  5. Classe de proteção: IP20; Insulation voltage 1000V AC, impulse withstand voltage 8kV; Operating temperature -25~+60℃
  6. Circuito principal: Conexão de barramento, not through-core CT type
  7. Aplicativo: Standard 3-phase asynchronous motors; Not recommended directly on VFD output; harmonics cause false tripping
  8. New Generation Replacement Series (Recomendado para novos projetos)

S6 50-200A replacement: 3RB3056 (nova geração, melhor estabilidade, active supply)

S10/S12 high-current: 3RB3066 for equivalent replacement

  1. Guia de seleção rápida

No remote reset required → 3RB20

PLC remote reset required → 3RB21

Ventiladores padrão, bombas, smooth start → Class10E (prefixo 1)

Transportadores de correia, trituradores, heavy-duty long start → Class20E (prefixo 2)

Snap-on mounting with contactor → FC2 / GC2 / MC2

Separate backplate mounting → FF2 / GF2 / MF2