Status: Discontinued by original manufacturer, Class 10E, S6 frame, electronic motor protection relay
Especificações básicas
Pedido nº.: 3RB2056-1FC2
Current setting range: 50 … 200 UM
Tamanho do quadro: S6 (compatible with S6 contactors such as 3RT1056)
Classe de viagem: Class 10E (fixo, não ajustável)
Matched motor power at 400V 50Hz: 30~90 kW
Conexão do circuito principal: Conexão de barramento
Circuito auxiliar: Terminais de parafuso, auxiliary contacts 1NO + 1NC
Modo de reinicialização: Manual / automatic reset selectable
Montagem: Direct snap-on to S6 contactor or standalone mounting
Classe de proteção: IP20
Tensão nominal de isolamento: 1000V e, impulse withstand voltage 8kV
Faixa de frequência: 50/60Hz
Temperatura operacional: -25℃ ~ +60 ℃
Funções de proteção
Tipo eletrônico, different from bimetallic thermal relays:
Inverse-time overload protection
Perda de fase / proteção de desequilíbrio de fase
Motor stall protection
Built-in test button for loop testing
Distinção de modelo (Easily Confused Models in the Same Series)
3RB2056-1FC2: Class10E, descontinuado
3RB2056-2FC2 / 2FX2: Class20E, heavy-duty start version, most common replacement
Replacement Selection Suggestions
- Substituição direta com a mesma especificação: 3RB2056-2FC2 (Class20E); if Class10 is strictly required, prioritize the new generation 3RB3056 series electronic relé de sobrecarga
- Matching contactor: Siemens 3RT1056 (S6)
- Alternativa doméstica: Domestic electronic thermal relay with 50-200A, S6 footprint, 1NÃO+1NC, Aula10
Notas principais
3RB2056-1FC2 is an older imported 3RB2 model, discontinued by Siemens. Stock units are only available from inventory. New projects are generally recommended to adopt the new 3RB30 series.
3RB2056-1FC2 (S6 / 50-200UM / Class10E) Fiação & Manual de Comissionamento
Observações: Electronic type requiring auxiliary power supply A1/A2; main circuit adopts busbar connection (S6, matched with 3RT1056 contactor), not through-core type; Contatos: 95-96 (NC normalmente fechado), 97-98 (NÃO normalmente aberto), 1NÃO+1NC
- Definição de terminal
A1, A2: Auxiliary power supply terminals (AC/DC 24V or 110~240V, depending on sub-version). The 3RB20 draws power here. The electronic relay must be powered up for phase loss/unbalance protection to work.
95, 96: Contato normalmente fechado (NC) → Standard usage: wired in series into the contactor coil control circuit to cut off and stop the motor on overload trip
97, 98: Contato normalmente aberto (NÃO) → For fault alarm, PLC fault input or fault indicator light
Circuito principal: Upper busbar connects to contactor output, lower busbar connects to motor (L1/L2/L3 straight through. The thermal relay does not break the main circuit, only the control circuit)
Painel frontal: Current adjustment knob (50-200UM), M/A DIP switch (manual / auto reset), TEST test button, RESET reset button
- Diagrama de fiação padrão (Direct-On-Line Start Circuit)
1) Circuito Principal
3-phase power supply → Circuit breaker → 3RT1056 (S6 contactor) → 3RB2056-1FC2 busbar input → 3RB busbar output → Motor
2) Circuito Auxiliar
- A1/A2: Connected to control power supply (to power the electronic board of thermal relay)
- Contactor coil circuit: Power supply → Stop button → Start button (travamento automático) → 95-96 (NC) → Contactor coil → Power supply neutral
- Fault signal: 97-98 parallel to fault indicator or PLC DI point
Importante: 95-96 is the protection series contact, opens on trip; 97-98 closes synchronously to output fault signal
3) Montagem autônoma (Not clipped onto contactor)
Main circuit remains busbar connection, auxiliary terminals unchanged, fixed separately on backplate. A1/A2 must be powered.
Observação: 3RB20 has no A3/A4 remote reset terminals (remote reset is available on 3RB21 only). Only local panel reset or automatic reset is supported.
- M / A Reset DIP Switch
M = Manual Reset (Recommended for safety circuits) : After overload / phase loss trip, the RESET button on panel must be pressed to reset; no automatic restart
A = Auto Reset : Automatically resets after approx. 3 minutes delay after tripping, suitable for low-risk fans with unattended operation; A mode is strictly prohibited for equipment with entanglement hazard
- Complete Commissioning Procedure (Before Power-on → No-load → On-load)
Etapa 1: Pre-power Check (Desligar)
- Check rated current on motor nameplate, set the current knob to motor rated current (Ou seja)
Exemplo: Motor rated 88A → Align knob at 88A; do not set directly to 200A
Range 50-200A, Class10E fixed and non-adjustable
- Set M/A DIP switch per process requirement (M is default)
- Check tightening torque of busbar bolts, no loose 3-phase busbar connections; secure auxiliary terminal screws
- Teste de continuidade com multímetro: 95-96 conducting normally; 97-98 open normally
Etapa 2: Power on Auxiliary Supply and Test Functions (No High Voltage on Main Circuit!)
- Supply power only to A1/A2, no 380V on main circuit
- Imprensa [TESTE] botão:
95-96 abre, 97-98 closes → Contact action normal
Release TEST and press RESET to restore normal state
TEST only simulates contact action, does not simulate real overload current, it is a loop verification
- Redefinir teste: For M mode, RESET button must be pressed to restore after test; for A mode wait for auto reset (M mode is used during commissioning generally)
Etapa 3: Energize Main Circuit and No-load Test Run
- Close main circuit, start motor for no-load operation
- Measure 3-phase no-load current with clamp meter and record; confirm no severe unbalance
- If 3-phase current deviation>20%, verifique o motor, wiring and power supply first. The electronic relay will trip for phase loss/unbalance protection directly
Etapa 4: On-load Operation and Current Verification (Crítico)
- After motor runs stably at rated load, measure 3-phase operating current with clamp meter
- If steady operating current is 70A, set the knob to 70A;
- Pay attention not to run below the lower limit of the range if starting inrush current is high and rated current is near 50A lower limit;
Definition of Class10E: Trips within 10s at 7.2 vezes a corrente nominal, suitable for standard motors; not suitable for heavy-duty long-start applications (use 3RB2056-2FC2 Class20E for heavy duty)
Etapa 5: Fault Simulation and Acceptance
- Cut off one phase (power off before operation), energize and verify: thermal relay triggers phase loss protection, 95-96 opens to stop motor
- Registro: setting current, modo de reinicialização, trip logs
- Acceptance criteria: Sobrecarga, phase loss and phase unbalance trigger reliable tripping; self-locking circuit and fault signal output normal
- Quick Fault Troubleshooting
- Nenhuma viagem por sobrecarga: ① A1/A2 no power supply (no supply = no protection for electronic relay); ② setting current too high; ③ TEST button failure
- Trip immediately upon energizing: Desequilíbrio trifásico grave, curto-circuito no enrolamento do motor, setting current too low
- Cannot auto reset after trip: DIP switch at M (normal); if switch at A and still no auto reset, device aging
- Normal no-load, trips frequently under load: Sobrecarga do motor, bearing jam, large supply voltage drop, setting current too low
- Important Safety Reminders
This is an electronic thermal relay. Protection fails if A1/A2 power is lost! This differs fundamentally from traditional bimetallic 3RU thermal relays
S6 busbar requires strict tightening torque. Poor contact causes heating and false tripping
Automatic reset mode A is forbidden for safety-critical equipment (transportadores, misturadores)
- Matching Replacement Reference
Same frame Class10: New generation 3RB3056
Same frame Class20: 3RB2056-2FC2 (heavy-duty start)
3RB2056-1FC2 (S6 / 50-200UM / Class10E) Falhas & Soluções
Pre-reminder: Electronic relay loses all protection without A1/A2 supply, different from traditional bimetallic 3RU. No fault indicator LEDs. Troubleshooting relies on TEST button, multimeter and clamp meter.
Falta 1: No trip when motor is overloaded (Protection failure)
Sintoma: Motor overheats obviously, 95-96 contacts of thermal relay do not act and motor does not stop
Causa 1: A1/A2 auxiliary supply lost, wrong voltage or loose terminals (Most frequent)
Remédio: Measure A1/A2 voltage; verify supply specification; tighten auxiliary terminals. Continuous power supply is required for current detection
Causa 2: Current knob set far higher than motor rated current
Remédio: Reset to motor rated current per nameplate, verify with clamp meter under operation
Causa 3: Loose main busbar bolts, poor contact and abnormal internal sampling
Remédio: Desligar, tighten 3-phase busbar to S6 specified torque; check busbar for oxidation and discoloration from heat
Causa 4: Internal sampling board damaged or component aging (High risk for discontinued stock units)
Remédio: Run TEST test. If 95-96 does not switch when TEST pressed → relay damaged, substitua diretamente
Falta 2: Normal no-load, frequent tripping under load (Falso disparo)
Sintoma: Starts fine without load, trips shortly after loading, 95-96 abre
Causa 1: Configuração de corrente muito baixa; Class10E trips fast, not fit for heavy-duty long-start motors
Remédio: Verifique a corrente nominal do motor; use 3RB2056-2FC2 (Class20E) for heavy starting applications
Causa 2: 3-phase current unbalance, perda de fase, burnt contactor contacts
Remédio: Measure 3-phase currents with clamp meter; trip triggered if deviation>20%; check upstream contactor and power supply
Causa 3: Loose busbar generates heat and sampling drift causes false overload judgement
Remédio: Pare o equipamento, check busbar temperature and oxidation, reapertar
Causa 4: Ambient temperature over 60℃, má ventilação do gabinete
Remédio: Melhorar o resfriamento; reserve current margin for high-temperature environments
Falta 3: Immediate trip when energizing / começando (Trip on switch-on)
Sintoma: Thermal relay trips as soon as main circuit is energized before motor rotates
Causa 1: Curto-circuito no enrolamento do motor, insulation failure, mechanical seizure or stall
Remédio: Disconnect motor, teste de isolamento com megômetro; check bearing by hand rotation
Causa 2: Interference on A1/A2 supply, large control voltage fluctuation
Remédio: Add filter on control supply; separate supply from variable frequency drives and large contactors
Causa 3: DIP switch at A auto reset, fault still present and re-trips immediately after closing
Remédio: Switch to M manual reset, eliminate root fault before re-energizing, avoid repeated trial switching
Falta 4: Cannot reset after tripping (RESET button ineffective)
Sintoma: After protection triggers, 95-96 cannot restore conduction even after pressing RESET
Causa 1: Root fault persists (sobrecarga contínua, perda de fase, convulsão) so protection latches
Remédio: Cut main circuit, eliminate load fault then reset
Causa 2: DIP switch at M manual reset but A1/A2 supply drops
Remédio: Reset only with stable A1/A2 supply; reset not possible when power is lost
Causa 3: Atolamento mecânico interno, contact welding or electronic board latch-up
Remédio: Power off and rest for 5 minutes and retry; if still fails TEST test, substituir unidade
Suplemento: 3RB20 has no remote reset terminals. Remote reset is available only on 3RB21. Do not add external remote reset wiring.
Falta 5: Auto reset mode A fails to reset automatically
Sintoma: Set to auto reset, no recovery after long waiting post trip
Causa 1: A1/A2 auxiliary supply interrupted, auto-reset timer stops when power is lost
Remédio: Keep A1/A2 continuously powered
Causa 2: Fault remains active (persistent overload, perda de fase), protection stays latched and will not reset
Remédio: Root fault must be cleared first
Causa 3: Unit aging, auto-reset timing circuit failure
Remédio: Change to M manual reset; replace if auto reset is mandatory
Falta 6: TEST button no response (Contacts do not switch on TEST press)
Sintoma: Only A1/A2 powered, 95-96 remains closed and 97-98 stays open when TEST pressed
Causa 1: A1/A2 no power supply or mismatched voltage
Remédio: Measure auxiliary supply voltage
Causa 2: TEST button mechanically jammed or internal electronic board damaged
Remédio: Power off and clean; replace relay if still invalid
TEST only verifies auxiliary contact loop, does not simulate real overload current. Passing TEST only confirms contact loop works, not current sampling.
Falta 7: No fault signal output from 97-98 after trip (PLC no fault feedback)
Sintoma: Motor stops after trip but NO fault signal output
Causa 1: Loose wiring or broken wire on 97-98 terminais
Remédio: Measure continuity of 97-98 under tripped state
Causa 2: Insufficient contact rating, voltage drop when driving low-power PLC DI
Remédio: Confirm contact load rating; add intermediate relay if required
Causa 3: Internal auxiliary contact burnt and damaged
Remédio: Run TEST test; replace relay if 97-98 does not close
Falta 8: Random intermittent tripping during operation
Sintoma: Current reading normal, trips irregularly
Causa 1: Intermittent loose connection on busbar or auxiliary terminals (vibração, thermal expansion)
Remédio: Retighten all terminals and check cabinet vibration
Causa 2: Control supply fluctuation and harmonic interference (common with VFD circuits)
Remédio: Add isolation on control loop; this model is not recommended directly on VFD output, dedicated motor protection relay preferred
Causa 3: Unit aging, sampling circuit drift (Common for old discontinued stock)
Remédio: Substitua o relé, prefer 3RB30 new generation
Falta 9: Relay latches to trip immediately after auxiliary power on, motor not energized
Sintoma: 380V main circuit not powered, 95-96 opens right after A1/A2 supply is switched on
Causa: Internal electronic board failure, damaged sampling circuit
Remédio: Replace overload relay
Standard Field Troubleshooting Flow
- Confirm A1/A2 auxiliary power supply normal (First check for electronic relay)
- Trigger TEST button to verify contact operation
- Measure 3-phase operating current with clamp meter and cross-check setting value
- Inspect 3-phase voltage, contactor contacts, motor insulation and busbar tightness
- Confirm M/A reset mode matches process requirements
- If all above checks pass and fault persists → Relay internal damage
Critical Pitfall Notes
- Not recommended for direct use on VFD output side; harmonics cause false detection
- Auto reset mode A must not be used long-term on safety equipment (transportadores, misturadores)
- Este modelo foi descontinuado; inventory spares suffer higher electronic board aging risk than newer 3RB30 series
- S6 busbar loose torque causes continuous heating and sampling drift false tripping
SIRIUS 3RB2 Electronic Overload Relay Series Overview
Series includes: 3RB20 (Versão padrão, no remote reset), 3RB21 (Enhanced version with remote reset terminals); All discontinued by OEM, only spare stock available. Electronic type requiring A1/A2 auxiliary supply; Proteção: sobrecarga, perda de fase, desequilíbrio de fase, parar; Standard contacts 1NO+1NC; Conexão do barramento do circuito principal; Frame sizes S6 / S10 / T12; Current range 50~820A
Definição de código de modelo (3RB2 □ □□ □□□)
3RB20: Versão básica, no remote reset (3RB2056-1FC2 belongs here)
3RB21: Versão aprimorada, with remote reset terminals A3/A4
5th-6th digits: 56=S6 (50-200UM); 66=S10/S12 (55-630UM)
Prefixo 1 = Class10E; prefixo 2 = Class20E (heavy-duty start)
Sufixo:
FC2: Terminais de parafuso, direct snap-on to contactor
FF2: Montagem autônoma, terminais de parafuso
FW2: Terminais de mola, snap-on
FX2: Terminais de mola + standalone mounting
GC2 / GF2 / MC2 / MF2: S10/S12 specifications
- 3RB20 Series List (No Remote Reset)
| Número do pedido. | Faixa Atual | Quadro | Classe de viagem | Contator correspondente | Observações |
| 3RB2056-1FC2 | 50–200A | S6 | Class10E | 3RT1056 | Snap-on, terminais de parafuso, main subject, descontinuado |
| 3RB2056-1FF2 | 50–200A | S6 | Class10E | 3RT1056 | Autônomo, terminais de parafuso |
| 3RB2056-1FW2 | 50–200A | S6 | Class10E | 3RT1056 | Snap-on, terminais de mola |
| 3RB2056-1FX2 | 50–200A | S6 | Class10E | 3RT1056 | Autônomo, terminais de mola |
| 3RB2056-2FC2 | 50–200A | S6 | Class20E | 3RT1056 | Heavy-duty snap-on, terminais de parafuso, popular replacement |
| 3RB2056-2FF2 | 50–200A | S6 | Class20E | 3RT1056 | Heavy-duty standalone, terminais de parafuso |
| 3RB2056-2FW2 | 50–200A | S6 | Class20E | 3RT1056 | Heavy-duty snap-on, terminais de mola |
| 3RB2056-2FX2 | 50–200A | S6 | Class20E | 3RT1056 | Heavy-duty standalone, terminais de mola |
| 3RB2066-1GC2 | 55–250A | S10 | Class10E | 3RT1065 | Snap-on, terminais de parafuso |
| 3RB2066-1GF2 | 55–250A | S10 | Class10E | 3RT1065 | Autônomo, terminais de parafuso |
| 3RB2066-1MC2 | 160–630A | T12 | Class10E | 3RT1066 | Snap-on, terminais de parafuso |
| 3RB2066-1MF2 | 160–630A | T12 | Class10E | 3RT1066 | Autônomo, terminais de parafuso |
| 3RB2066-2GC2 | 55–250A | S10 | Class20E | 3RT1065 | Heavy-duty snap-on, terminais de parafuso |
| 3RB2066-2GF2 | 55–250A | S10 | Class20E | 3RT1065 | Heavy-duty standalone, terminais de parafuso |
| 3RB2066-2MC2 | 160–630A | T12 | Class20E | 3RT1066 | Heavy-duty snap-on, terminais de parafuso |
| 3RB2066-2MF2 | 160–630A | T12 | Class20E | 3RT1066 | Heavy-duty standalone, terminais de parafuso |
| 3RB2011 + 3UF18 | 630–820A | T14 | Class10E | 3TF68/3TF69 | CT combination solution |
- 3RB21 Series List (With Remote Reset A3/A4)
Suitable for PLC remote reset; protection functions and current ranges same as 3RB20
| 3RB2156-1FC2 | 50-200UM | S6 | Class10E | Remote reset, snap-on, terminais de parafuso |
| 3RB2156-1FF2 | 50-200UM | S6 | Class10E | Remote reset, autônomo, terminais de parafuso |
| 3RB2156-2FC2 | 50-200UM | S6 | Class20E | Serviço pesado + reinicialização remota |
| 3RB2166-1GC2 | 55-250UM | S10 | Class10E | S10 remote reset |
| 3RB2166-1MC2 | 160-630UM | T12 | Class10E | S12 remote reset |
| 3RB2166-2GC2 | 55-250UM | S10 | Class20E | S10 heavy duty + reinicialização remota |
| 3RB2166-2MC2 | 160-630UM | T12 | Class20E | S12 heavy duty + reinicialização remota |
| 3RB2111 + 3UF18 | 630-820UM | T14 | Class10E | CT combination, reinicialização remota |
- Common Series Parameters
- Auxiliary supply: A1/A2, AC/DC 24V or AC110~240V (depends on sub-version). Protection fails when supply is lost
- Contatos auxiliares: 95-96 (NC), 97-98 (NÃO), 1NÃO+1NC, 5Uma classificação
- Reiniciar: M/A DIP switch (manual / auto reset); 3RB21 adds A3/A4 remote reset
- Classe de proteção: IP20; Insulation voltage 1000V AC, impulse withstand voltage 8kV; Operating temperature -25~+60℃
- Circuito principal: Conexão de barramento, not through-core CT type
- Aplicativo: Standard 3-phase asynchronous motors; Not recommended directly on VFD output; harmonics cause false tripping
- New Generation Replacement Series (Recomendado para novos projetos)
S6 50-200A replacement: 3RB3056 (nova geração, melhor estabilidade, active supply)
S10/S12 high-current: 3RB3066 for equivalent replacement
- Guia de seleção rápida
No remote reset required → 3RB20
PLC remote reset required → 3RB21
Ventiladores padrão, bombas, smooth start → Class10E (prefixo 1)
Transportadores de correia, trituradores, heavy-duty long start → Class20E (prefixo 2)
Snap-on mounting with contactor → FC2 / GC2 / MC2
Separate backplate mounting → FF2 / GF2 / MF2