3VA1 series MCCB, 3 postes, frame current 160A, rated current 80A, breaking capacity 25kA@415V (Type N), thermal-magnetic trip unit TM240, adjustable overload protection 56–80A, adjustable short-circuit protection 5–10×In, fixed mounting, front connection.
- Explicação do código do modelo
| Segmento de código | Descrição |
| 3VA1 | Série de produtos: 3VA1 series MCCB (thermal‑magnetic trip, standard application) |
| 180 | Frame current: 160UM (IEC Frame 160) |
| 3 | Número de pólos: 3 postes |
| EF | Tipo de viagem: TM240 thermal‑magnetic trip unit, ATAM adjustable overload and short‑circuit protection |
| 32 | Configuração de acessórios: standard version with nut mounting kit |
| 0AA0 | Special function: no diagnostic function (0AB0 = with diagnostic function) |
- Detailed Technical Parameters
| Categoria de parâmetro | Valor |
| Especificações básicas | |
| Product type | Disjuntor em caixa moldada (MCCB), SENTRON series |
| Tensão operacional nominal (main circuit) | AC 690V, DC 250V |
| Tensão nominal de isolamento | 1000V CA/CC |
| Frame current (IEC Frame) | 160UM |
| Corrente nominal (Em) | 80UM |
| Número de pólos | 3 postes |
| Características de proteção | |
| Tipo de viagem | Thermal‑magnetic (TM240), ATAM |
| Proteção contra sobrecarga (E) | Ajustável, 56–80A |
| Short‑circuit protection (Ii) | Ajustável, 5–10×In |
| Ultimate breaking capacity (UTI) | 25kA @ 415V (Type N) |
| Service breaking capacity (CIs) | 50% de UTI (12.5kA @ 415V) |
| Mecânico & Instalação | |
| Tipo de montagem | Montagem fixa |
| Connection type | Conexão frontal, screw-type flat terminals |
| Operating type | Manual operation |
| Ingress protection | IP40 (front) |
| Temperatura ambiente | -25°C a +70°C (derating required at high temperatures) |
| Mechanical endurance | 10,000 operações (padrão) |
| Electrical endurance | 1,000 operações (at rated current) |
- Condições ambientais & Aplicações Típicas
- Condições ambientais
Low-voltage distribution systems in industrial plants, commercial buildings and infrastructure
Temperatura ambiente: -25°C a +70°C (derating according to curve in high-temperature environments)
Altitude: ≤ 2000m (derating above this altitude)
Grau de poluição: 2 (standard industrial environment)
- Aplicações Típicas
Distribution line protection (cables, transformadores, generators)
Motor control circuit protection (used with contactors)
Protection of low-voltage loads such as lighting and air conditioning
Main or branch protection in distribution boards and switchgear
- Modelos Alternativos & Series Equivalents
- Siemens Same-Series Alternatives
| Modelo | Principal diferença | Aplicativo |
| 3VA1180-3ED32-0AA0 | Fixed overload protection (80UM), FTFM | Simple applications without adjustable overload |
| 3VA1180-5EF32-0AA0 | Breaking capacity 55kA (Type M) | Systems with high short‑circuit current |
| 3VA1180-6EF32-0AA0 | Breaking capacity 70kA (Type H) | Industrial environments with high short‑circuit stress |
| 3VA1180-3EF42-0AA0 | 4‑pole design | Three‑phase four‑wire systems |
- Cross-Brand Alternatives
| Marca | Modelo de substituição | Compatibilidade |
| Schneider | NSX100N TMD 80 3P | Alto (25o, thermal‑magnetic trip) |
| ABB | T1N160 TMD 80/800 FF 3P | Alto (160Um quadro, 80A rated) |
| Chint | NZM1-160H/3P 80A | Médio (domestic equivalent, similar performance) |
| Delicioso | CW3-160N/3P 80A | Médio (domestic alternative, econômico) |
- Pedido & Notas de instalação
- Official order number: 3VA1180-3EF32-0AA0
- Installation precautions
Sufficient heat dissipation space must be reserved (≥10mm clearance)
Torque de aperto: M6 screws 10Nm, M8 screws 20Nm
Seção transversal do condutor: máx.. 17×6.5mm (copper bar) or 35mm² (cable)
- Compatibilidade de acessórios
Can be fitted with auxiliary contacts, contatos de alarme, viagem de manobra, liberação de subtensão
Supports extended rotary handles, door-coupled operating mechanisms
- Key Advantages
- Reliable protection: Thermal-magnetic trip provides dual overload and short-circuit protection, with adjustable ranges for various loads
- Flexible installation: Fixed mounting with front connection, compatible with standard switchgear and distribution boards
- Robust design: IP40 protection, 10,000 operações mecânicas, suitable for long-term industrial use
- Brand assurance: Siemens SENTRON series, compatível com IEC/EN 60947-2
Siemens MCCB Model List
- Core Series & Naming Rules
1.1 Main Product Series
Siemens MCCBs mainly include the 3VA series (nova geração) and 3VL/3VT series (legacy). The 3VA series covers frame currents from 100A to 1600A, divided into 3VA1 (viagem termomagnética) and 3VA2 (viagem eletrônica) sub-series.
1.2 3VA Series Naming Rule (Exemplo: 3VA1180-3EF32-0AA0)
| Segment | Código | Significado |
| 1 | 3VA1 | Série: 3VA1 = thermal‑magnetic, 3VA2 = electronic trip |
| 2 | 180 | Frame current: 100=100A, 160=160A, 250=250A, 400=400A, 630=630A |
| 3 | 3 | Poloneses: 1=1P, 2=2P, 3=3P, 4=4P |
| 4 | EF | Viagem + capacidade de interrupção: E=25kA, F=36kA, G=50kA, H=70kA, J=85kA; E=fixed thermal‑magnetic, F=adjustable thermal‑magnetic |
| 5 | 32 | Accessory: 3=standard, 4=with auxiliary contact, 5=with shunt trip |
| 6 | 0AA0 | Special function: 0AA0=no diagnostics, 0AB0=with diagnostics |
- Complete Model List-3VA1 Series (Thermal-Magnetic TM Trip)
2.1 100A Frame (3VA1100)
| Modelo | Corrente nominal | Poloneses | Trip Unit | Quebrando Capacidade |
| 3VA1100-3EE32-0AA0 | 63UM | 3P | TM220 (fixo) | 25kA@415V |
| 3VA1100-3EF32-0AA0 | 63UM | 3P | TM240 (ajustável) | 25kA@415V |
| 3VA1100-4EE32-0AA0 | 63UM | 4P | TM220 (fixo) | 25kA@415V |
| 3VA1100-5EF32-0AA0 | 80UM | 3P | TM240 (ajustável) | 36kA@415V |
2.2 160A Frame (3VA1160/3VA1180)
| Modelo | Corrente nominal | Poloneses | Trip Unit | Quebrando Capacidade |
| 3VA1180-3EE32-0AA0 | 80UM | 3P | TM220 (fixo) | 25kA@415V |
| 3VA1180-3EF32-0AA0 | 80UM | 3P | TM240 (adjustable 56–80A) | 25kA@415V |
| 3VA1180-4EF32-0AA0 | 80UM | 4P | TM240 (ajustável) | 25kA@415V |
| 3VA1180-5EF32-0AA0 | 80UM | 3P | TM240 (ajustável) | 36kA@415V |
| 3VA1180-6EF32-0AA0 | 80UM | 3P | TM240 (ajustável) | 50kA@415V |
| 3VA1160-3EF32-0AA0 | 63UM | 3P | TM240 (ajustável) | 25kA@415V |
2.3 250A Frame (3VA1250)
| Modelo | Corrente nominal | Poloneses | Trip Unit | Quebrando Capacidade |
| 3VA1250-3EE32-0AA0 | 160UM | 3P | TM220 (fixo) | 25kA@415V |
| 3VA1250-3EF32-0AA0 | 160UM | 3P | TM240 (adjustable 112–160A) | 25kA@415V |
| 3VA1250-4EF32-0AA0 | 160UM | 4P | TM240 (ajustável) | 25kA@415V |
| 3VA1250-5EF32-0AA0 | 200UM | 3P | TM240 (ajustável) | 36kA@415V |
2.4 400A Frame (3VA1400)
| Modelo | Corrente nominal | Poloneses | Trip Unit | Quebrando Capacidade |
| 3VA1400-3EE32-0AA0 | 250UM | 3P | TM220 (fixo) | 25kA@415V |
| 3VA1400-3EF32-0AA0 | 250UM | 3P | TM240 (adjustable 175–250A) | 25kA@415V |
| 3VA1400-4EF32-0AA0 | 250UM | 4P | TM240 (ajustável) | 25kA@415V |
| 3VA1400-6EF32-0AA0 | 315UM | 3P | TM240 (ajustável) | 50kA@415V |
2.5 630A Frame (3VA1630)
| Modelo | Corrente nominal | Poloneses | Trip Unit | Quebrando Capacidade |
| 3VA1630-3EE32-0AA0 | 400UM | 3P | TM220 (fixo) | 25kA@415V |
| 3VA1630-3EF32-0AA0 | 400UM | 3P | TM240 (adjustable 280–400A) | 25kA@415V |
| 3VA1630-4EF32-0AA0 | 400UM | 4P | TM240 (ajustável) | 25kA@415V |
| 3VA1630-7EF32-0AA0 | 500UM | 3P | TM240 (ajustável) | 70kA@415V |
- Typical Models-3VA2 Series (Electronic ETU Trip)
| Modelo | Quadro atual | Corrente nominal | Poloneses | Trip Unit | Quebrando Capacidade |
| 3VA2180-3MF32-0AA0 | 160UM | 80UM | 3P | ETU200 (ajustável) | 25kA@415V |
| 3VA2250-3MF32-0AA0 | 250UM | 160UM | 3P | ETU200 (ajustável) | 25kA@415V |
| 3VA2400-3MF32-0AA0 | 400UM | 250UM | 3P | ETU200 (ajustável) | 25kA@415V |
| 3VA2630-3MF32-0AA0 | 630UM | 400UM | 3P | ETU200 (ajustável) | 25kA@415V |
| 3VA2630-6MF32-0AA0 | 630UM | 500UM | 3P | ETU200 (ajustável) | 50kA@415V |
- Popular Models-Legacy Series (3VL/3VT)
| Série | Modelo | Quadro atual | Corrente nominal | Poloneses | Quebrando Capacidade |
| 3VL | 3VL1701-1DD33-0AA0 | 160UM | 80UM | 3P | 25kA@415V |
| 3VL | 3VL2701-1DD33-0AA0 | 250UM | 160UM | 3P | 25kA@415V |
| 3VL | 3VL3701-1DD33-0AA0 | 400UM | 250UM | 3P | 25kA@415V |
| 3VT | 3VT8106-1AA03-0AA0 | 160UM | 63UM | 3P | 25kA@415V |
| 3VT | 3VT8207-1AA03-0AA0 | 250UM | 100UM | 3P | 25kA@415V |
- Selection Parameter Reference Table
| Quadro atual | Faixa atual nominal | Classe de Capacidade de Quebra | Tipo de viagem | Typical Application |
| 100UM | 16–100A | 25–85kA | TM220/TM240 | Lighting, motores pequenos |
| 160UM | 16–160A | 25–85kA | TM220/TM240 | Branch distribution, medium motors |
| 250UM | 100–250A | 25–85kA | TM240 | Main distribution, large motors |
| 400UM | 250–400A | 25–85kA | TM240/ETU200 | Main switch in distribution panels |
| 630UM | 400–630A | 25–85kA | TM240/ETU200 | Substations, main factory distribution |
- Pedido & Purchasing Tips
- Complete model: Provide full model code as shown (por exemplo, 3VA1180-3EF32-0AA0), including all six segments
- Accessory options: Contatos auxiliares (-4XX), shunt trips (-5XX), liberações de subtensão (-6XX), etc..
- Tipo de montagem: Fixed by default; specify plug-in type if required (-XX4X)
- Authorized channels: Purchase through Siemens authorized distributors or industrial platforms to ensure genuine products and warranty
Contator,disjuntor,inversor solar,medidor elétrico,baterias solares




















NH42-63-318x560.png)